Short Circuit and Arc Flash Evaluations Using AmpSentry Capability - Part 1
Cummins · Rich Scroggins, Ravi Thapa
Cummins white paper 5544186 (2025): shows in an SKM model that AmpSentry maintenance mode cuts arc flash incident energy at the generator terminals from 75.2 cal/cm2 to 19.5 cal/cm2.
On this page
Overview
The white paper shows how to model AmpSentry, the overcurrent protection and fault-current regulating feature of Cummins PowerCommand controls, in SKM software. AmpSentry is UL listed as a protective relay, appears in SKM as a motor overload protective device, and its maintenance mode meets the NEC 240.87 arc flash mitigation requirement. The calculation relies only on AmpSentry and alternator characteristics; a breaker can additionally be shunt tripped.
Modelling steps: the genset is defined by rated voltage and kW, and alternator reactances and time constants from the data sheet go into the ANSI contribution menu using the 125 C kVA on which the data sheet is based. In the decrement curve the field current If is set to 3 x Xd x Ifg x (set kVA / alternator kVA) to reflect AmpSentry regulating fault current to 300% of rated. The arc flash calculation splits the fault into a subtransient (1/Xd'') period and a sustained, field-forced period and adds the incident energies of the two.
For maintenance mode the maximum arc duration is set to 50 ms for the control to sense the fault plus one alternator transient time constant (Td'); with Td' = 213 ms in the example this is 0.263 s. Normal mode uses 2 s. By the IEEE 1584 method incident energy at the generator terminals falls from 75.2 cal/cm2 to 19.5 cal/cm2. Shunt tripping a breaker also removes alternator winding contribution and limits energy downstream, but does not reduce energy inside the breaker's own enclosure unless its line-side terminals are isolated.
Key points
- AmpSentry is a UL-listed protective relay and its maintenance mode meets the NEC 240.87 arc flash mitigation requirement.
- AmpSentry regulates fault current to 300% of rated; in SKM it is modelled as If = 3 x Xd x Ifg x (set kVA / alternator kVA).
- Enter alternator reactances on the 125 C kVA basis of the data sheet; do not tick 'Link with Rated'.
- The arc flash calculation splits into subtransient and sustained periods; the transition is set by Td' (0.213 s in the example, about 12.8 cycles).
- Maximum arc duration is 2 s in normal mode (NFPA 70E reasonable escape time) and 50 ms plus Td' = 0.263 s in maintenance mode.
- Incident energy at the generator terminals drops from 75.2 cal/cm2 to 19.5 cal/cm2.
- Shunt tripping limits energy downstream of the breaker, but line-side terminals within its enclosure stay live.
- NFPA 70E gives no clear label guidance for mitigation such as maintenance mode; many engineers prepare two label sets, normal and maintenance mode.
Using it in design
- In an arc flash study at the generator output, calculate normal mode (2 s) and maintenance mode (50 ms plus Td') separately and prepare two label sets.
- If reduced PPE is used in maintenance mode, write the mode-on step into the work procedure and use a lockable switch.
- Enter alternator data-sheet reactances and time constants on the correct kVA base.
- Where more than one source feeds the fault (generator and utility transformer), enter the maximum arc duration per bus.
- If a shunt trip is configured on a breaker, credit the extra reduction downstream, but do not count it as reduction inside the breaker enclosure.
Who should read it
Power-system engineers carrying out short-circuit, coordination and arc flash studies for generator systems.
Document contents
- Introduction
- System modelling: generator set component
- AmpSentry selection
- Arc flash evaluation
- Maximum arc duration
- Arc energy reduction example
- Labeling requirements
- Summary
Related standards
- NEC 240.87
- IEEE 1584
- NFPA 70E
Publication details
- Authors
- Rich Scroggins; Ravi Thapa
- Publisher
- Cummins
- Year
- 2025
- Document number
- Bulletin 5544186, Rev. 10/25
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Cummins official white-paper landing page opened via TinyFish; official PDF opened via web tool. PDF p. 8 states ©2025 Cummins Inc. and Rev. 10/25. No open licence; metadata only. Official publisher listing and 8-page PDF both opened. No PDF retained locally. License evidence: https://www.cummins.com/en-na/generators/white-papers
Citation
Rich Scroggins; Ravi Thapa (2025). Short Circuit and Arc Flash Evaluations Using AmpSentry Capability - Part 1. Cummins. Bulletin 5544186, Rev. 10/25. https://mart.cummins.com/imagelibrary/data/assetfiles/0057942.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.