Techno-economic design and reliability assessment of a solar PV-battery-based green data center
Franklin Open (Elsevier BV) · Alok Kumar Shrivastav, Dipak Kumar Dash et al.
A 2025 study in Franklin Open benchmarks the reliability of a solar PV and battery storage data centre using capacity shortage and unmet load metrics, and reports that high reliability can be maintained without generator sets.
On this page
Overview
The study starts from rising data centre electricity use, carbon emissions and operational reliability concerns as digital infrastructure grows, and presents a techno-economic design framework for a sustainable data centre powered by solar photovoltaic (PV) and battery storage. The authors are Shrivastav, Dash, Dhara and Ghosh.
Reliability simulations assess power availability and downtime, with capacity shortage and unmet load as the key metrics. The proposed green data centre model is benchmarked against conventional designs and its performance evaluated against established tier reliability standards. Results show PV-battery systems can maintain high reliability, reduce greenhouse gas emissions and offer stable, competitive energy costs over time.
Key points
- Reliability is measured through capacity shortage and unmet load.
- The proposed model is benchmarked against conventional data centre designs.
- Performance is evaluated against established tier reliability standards.
- PV-battery systems can maintain high reliability and stable energy costs.
- The authors argue operational sustainability and reliability can be achieved without conventional generator sets.
Using it in design
- In renewable-powered data centre design, simulate power availability using capacity shortage and unmet load metrics.
- Compare PV and battery sizing with the reliability requirement of the target Tier level.
- Evaluate renewable-based backup as an alternative to standby generator sets on cost and emissions.
- For projects with carbon targets, consider the backup power strategy together with policy requirements.
Who should read it
Data centre designers and energy planners working on renewable energy and backup power strategy.
Related standards
- Uptime Institute Tier Standard
Publication details
- Authors
- Alok Kumar Shrivastav; Dipak Kumar Dash; Saumen Dhara; Pritish Ghosh
- Publisher
- Franklin Open (Elsevier BV)
- Year
- 2025
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Alok Kumar Shrivastav; Dipak Kumar Dash; Saumen Dhara; Pritish Ghosh (2025). Techno-economic design and reliability assessment of a solar PV-battery-based green data center. Franklin Open (Elsevier BV). https://doi.org/10.1016/j.fraope.2025.100290
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.