Ventilation condition effects on heat dissipation of the lithium-ion battery energy storage cabin fire
Case Studies in Thermal Engineering (Elsevier BV) · Jie Wang, Meilin Yang et al.
A 2024 Case Studies in Thermal Engineering numerical study: combined mechanical and natural ventilation lowers average cabin temperature by about 20 C, a top-centre exhaust vent cuts peak temperature from 810 C to 620 C, and 6 m/s gives 62.17% heat dissipation efficiency.
On this page
Overview
The study notes that the high energy density of lithium-ion batteries means a lot of heat, smoke and toxic gas is produced rapidly in thermal runaway and accumulates at extreme cabin temperature, so an energy storage cabin needs efficient ventilation for fire safety. It investigates numerically the effects of ventilation mode, position and speed on heat dissipation inside the cabin.
Results indicate that under an optimal ventilation condition the cabin can achieve excellent heat dissipation efficiency. When mechanical and natural ventilation are combined for smoke evacuation, the average cabin temperature falls by about 20 C. With an exhaust vent at the top centre of the cabin, the maximum temperature falls from 810 C to 620 C. As ventilation velocity rises from 1 m/s to 10 m/s, average cabin temperature decreases linearly; at 6 m/s the average temperature can be held at about 40 to 80 C and heat dissipation efficiency reaches 62.17%.
Key points
- Combining mechanical and natural ventilation lowers average cabin temperature by about 20 C.
- A top-centre exhaust vent cuts maximum temperature from 810 C to 620 C.
- Average temperature falls linearly as ventilation velocity rises from 1 to 10 m/s.
- At 6 m/s average temperature stays at about 40 to 80 C with 62.17% heat dissipation efficiency.
- Variables studied: ventilation mode, vent position and speed.
Using it in design
- Plan mechanical and natural ventilation together for smoke evacuation in a battery container or cabin.
- Position the exhaust vent at the top centre of the cabin and verify with numerical analysis for your own geometry.
- Select ventilation velocity (for example 6 m/s) by calculating heat dissipation efficiency and target cabin temperature.
- Define the combined operating logic of ventilation and suppression (fans, dampers) at design stage.
Who should read it
Engineers designing ventilation and fire safety for battery energy storage cabins and containers.
Publication details
- Authors
- Jie Wang; Meilin Yang; Kaihua Lu
- Publisher
- Case Studies in Thermal Engineering (Elsevier BV)
- Year
- 2024
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY-NC 4.0: share with attribution for noncommercial purposes
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by-nc/4.0/ (OpenAlex: cc-by-nc); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Non-commercial licence: link/cite only in a commercial product.
Citation
Jie Wang; Meilin Yang; Kaihua Lu (2024). Ventilation condition effects on heat dissipation of the lithium-ion battery energy storage cabin fire. Case Studies in Thermal Engineering (Elsevier BV). https://doi.org/10.1016/j.csite.2024.105373
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.