Emicon 2018 Product Overview: IR In-Row Technical Table

Original title Emicon 2018 product overview, IR technical table, PDF p.11

Emicon

Emicon's 2018 product guide with the IR in-row cooler table for 10-25 kW units: at 35 °C inside and outside, total capacity 10.2-24 kW, sensible 9.2-21.6 kW, SHR 90%.

On this page

Overview

The document is the 2018 product guide of the Italian manufacturer Emicon, published in Spanish. It presents precision air conditioners (CED), air- and water-cooled chillers, heat pumps, rooftop units and custom-built equipment, and also describes the maker's acoustic and performance test rooms, its environmental policy and reference projects, including a 3800 kW university installation and a 1032 kW telecom site.

In the technical part the precision-cooling family is offered as direct-expansion ED.X (air-cooled), ED.H (water-cooled) and ED.E (remote condenser) versions across 6.7-138 kW. For the IR in-row series the table gives the performance of 300 mm wide units placed between hot and cold aisles at 35 °C outdoor, 35 °C indoor and 30% relative humidity.

The IR 10, 15, 20 and 25 models deliver total cooling of 10.2, 15.3, 21.0 and 24.0 kW, sensible capacity of 9.2, 13.8, 18.9 and 21.6 kW and electrical input of 4.45, 6.60, 9.00 and 11.00 kW. Nominal airflow is 2500-4500 m3/h. The difference between sensible and net sensible capacity is not defined.

The document is a product brochure that keeps the table of the older IR series. Current ordering status and detailed selection must be confirmed with the manufacturer; the table serves for pre-sizing and model comparison.

Key points

  1. The in-row table lists four models, IR 10, 15, 20, 25; each unit is 300 mm long.
  2. Test condition: 35 °C outdoor, 35 °C indoor, 30% relative humidity.
  3. Total cooling 10.2 / 15.3 / 21.0 / 24.0 kW; sensible 9.2 / 13.8 / 18.9 / 21.6 kW.
  4. Electrical input 4.45 / 6.60 / 9.00 / 11.00 kW; SHR is 90% on all four models.
  5. Nominal airflow 2500 / 3200 / 4000 / 4500 m3/h.
  6. ED.X, ED.H and ED.E precision units are direct-expansion and cover 6.7-138 kW.
  7. The air-cooled RAE chiller range covers 5-588.1 kW with scroll compressors and axial fans.
  8. The guide lists HFO 1234ze (GWP 6) and R290 (GWP 3) units in the catalogue.

Using it in design

  • When selecting in-row cooling, use sensible capacity and SHR, not only total capacity; the sensible figure in the table is not defined as net sensible (fan heat deducted).
  • Because the test condition is 35 °C indoor air, request capacity again from the maker for hot-aisle designs with a lower entering temperature.
  • Relate the electrical input (4.45-11 kW) to the load to include the PUE effect of in-row cooling.
  • Obtain confirmation of current ordering status and model code from the manufacturer; do not fix the old IR series into a new project directly.
  • Compare airflow (2500-4500 m3/h) with rack heat load to check the air balance.

Who should read it

HVAC designers comparing in-row cooling models and operators refurbishing legacy Emicon IR installations.

Document contents

  1. Evolution and Environment
  2. Emicon Laboratories
  3. Environmental Policy
  4. Reference Projects
  5. Precision Air Conditioners ED.X, ED.H, ED.E
  6. IR In-Row Unit Table
  7. Air-cooled Chillers RAE

Publication details

Authors
Emicon
Publisher
Emicon
Year
2018
Document language
Spanish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Emicon (2018). Emicon 2018 product overview, IR technical table, PDF p.11. Emicon. https://www.hidemgroup.com/wp-content/download/EMICON_product-overview-ESP.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.