EMKO TRANS-SYNCRO Synchronisation and Load Sharing Panel: Product Page and FAQ

Original title TRANS-SYNCRO: Otomatik Start ve Yük Paylaşım Ünitesi: teknik açıklama ve sorular

EMKO Elektronik

EMKO TRANS-SYNCRO is a synchronising panel controller for up to 32 generators with kW and kVAr load sharing, dead-bus detection and CANopen communication; at 250 kbps the bus may be 250 m long.

On this page

Overview

The page presents EMKO Elektronik's TRANS-SYNCRO automatic start and load-sharing unit. The unit parallels several generators onto a bus and shares load automatically. Highlighted functions are kW and kVAr load sharing, bus voltage and frequency measurement, dead-bus detection, CANopen fault monitoring, sequential start by set value, equal ageing of generators, a logic controller for PLC use and SNMP for Ethernet.

The technical table lists 13 configurable digital inputs, 4 resistive inputs, magnetic pickup and charge-alternator inputs, 2 relay outputs, 7 transistor outputs and a generator contactor output. Three-phase generator and three-phase bus voltages are measured at 3-300 VAC phase-neutral, 5-99.9 Hz with 1% FS accuracy, with harmonics monitored to the 11th. Supply is 8-32 VDC and the front panel is NEMA 4X IP65.

The FAQ states that two or more generators can be synchronised and load-shared with TRANS-SYNCRO, and that a TRANS-MAINS unit per mains source allows the generator-to-mains transfer to be open, closed or soft transition. The maximum CANopen line length depends on communication speed: 250 m at 250 kbps. The page is a product introduction and gives no capacity selection or commissioning settings.

Key points

  1. TRANS-SYNCRO supports load sharing among up to 32 generators.
  2. It offers kW and kVAr load sharing, bus voltage and frequency measurement, dead-bus detection and CANopen fault monitoring.
  3. Sequential start by set value and equal ageing of generators are included.
  4. Inputs: 13 configurable digital, 4 resistive (0-1300 ohm, 1% FS), magnetic pickup and charge alternator; outputs: 2 relays, 7 transistors and a generator contactor output.
  5. Voltage measurement is 3-300 VAC phase-neutral, 5-99.9 Hz, 1% FS accuracy, up to the 11th harmonic.
  6. Supply is 8-32 VDC at up to 360 mA; front panel NEMA 4X IP65; operating temperature -20 to +70 degrees C.
  7. Communication: USB, J1939 ECU, CANopen, Ethernet, RS485; optional embedded web server and serial Modbus.
  8. The CANopen line may be 250 m at 250 kbps; one TRANS-MAINS unit is used per mains source for transfer.

Using it in design

  • Plan the CANopen line length against the chosen baud rate; where a layout exceeds the 250 m limit at 250 kbps, lower the speed or change the topology.
  • Where soft transition to mains is required, add one TRANS-MAINS unit per mains source to the specification.
  • Set dead-bus detection and sequential start parameters together with load prioritisation and the redundancy (N+1) scenario.
  • Decide the Ethernet SNMP, Modbus and web server options early for BMS and SCADA integration.
  • In panel design, allow for the unit size (276 x 189 x 45 mm) and the IP65 front panel requirement.

Who should read it

Electrical engineers designing paralleled generator systems and synchronising panels, and panel builders.

Document contents

  1. Product features
  2. Technical specifications
  3. Downloads
  4. Frequently asked questions

Publication details

Authors
EMKO Elektronik
Publisher
EMKO Elektronik
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public source opened on the access date. No open redistribution licence established; metadata and original short summaries only. Download endpoint returned an application error instead of a PDF. This record is only the opened product/FAQ page and does not close the TRANS-SYNCRO full-manual gap. A current-measurement table row is mislabeled with voltage units and was not used.

Citation

EMKO Elektronik TRANS-SYNCRO: Otomatik Start ve Yük Paylaşım Ünitesi: teknik açıklama ve sorular. EMKO Elektronik. https://www.emkoelektronik.com.tr/tr/urunler/trans-syncro

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.