Long-term field performance of an innovative dew point evaporative cooling system as a low-energy cooling solution for a live edge data Centre

Energy and Buildings (Elsevier BV) · Cheng Zeng, Zhichu Wang et al.

A 2026 Energy and Buildings paper gives the first full-year field data on dew point evaporative cooling in a live UK edge data centre: annual mean COP about 30, falling to about 18 in a hot July period.

On this page

Overview

The study by Zeng and colleagues notes that small edge data centres are expanding rapidly and, being embedded in existing building services, are cooled less efficiently than large purpose-built centres. To the authors' knowledge it is the first full-year field study of a dew point evaporative cooling (DPC) system operating within a building-integrated cooling arrangement in a live edge data centre. The system was assessed through performance mapping, full-year operational data, seasonal temperature profiles, hourly analysis and microbiological monitoring.

In normal operation the DPC system delivered humidity-neutral sensible cooling at stable, low electricity demand. Monthly average COP reached about 37 in September to November, with an annual mean of about 30. In a hot period in July COP fell to about 18 and supply air became warmer than return air; this was a system-level effect from heat gain in the plant enclosure and interaction with auxiliary cooling units, not a limit of the heat and mass exchanger itself. Water-side microbiological risk was controllable under a bespoke management protocol.

Key points

  1. The study is presented as the first full-year field study of a DPC system in a live UK edge data centre.
  2. Monthly average COP is about 37 in September to November and the annual mean about 30.
  3. In a hot July period COP fell to about 18 and supply air became warmer than return air.
  4. The drop is a system-level effect from plant enclosure heat gain and interaction with auxiliary units.
  5. Microbiological water-side risk is controllable under a bespoke management protocol.
  6. The system gives humidity-neutral sensible cooling at stable, low electricity demand.

Using it in design

  • When designing DPC for an edge data centre, look at plant enclosure heat gain and auxiliary cooling unit interaction, not only component COP.
  • Define the auxiliary cooling control strategy for hot periods separately.
  • Add microbiological monitoring and a management protocol for the water side to the operating plan.
  • Use the full-year seasonal profile as input to design performance estimates.

Who should read it

Mechanical engineers designing edge data centres and building-integrated cooling.

Publication details

Authors
Cheng Zeng; Zhichu Wang; Zishang Zhu; Sulaimon Sikiru; Xiaoli Ma; Xudong Zhao
Publisher
Energy and Buildings (Elsevier BV)
Year
2026
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Cheng Zeng; Zhichu Wang; Zishang Zhu; Sulaimon Sikiru; Xiaoli Ma; Xudong Zhao (2026). Long-term field performance of an innovative dew point evaporative cooling system as a low-energy cooling solution for a live edge data Centre. Energy and Buildings (Elsevier BV). https://doi.org/10.1016/j.enbuild.2026.118096

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.