Review of gas emissions from lithium-ion battery thermal runaway failure: Considering toxic and flammable compounds
Journal of Energy Storage (Elsevier BV) · Peter J. Bugryniec, Erik G. Resendiz et al.
A 2024 Journal of Energy Storage review: NMC cells generate larger specific off-gas volumes than other chemistries, LFP off-gas is more toxic and more flammable than NMC, and higher state of charge generally increases gas volume.
On this page
Overview
The review addresses the fire, explosion and toxicity hazards from the flammable and noxious gases lithium-ion batteries release during rare thermal runaway events. The authors say no comprehensive review of the topic existed. The work analyses literature data to determine how battery parameters affect the variation in off-gas volume and composition, and to determine the flammability and toxicity hazards of different chemistries.
On average it finds: NMC batteries generate larger specific off-gas volumes than other chemistries; prismatic cells tend to generate larger specific off-gas volumes than other cell forms; generally a higher state of charge (SOC) leads to greater specific gas volume; LFP batteries show greater toxicity than NMC; LFP is more toxic at lower SOC while NMC is more toxic at higher SOC; and LFP off-gas has a greater flammability hazard. The review also makes recommendations to advance research and is described as a critical resource for risk assessment of thermal runaway fire, explosion and toxicity hazards.
Key points
- NMC batteries on average generate larger specific off-gas volumes than other chemistries.
- Prismatic cells tend to generate larger specific off-gas volumes than other cell forms.
- Higher state of charge (SOC) generally leads to greater specific gas volume.
- LFP off-gas is more toxic than NMC and carries a greater flammability hazard.
- LFP is more toxic at lower SOC, NMC at higher SOC, each relative to itself.
Using it in design
- In battery room gas exhaust and detection design, account for specific gas volume and flammability differences by chemistry (NMC or LFP) and cell format.
- State toxicity and flammability differences for LFP and NMC separately in fire service and operating procedures.
- Include the effect of state of charge on gas volume in the fire risk assessment.
- Ask the manufacturer for chemistry-specific gas data for ventilation and explosion protection calculations.
Who should read it
Engineers designing battery room ventilation, gas detection and explosion protection, and risk assessors.
Related standards
- NFPA 855
Publication details
- Authors
- Peter J. Bugryniec; Erik G. Resendiz; Solomon M. Nwophoke; Simran Khanna; Charles James; Solomon F. Brown
- Publisher
- Journal of Energy Storage (Elsevier BV)
- Year
- 2024
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Peter J. Bugryniec; Erik G. Resendiz; Solomon M. Nwophoke; Simran Khanna; Charles James; Solomon F. Brown (2024). Review of gas emissions from lithium-ion battery thermal runaway failure: Considering toxic and flammable compounds. Journal of Energy Storage (Elsevier BV). https://doi.org/10.1016/j.est.2024.111288
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.