Performance optimization and energy analysis of a proposed data center dual-mode air source cooling system on the mode change temperature

Case Studies in Thermal Engineering (Elsevier BV) · Nicholas Lamptey Boafo, Samuel Boahen et al.

A 2025 Case Studies in Thermal Engineering paper raises the mode change temperature from 9.5 °C to 12.5 °C with ambient-air mixing and finds about 37% annual energy saving over the conventional system.

On this page

Overview

The study proposes a novel ambient air mixing control strategy that raises the mode change temperature (MCT) and extends the free cooling period of a hybrid air-source data-centre cooling system. The system's energy performance is assessed experimentally, and a comparison with a conventional hybrid system is simulated in EnergyPlus for the climate of Chuncheon, South Korea. The variables are outdoor air temperature and intake air volume.

The conventional system's MCT stays constant at 8.6 °C, while the proposed system's MCT rises from 9.5 °C to 12.5 °C as outdoor temperature falls from 24 °C to 15 °C and intake air rises from 5% to 30%. This extends free cooling and gives an annual energy saving of 37% over the conventional system. The study shows that control strategy, not just equipment, sets free-cooling hours.

Key points

  1. Proposed strategy: ambient air mixing to raise the mode change temperature (MCT).
  2. The conventional system's MCT is fixed at 8.6 °C.
  3. In the proposed system MCT rises from 9.5 °C to 12.5 °C (outdoor 24 to 15 °C, intake air 5% to 30%).
  4. The extended free-cooling period gives about 37% annual energy saving.
  5. Climate data: Chuncheon, South Korea; EnergyPlus simulation and experiment.

Using it in design

  • In hybrid air-source cooling systems, design the mode changeover temperature as a control curve tied to outdoor temperature and intake air fraction, not a fixed value.
  • Simulate free-cooling hours with control strategy variants before selecting equipment.
  • Include the humidity and filtration effect of outdoor air mixing in the control design.
  • Recompute the results with local climate data.

Who should read it

Engineers designing hybrid and free-cooled data-centre cooling systems and their control strategies.

Publication details

Authors
Nicholas Lamptey Boafo; Samuel Boahen; Jong Min Choi
Publisher
Case Studies in Thermal Engineering (Elsevier BV)
Year
2025
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY-NC-ND 4.0: share unaltered with attribution for noncommercial purposes
Original licence note

Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by-nc-nd/4.0/ (OpenAlex: cc-by-nc-nd); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Non-commercial licence: link/cite only in a commercial product.

Citation

Nicholas Lamptey Boafo; Samuel Boahen; Jong Min Choi (2025). Performance optimization and energy analysis of a proposed data center dual-mode air source cooling system on the mode change temperature. Case Studies in Thermal Engineering (Elsevier BV). https://doi.org/10.1016/j.csite.2025.106957

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.