Direct liquid cooling supply water temperature in the HAWK supercomputer: a facility-level power and thermal model

Original title Operational analysis of the cooling system in a direct liquid-cooled data center: a measurement and simulation study on the impact of supply water temperature

Applied Energy (Elsevier BV) · Mashhur Gheni, Henner Kerskes et al.

An Applied Energy paper showing, from 21 months of HAWK supercomputer data, that raising supply water from 17 to 25 °C cut liquid cooling power by 63.3% but raised IT power by about 3.15%.

On this page

Overview

The study analyses 21 months of operating data from the direct liquid-cooled HAWK supercomputer under different supply water temperatures. It then builds a facility-level power and thermal model that links liquid cooling, air cooling and IT.

At 19 °C outdoor wet-bulb, raising the supply temperature from 17 to 25 °C cut liquid cooling system power by 63.3%. The share of heat going to room air nearly doubled, from about 2.6% to 5.0%, and IT equipment power rose by about 3.15%.

The result shows the trade-off between cooling plant savings and the increased heat-to-air and IT power. Dynamic supply temperature control based on outdoor conditions shows significant saving potential.

Key points

  1. The data covers 21 months of operation of the direct liquid-cooled HAWK supercomputer.
  2. At 19 °C outdoor wet-bulb, raising supply from 17 to 25 °C cut liquid cooling power by 63.3%.
  3. The share of heat going to room air rose from about 2.6% to 5.0%.
  4. IT equipment power rose by about 3.15%.
  5. Dynamic supply temperature control tied to outdoor conditions shows significant saving potential.

Using it in design

  • Optimise the supply temperature target against rising IT power and air-side load, not plant savings alone.
  • At high supply temperature, check air cooling capacity against the larger air-side heat share.
  • Include a dynamic supply temperature strategy driven by outdoor wet-bulb in the control design.

Who should read it

Mechanical engineers and operations teams designing liquid-cooled HPC and AI facilities.

Publication details

Authors
Mashhur Gheni; Henner Kerskes; Konstantinos Stergiaropoulos
Publisher
Applied Energy (Elsevier BV)
Year
2026
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Mashhur Gheni; Henner Kerskes; Konstantinos Stergiaropoulos (2026). Operational analysis of the cooling system in a direct liquid-cooled data center: a measurement and simulation study on the impact of supply water temperature. Applied Energy (Elsevier BV). https://doi.org/10.1016/j.apenergy.2025.127061

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.