TRANS-AMF Automatic Mains Failure Unit for Diesel/Gas Generators with J1939 ECUs: User Manual

EMKO Elektronik

The EMKO TRANS-AMF manual is the 73-page parameter, input-output and technical reference for a controller that starts a J1939-ECU generator and transfers load on mains failure.

On this page

Overview

The manual describes EMKO Elektronik's TRANS-AMF automatic mains failure (AMF) unit. The device detects loss of any mains phase or mains voltage moving outside preset limits, starts the generator and transfers the load from mains to generator. Automatic and manual control are available, and a test mode runs the generator without taking the load.

The unit calculates engine speed from a magnetic pickup input or the generator voltage signal, and monitors J1939 messages for remote start and stop. Supported ECUs include Volvo EMS2, Volvo EDC4, Perkins and standard messages. If the first start fails, attempts repeat a programmed number of times or until success; if a fault is detected, the engine is shut down and the message shown on the LCD.

Programming is done through front-panel buttons with two-level password protection or through the built-in USB port from a PC. Parameters are split into operator and technician groups; the technician group covers system, mains, generator, engine, inputs, outputs, timers, expansion modules and user adjustment. The configurable inputs and the six configurable outputs can be assigned many functions. The document is a 2011 product manual and is a setting and connection reference for the device, not a design standard. Its value lies in showing which protection, timer and communication options an AMF controller offers and which parameters commission them.

Key points

  1. The unit starts the generator and transfers load when a mains phase is lost or mains voltage leaves preset limits; test mode runs without load.
  2. J1939 ECU support: Volvo EMS2, Volvo EDC4, Perkins and standard messages; remote start and stop go over J1939.
  3. Configurable inputs 1, 4 and 5 offer 26 functions, the other four inputs 25, and the six configurable outputs 114 functions.
  4. Mains and generator voltage measurement is 3-300 VAC phase-neutral, 5-99.9 Hz, with 1% FS accuracy and 0.25% FS frequency accuracy.
  5. DC supply is 8-32 V at up to 360 mA; battery voltage may drop to zero for at most 50 ms during cranking.
  6. The magnetic pickup input covers 35-10000 Hz, the CT secondary is 5 A and sender measurement is 0-1300 ohm.
  7. Front panel protection is IP65, operating temperature -20 to +70 degrees C, rated for altitude below 2000 m and non-condensing humidity.
  8. An optional expansion module has 8 inputs and 8 outputs, with Ethernet, GSM/GPRS and dual set modules; warranty is 2 years.

Using it in design

  • When selecting an AMF controller, specify that the engine ECU is on the supported J1939 list and that the CAN line needs 120 ohm termination at both ends.
  • Record mains-failure detection thresholds and delays (voltage, frequency, transfer timers) in the design document alongside selectivity and load classes.
  • Check the battery and cranking circuit against the 8-32 V supply range and the 50 ms interruption limit.
  • Decide early whether remote monitoring needs USB, Ethernet or GSM modules and what BMS/SCADA interface is required.
  • Carry the 182 x 135 mm panel cut-out and IP65 front protection into the panel design.

Who should read it

Electrical engineers designing and commissioning generator control panels and specifying automatic transfer systems.

Document contents

  1. Introduction
  2. Installation
  3. Front Panel Description and Accessing Parameters
  4. Parameters (operator and technician)
  5. Specifications

Publication details

Authors
EMKO Elektronik
Publisher
EMKO Elektronik
Year
Year not stated
Document number
ENG TRANS-AMF 02 V01 11/11
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

EMKO-authored manual inspected on EMSA official generator support hosting. No redistribution permission established; metadata and original short summaries only. Document code does not independently establish publication year.

Citation

EMKO Elektronik TRANS-AMF Automatic Mains Failure Unit for Diesel/Gas Generators with J1939 ECUs: User Manual. EMKO Elektronik. ENG TRANS-AMF 02 V01 11/11. https://emsa.gen.tr/images/brochures/TECHNICAL%20DOCUMENTS/CONTROLLER%20DATASHEET/Emko/Emko%20Trans%20AMF%20Manual.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.