Research paperFree to read2026

Beyond PUE: An integrated scenario assessment of electricity, cooling, polymer–elastomer demand, carbon, and circularity in AI data centers

Results in Engineering (Elsevier BV) · Masoumeh Bararzadeh Ledari, Seyed Mohammad Shirafkan

A 2026 scenario study in Results in Engineering finds global data-centre electricity rising from 416 TWh in 2024 to 707-1,719 TWh in 2035 and argues PUE alone cannot assess AI facilities.

On this page

Overview

The study is a scenario framework for 2024 to 2035 that links AI electricity pathways, H100 node calibration, facility load, the transition from air cooling to direct-to-chip and immersion, polymer and elastomer demand, operational carbon and circularity. Its central argument is that PUE alone cannot assess AI data centres.

Depending on scenario, global data-centre electricity rises from 416 TWh in 2024 to between 707 and 1,719 TWh in 2035. PUE improves to 1.13-1.22 by 2035, but infrastructure growth outweighs efficiency gains. In the base pathway, cooling electricity is 123.1 TWh and the plastics proxy 344.8 kt in 2035. Stronger liquid-cooling adoption lowers cooling electricity but raises material intensity.

Key points

  1. Global data-centre electricity rises from 416 TWh in 2024 to 707-1,719 TWh in 2035 depending on scenario.
  2. PUE improves to 1.13-1.22 by 2035; infrastructure growth dominates efficiency gains.
  3. In the base pathway, 2035 cooling electricity is 123.1 TWh.
  4. In the base pathway, the 2035 plastics proxy is 344.8 kt.
  5. Stronger liquid cooling lowers cooling electricity and raises material intensity.

Using it in design

  • When choosing cooling technology (air, direct-to-chip, immersion), compare electricity, material intensity and carbon together, not PUE alone.
  • Reflect in the materials and procurement plan that moving to liquid cooling cuts cooling electricity while increasing polymer and elastomer demand.
  • Plan AI capacity growth with total electricity demand scenarios independent of PUE improvement.
  • Add absolute electricity, operational carbon and circularity indicators next to PUE in the reporting set.

Who should read it

Designers and decision makers setting cooling technology, capacity and sustainability strategy for AI data centres.

Related standards

  • ISO/IEC 30134-2 (PUE)

Publication details

Authors
Masoumeh Bararzadeh Ledari; Seyed Mohammad Shirafkan
Publisher
Results in Engineering (Elsevier BV)
Year
2026
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Publisher-deposited Crossref licence metadata: http://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by-nc-nd); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Crossref says CC BY but OpenAlex lists CC BY-NC-ND; kept non-redistributable until checked manually.

Citation

Masoumeh Bararzadeh Ledari; Seyed Mohammad Shirafkan (2026). Beyond PUE: An integrated scenario assessment of electricity, cooling, polymer–elastomer demand, carbon, and circularity in AI data centers. Results in Engineering (Elsevier BV). https://doi.org/10.1016/j.rineng.2026.113927

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.