Numerical analysis of rack-based data center cooling with rear door heat exchanger (RDHx): Interrelationship between thermal performance and energy efficiency
Case Studies in Thermal Engineering (Elsevier BV) · Jinkyun Cho
A 2024 Case Studies in Thermal Engineering study shows RDHx keeps a 150 kW IT module within ASHRAE limits at 24 °C supply air, with annual cooling PUE of 1.25 to 1.33 (average 1.27) for a 30 MW plant.
On this page
Overview
The study presents a numerical analysis of the thermal performance, energy efficiency and IT operating environment of the RDHx system, a rack-based solution for high-density IT power using air-cooled equipment. A 150 kW IT module and RDHx cooling system are designed and evaluated. CFD analysis confirms that the IT environment stays within ASHRAE standards at a supply air temperature of 24 °C.
The chilled water supply for the secondary CDU can be raised to 14 °C, and for the primary chiller to 12 °C. A central chilled water system for a 30 MW reference data center is designed and analyzed; efficiency rises with a 12 °C supply and varying condenser water return temperatures in winter. Annual cooling PUE ranges from 1.25 to 1.33, averaging 1.27.
For rack-based cooling, annual energy use splits about 46% chillers, 21% fans and 33% pumps. The author names validation through a field mock-up test of the 150 kW IT module as future work.
Key points
- For a 150 kW IT module, RDHx keeps the IT environment within ASHRAE limits at 24 °C supply air (CFD).
- Secondary CDU chilled water supply can rise to 14 °C and the primary chiller supply to 12 °C.
- 30 MW reference data center: annual cooling PUE 1.25 to 1.33, average 1.27.
- Annual cooling energy split: about 46% chillers, 21% fans, 33% pumps.
- Results are numerical; field mock-up validation is stated as future work.
Using it in design
- For high-density air-cooled racks, evaluate RDHx with 24 °C supply air against the ASHRAE recommended band.
- Calculate how raising chiller supply to 12 °C and CDU water to 14 °C adds free cooling hours.
- Note that pump energy (33%) exceeds fan energy (21%) and optimize pump and ΔT design accordingly.
- Use the 1.25 to 1.33 cooling PUE range as a reference for early sizing and verify against site results.
Who should read it
Mechanical engineers sizing rear door cooling and central chilled water plants for high-density racks.
Related standards
- ASHRAE TC 9.9 thermal guidelines
Publication details
- Authors
- Jinkyun Cho
- Publisher
- Case Studies in Thermal Engineering (Elsevier BV)
- Year
- 2024
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY-NC 4.0: share with attribution for noncommercial purposes
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by-nc/4.0/ (OpenAlex: cc-by-nc); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Non-commercial licence: link/cite only in a commercial product.
Citation
Jinkyun Cho (2024). Numerical analysis of rack-based data center cooling with rear door heat exchanger (RDHx): Interrelationship between thermal performance and energy efficiency. Case Studies in Thermal Engineering (Elsevier BV). https://doi.org/10.1016/j.csite.2024.105247
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.