Direct liquid cooling supply water temperature in the HAWK supercomputer: a facility-level power and thermal model
Original title Operational analysis of the cooling system in a direct liquid-cooled data center: a measurement and simulation study on the impact of supply water temperature
Applied Energy (Elsevier BV) · Mashhur Gheni, Henner Kerskes et al.
An Applied Energy paper showing, from 21 months of HAWK supercomputer data, that raising supply water from 17 to 25 °C cut liquid cooling power by 63.3% but raised IT power by about 3.15%.
On this page
Overview
The study analyses 21 months of operating data from the direct liquid-cooled HAWK supercomputer under different supply water temperatures. It then builds a facility-level power and thermal model that links liquid cooling, air cooling and IT.
At 19 °C outdoor wet-bulb, raising the supply temperature from 17 to 25 °C cut liquid cooling system power by 63.3%. The share of heat going to room air nearly doubled, from about 2.6% to 5.0%, and IT equipment power rose by about 3.15%.
The result shows the trade-off between cooling plant savings and the increased heat-to-air and IT power. Dynamic supply temperature control based on outdoor conditions shows significant saving potential.
Key points
- The data covers 21 months of operation of the direct liquid-cooled HAWK supercomputer.
- At 19 °C outdoor wet-bulb, raising supply from 17 to 25 °C cut liquid cooling power by 63.3%.
- The share of heat going to room air rose from about 2.6% to 5.0%.
- IT equipment power rose by about 3.15%.
- Dynamic supply temperature control tied to outdoor conditions shows significant saving potential.
Using it in design
- Optimise the supply temperature target against rising IT power and air-side load, not plant savings alone.
- At high supply temperature, check air cooling capacity against the larger air-side heat share.
- Include a dynamic supply temperature strategy driven by outdoor wet-bulb in the control design.
Who should read it
Mechanical engineers and operations teams designing liquid-cooled HPC and AI facilities.
Publication details
- Authors
- Mashhur Gheni; Henner Kerskes; Konstantinos Stergiaropoulos
- Publisher
- Applied Energy (Elsevier BV)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Mashhur Gheni; Henner Kerskes; Konstantinos Stergiaropoulos (2026). Operational analysis of the cooling system in a direct liquid-cooled data center: a measurement and simulation study on the impact of supply water temperature. Applied Energy (Elsevier BV). https://doi.org/10.1016/j.apenergy.2025.127061
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.