Energy-saving and economic analysis of the data center cooling system using magnetic bearing chillers under different climate conditions
Case Studies in Thermal Engineering (Elsevier BV) · Yuande Dai, Jin Liu et al.
A 2024 Case Studies in Thermal Engineering study retrofits a Nanchang data center with water-side economizers and centrifugal or magnetic-bearing chillers: 63.19% and 64.54% energy savings and PUE cuts of 0.341 and 0.349.
On this page
Overview
The study starts from the point that magnetic-bearing chillers have excellent COP but high first cost, making it hard to balance energy saving and economics. Two water-side economizer retrofits are proposed to replace the existing cooling system of a case data center in Nanchang: Plan 1 with efficient centrifugal chillers and Plan 2 with magnetic-bearing chillers. Energy models are built for the three cooling systems.
Results show full and partial free cooling operation of 2,489 and 1,324 hours for Plan 1 and Plan 2. Energy savings are 63.19% and 64.54%, with PUE reductions of 0.341 and 0.349. Plan 2's annual chiller COP is 6.7% higher than Plan 1's and saves a further 3.96% of annual energy.
The study also discusses energy savings and economics in five typical climate cities in China: savings are 61.4% to 64.7% for Plan 1 and 62.1% to 65.6% for Plan 2, with dynamic payback periods of 2.02 to 5.15 years and 2.16 to 5.6 years respectively.
Key points
- Case: the cooling system of a Nanchang data center is retrofitted with two water-side economizer plans (Plan 1 centrifugal, Plan 2 magnetic-bearing chillers).
- Full and partial free cooling operation is 2,489 hours for Plan 1 and 1,324 hours for Plan 2.
- Energy savings versus the existing system are 63.19% (Plan 1) and 64.54% (Plan 2); PUE reductions are 0.341 and 0.349.
- Plan 2's annual chiller COP is 6.7% higher and saves a further 3.96% annual energy versus Plan 1.
- Across five climate cities savings are 61.4% to 64.7% (Plan 1) and 62.1% to 65.6% (Plan 2).
- Dynamic payback is 2.02 to 5.15 years for Plan 1 and 2.16 to 5.6 years for Plan 2.
Using it in design
- Evaluate the water-side economizer and chiller type together; weigh the extra saving of magnetic-bearing chillers (about 4%) against the first-cost difference.
- Calculate climate-based free cooling hours and payback for your own city; the study shows a 2 to 5.6 year range.
- In retrofits, build an energy model of the existing system and compare both plans on the same model.
- The results are for Chinese climate cities; do not transfer them directly to other climates.
Who should read it
Engineers retrofitting an existing data center cooling plant and comparing chiller technology and economizer options on economics.
Publication details
- Authors
- Yuande Dai; Jin Liu; Sikai Zou
- Publisher
- Case Studies in Thermal Engineering (Elsevier BV)
- Year
- 2024
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY-NC-ND 4.0: share unaltered with attribution for noncommercial purposes
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by-nc-nd/4.0/ (OpenAlex: cc-by-nc-nd); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Non-commercial licence: link/cite only in a commercial product.
Citation
Yuande Dai; Jin Liu; Sikai Zou (2024). Energy-saving and economic analysis of the data center cooling system using magnetic bearing chillers under different climate conditions. Case Studies in Thermal Engineering (Elsevier BV). https://doi.org/10.1016/j.csite.2024.104915
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.