Emicon RAS F Kp: Air-Cooled Chillers with R290 and Integrated Free Cooling

Original title Emicon RAS F Kp technical data, printed pp.48–49

Emicon

Emicon's RAS F Kp series are air-cooled chillers on R290 (propane) with an integrated free cooling coil: 54 to 350 kW, EER 2.65 to 3.08 at 35 °C air, and 26 to 119 kW free cooling at 3 °C air and 12 °C fluid.

On this page

Overview

The document is the catalog of Emicon's RAS F Kp series of air-cooled chillers for outdoor installation with semi-hermetic reciprocating compressors and axial fans. The series covers 54 to 350 kW cooling capacity and targets industrial applications or service-industry air-conditioning. The refrigerant is propane (R290); the units are designed as outdoor groups in compliance with EN 378 and updates, and are CE certified (2016/2281 ERP 2021).

The integrated free cooling section partly or fully recovers cooling capacity from outdoor air. An additional coil carrying the fluid to be chilled sits in the full airflow of the condenser fans. Free cooling starts as soon as the inlet air temperature is below the water returning from the plant; the benefit grows as outdoor air gets colder relative to the fluid. The units suit plants with medium to low outdoor temperatures and long cooling demand. Depending on capacity they have 1 or 2 independent circuits with 1 or 2 compressors per circuit (tandem).

The catalog describes the components: galvanized steel frame, a closed cabinet for compressors and the cooling circuit (on a refrigerant leak an external axial fan clears the cabinet air 4 times a minute), an R290 leak sensor, a stainless plate evaporator, micro-finned copper coils, 6-pole external-rotor fans and a regenerative heat exchanger. Technical tables cover models 521 to 3402 with capacity, EER, SEPR, refrigerant charge, water flow, free cooling capacity, dimensions, weights and sound data. Capacity is rated at 35 °C air and 12/7 °C water with 30% ethylene glycol; free cooling at 3 °C air and 12 °C fluid.

Key points

  1. Capacity range is 54 to 350 kW; tables give 50.9 to 332.6 kW at 35 °C air and 12/7 °C water with 30% ethylene glycol (models 521 to 3402).
  2. EER ranges from 2.65 (2402) to 3.08 (721 and 1402); SEPR 5.32 to 5.49 (521 to 1402).
  3. Refrigerant is R290 (propane); charge 4 to 24 kg, CO2 equivalent 12 to 72 kg.
  4. Free cooling capacity (3 °C air, 12 °C fluid) is 26.3 to 119.2 kW; 31.5 kW for the 521 and 119.2 kW for the 3402.
  5. Free cooling starts when inlet air is below the plant return water temperature; free cooling coil fluid side maximum pressure is 10 bar.
  6. Units have 1 or 2 independent circuits and 1 or 2 compressors per circuit (tandem); a differential pressure switch stops operation on low evaporator flow.
  7. R290 safety: the leak sensor stops compressors and starts the extraction fan; cabinet air is renewed 4 times per minute.
  8. Options: cooling mode down to -20 °C (BF), EC fans, FCN (compressor disabled in free cooling), BACnet, RS 485 and TCP/IP interfaces, evaporator antifreeze heater.
  9. Sound power is 88.9 to 94.7 dB(A) (521 to 1402) and sound pressure at 10 m 57.0 to 62.7 dB(A).

Using it in design

  • In medium to low outdoor temperature climates with long cooling demand, evaluate free cooling chillers; compute free cooling hours against fluid temperature (benefit grows with the fluid-to-ambient difference).
  • For data centers a warmer water temperature than 12/7 °C raises free cooling capacity and hours; have catalog values recalculated at your condition.
  • R290 is flammable; check EN 378 requirements, leak detection, ventilation and separation distances.
  • Compare sound power and pressure (for example 57 to 62.7 dB(A) at 10 m) with neighbour noise limits; consider the CFU and EC fan options.
  • Check chiller weight (1,088 to 1,776 kg, more for larger models) and 2420 mm height against roof or slab capacity.

Who should read it

Mechanical designers and consultants selecting low-GWP air-cooled chillers with free cooling.

Document contents

  1. Versions and general introduction
  2. Main components (frame, compressors, evaporator, coils, fans, regenerative exchanger, cooling circuit, electrical board)
  3. Accessories
  4. Technical data (models 521 to 3402)

Publication details

Authors
Emicon
Publisher
Emicon
Year
2024
Document number
RAS F Kp
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Emicon (2024). Emicon RAS F Kp technical data, printed pp.48–49. Emicon. RAS F Kp. https://www.emiconac.it/wp-content/uploads/2024/03/RAS-F-Kp_ENG.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.