Numerical analysis of rack-based data center cooling with rear door heat exchanger (RDHx): Interrelationship between thermal performance and energy efficiency

Case Studies in Thermal Engineering (Elsevier BV) · Jinkyun Cho

A 2024 Case Studies in Thermal Engineering study shows RDHx keeps a 150 kW IT module within ASHRAE limits at 24 °C supply air, with annual cooling PUE of 1.25 to 1.33 (average 1.27) for a 30 MW plant.

On this page

Overview

The study presents a numerical analysis of the thermal performance, energy efficiency and IT operating environment of the RDHx system, a rack-based solution for high-density IT power using air-cooled equipment. A 150 kW IT module and RDHx cooling system are designed and evaluated. CFD analysis confirms that the IT environment stays within ASHRAE standards at a supply air temperature of 24 °C.

The chilled water supply for the secondary CDU can be raised to 14 °C, and for the primary chiller to 12 °C. A central chilled water system for a 30 MW reference data center is designed and analyzed; efficiency rises with a 12 °C supply and varying condenser water return temperatures in winter. Annual cooling PUE ranges from 1.25 to 1.33, averaging 1.27.

For rack-based cooling, annual energy use splits about 46% chillers, 21% fans and 33% pumps. The author names validation through a field mock-up test of the 150 kW IT module as future work.

Key points

  1. For a 150 kW IT module, RDHx keeps the IT environment within ASHRAE limits at 24 °C supply air (CFD).
  2. Secondary CDU chilled water supply can rise to 14 °C and the primary chiller supply to 12 °C.
  3. 30 MW reference data center: annual cooling PUE 1.25 to 1.33, average 1.27.
  4. Annual cooling energy split: about 46% chillers, 21% fans, 33% pumps.
  5. Results are numerical; field mock-up validation is stated as future work.

Using it in design

  • For high-density air-cooled racks, evaluate RDHx with 24 °C supply air against the ASHRAE recommended band.
  • Calculate how raising chiller supply to 12 °C and CDU water to 14 °C adds free cooling hours.
  • Note that pump energy (33%) exceeds fan energy (21%) and optimize pump and ΔT design accordingly.
  • Use the 1.25 to 1.33 cooling PUE range as a reference for early sizing and verify against site results.

Who should read it

Mechanical engineers sizing rear door cooling and central chilled water plants for high-density racks.

Related standards

  • ASHRAE TC 9.9 thermal guidelines

Publication details

Authors
Jinkyun Cho
Publisher
Case Studies in Thermal Engineering (Elsevier BV)
Year
2024
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY-NC 4.0: share with attribution for noncommercial purposes
Original licence note

Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by-nc/4.0/ (OpenAlex: cc-by-nc); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Non-commercial licence: link/cite only in a commercial product.

Citation

Jinkyun Cho (2024). Numerical analysis of rack-based data center cooling with rear door heat exchanger (RDHx): Interrelationship between thermal performance and energy efficiency. Case Studies in Thermal Engineering (Elsevier BV). https://doi.org/10.1016/j.csite.2024.105247

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.