Energy-saving and economic analysis of the data center cooling system using magnetic bearing chillers under different climate conditions

Case Studies in Thermal Engineering (Elsevier BV) · Yuande Dai, Jin Liu et al.

A 2024 Case Studies in Thermal Engineering study retrofits a Nanchang data center with water-side economizers and centrifugal or magnetic-bearing chillers: 63.19% and 64.54% energy savings and PUE cuts of 0.341 and 0.349.

On this page

Overview

The study starts from the point that magnetic-bearing chillers have excellent COP but high first cost, making it hard to balance energy saving and economics. Two water-side economizer retrofits are proposed to replace the existing cooling system of a case data center in Nanchang: Plan 1 with efficient centrifugal chillers and Plan 2 with magnetic-bearing chillers. Energy models are built for the three cooling systems.

Results show full and partial free cooling operation of 2,489 and 1,324 hours for Plan 1 and Plan 2. Energy savings are 63.19% and 64.54%, with PUE reductions of 0.341 and 0.349. Plan 2's annual chiller COP is 6.7% higher than Plan 1's and saves a further 3.96% of annual energy.

The study also discusses energy savings and economics in five typical climate cities in China: savings are 61.4% to 64.7% for Plan 1 and 62.1% to 65.6% for Plan 2, with dynamic payback periods of 2.02 to 5.15 years and 2.16 to 5.6 years respectively.

Key points

  1. Case: the cooling system of a Nanchang data center is retrofitted with two water-side economizer plans (Plan 1 centrifugal, Plan 2 magnetic-bearing chillers).
  2. Full and partial free cooling operation is 2,489 hours for Plan 1 and 1,324 hours for Plan 2.
  3. Energy savings versus the existing system are 63.19% (Plan 1) and 64.54% (Plan 2); PUE reductions are 0.341 and 0.349.
  4. Plan 2's annual chiller COP is 6.7% higher and saves a further 3.96% annual energy versus Plan 1.
  5. Across five climate cities savings are 61.4% to 64.7% (Plan 1) and 62.1% to 65.6% (Plan 2).
  6. Dynamic payback is 2.02 to 5.15 years for Plan 1 and 2.16 to 5.6 years for Plan 2.

Using it in design

  • Evaluate the water-side economizer and chiller type together; weigh the extra saving of magnetic-bearing chillers (about 4%) against the first-cost difference.
  • Calculate climate-based free cooling hours and payback for your own city; the study shows a 2 to 5.6 year range.
  • In retrofits, build an energy model of the existing system and compare both plans on the same model.
  • The results are for Chinese climate cities; do not transfer them directly to other climates.

Who should read it

Engineers retrofitting an existing data center cooling plant and comparing chiller technology and economizer options on economics.

Publication details

Authors
Yuande Dai; Jin Liu; Sikai Zou
Publisher
Case Studies in Thermal Engineering (Elsevier BV)
Year
2024
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY-NC-ND 4.0: share unaltered with attribution for noncommercial purposes
Original licence note

Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by-nc-nd/4.0/ (OpenAlex: cc-by-nc-nd); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Non-commercial licence: link/cite only in a commercial product.

Citation

Yuande Dai; Jin Liu; Sikai Zou (2024). Energy-saving and economic analysis of the data center cooling system using magnetic bearing chillers under different climate conditions. Case Studies in Thermal Engineering (Elsevier BV). https://doi.org/10.1016/j.csite.2024.104915

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.