Enko Elektronik's 2025 ATS-S manual (version 1.01) describing the modes, parameters, faults and generator operating states of an automatic transfer controller for mains-generator or mains-mains sources.

On this page

Overview

The manual covers the menu structure, display indicators, connection terminals, alarm and fault descriptions and operating principles of the ATS-S control panel, which provides automatic transfer between two sources (mains-mains or mains-generator). The unit monitors mains and generator voltage and frequency, applies an adjustable delay before transfer, offers generator start/stop outputs and programmable inputs and outputs, and presents settings, event logs and faults on screen.

There are three operating modes. In Auto mode the mains is monitored continuously, the generator starts on failure, the load transfers, and on mains return the load is retransferred and the generator cooled and stopped. Manual mode is for test and maintenance: the generator is started by hand and the load is moved with MCB/GCB buttons. In Off mode the generator is not started. In manual transfer the closed contactor must be opened before the other is closed, which prevents both sources being connected together.

Technical data include a 5-35 Vdc supply, three-phase TRUE RMS mains and generator measurement, 4 configurable digital inputs, 6 solid-state outputs (300 mA), a USB parameter port, -10 to 60 degrees operating temperature, CAT III 300 V safety and IP54 at the front. Parameters are protected by three password levels. The end of the manual explains 17 fault definitions (emergency stop, generator voltage/frequency/phase sequence, high current and power, battery voltage, contactor feedback, start and stop failures) and the generator operating states (breaker off, mains active, mains fault, generator active and others).

Key points

  1. Three modes: Auto (automatic generator start and transfer on mains failure), Manual (test and maintenance, MCB/GCB buttons), Off (generator disabled).
  2. Manual transfer rule: MCB must be opened before closing GCB, and GCB opened before closing MCB.
  3. Three-phase TRUE RMS measurement for mains and generator, single-phase load current; adjustable delay before transfer.
  4. 4 configurable digital inputs, 6 solid-state outputs (300 mA), USB 2.0 Type-B parameter port.
  5. 5-35 Vdc supply, operating temperature -10 to 60 degrees, humidity 10-97% (non-condensing), CAT III 300 V, front IP54, rear IP20.
  6. Size 94 x 82 x 50 mm, panel cut-out 80 x 68 mm, weight about 140 g; a silicone gasket must be used for IP54.
  7. Faults: emergency stop, generator high/low voltage and frequency, phase sequence, high current and power, battery voltage, contactor feedback, start and stop failure.
  8. Three-level password protection (factory, service, user); event and fault log screens are provided.

Using it in design

  • When selecting ATS-S type controllers, state the monitored quantities (voltage, frequency, phase sequence) and the pre-transfer delay parameters in the ATS specification.
  • Add the MCB/GCB mutual interlock sequence in manual transfer and contactor feedback fault detection to commissioning tests.
  • Set generator alarm delays (voltage, frequency, current, power) consistently with generator and load characteristics.
  • For panel mounting, confirm the silicone gasket is used for the IP54 requirement and the screw tightening limit is respected.
  • Wire fault outputs such as start failure, stop failure and contactor feedback into the BMS or monitoring system.

Who should read it

Electricians and engineers who install, commission and operate generator and ATS panels.

Document contents

  1. Front panel description
  2. Rear panel description
  3. Display and menu structure
  4. Main menu and user interface
  5. Technical specifications
  6. Mechanical installation
  7. Electrical installation and example connections
  8. Parameters
  9. Fault definitions
  10. Generator operating states
  11. Software update
  12. Customer support

Publication details

Authors
Enko Elektronik
Publisher
Enko Elektronik
Year
2025
Document number
Version 1.01
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.

Citation

Enko Elektronik (2025). ATS-S Kullanım Kılavuzu. Enko Elektronik. Version 1.01. https://enkoelektronik.com/wp-content/uploads/2026/07/ATS-S_KK.V01.TR_.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.