Technical guideFree to read1986

Uninterruptible Power Supplies and an Example

Original title Kesintisiz Güç Kaynakları ve Bir Örnek

TMMOB Elektrik Mühendisleri Odası · Cemil Arıkan, Behçet Sarıbatır

A 1986 paper in the Chamber of Electrical Engineers journal Elektrik Mühendisliği covering UPS building blocks, PWM harmonic elimination and ASELSAN's 1 kVA transistor-based KGK3450.

On this page

Overview

The paper gives a general assessment of uninterruptible power supplies as the answer to the growing demand for quality supply as computers spread. It notes that at the time foreign firms built UPSs up to 300 kVA, domestic production was new and series production at high ratings had not yet been achieved.

A UPS has nine main units, and not every installation needs all of them: the generator is omitted for short outages, and the static transfer switch may be absent where the mains is a constant problem. The load is normally fed through the static switch from the mains; on loss or degradation of voltage the switch opens and the battery bank feeds the inverter. The author reduces the topic to two parts: rectifying and filtering the mains, then generating low-harmonic AC.

The technical core is eliminating inverter output harmonics through the choice of switching angles. Unlike motor drives, minimising harmonic distortion of output voltage is the first priority in a UPS, and the output filter corner must sit below the lowest harmonic present. More switching angles shrink the filter but raise switching losses and produce very narrow pulses.

The example unit, the KGK3450, is a bridge-inverter transistor design. The paper is a 1986 design narrative; it cannot be compared directly with today's IGBT double-conversion systems, but it documents the basic logic of harmonic elimination and of switching-device selection.

Key points

  1. The example is ASELSAN's EPROM-based, PWM-controlled 1 kVA KGK3450.
  2. The inverter is a bridge using GE D66EV7 transistors rated 500 V, 50 A, with a total switching time of about 5 microseconds.
  3. 18 pulses (9 angles) are used per cycle; the narrowest interval is calculated as 75 microseconds.
  4. The first harmonic seen is at 950 Hz; a filter with a 250 Hz corner keeps total harmonics under five percent in every load condition (0.8 capacitive to 0.8 inductive).
  5. The input voltage range is 43.2 V to 60 V, about a thirty percent variation.
  6. The fundamental is adjusted between 0.60 and 1 p.u. in steps of 0.005 under feedback to hold output voltage constant.
  7. At the time foreign firms made UPSs up to 300 kVA; FETs serve up to about 4-5 kVA, bipolar transistors 40-50 kVA, and thyristors above that.
  8. The nine UPS units are not all required in every installation; the generator and static transfer switch depend on the application.

Using it in design

  • In a UPS specification, decide from load and mains quality which units (generator, static switch, output filter) are actually needed.
  • Verify output total harmonic distortion at both load power-factor extremes (0.8 capacitive and inductive).
  • If a thyristor or early transistor UPS remains in an old facility, assess replacement priority given forced-commutation circuits and noise sensitivity.
  • Include the trade-off between output filter size and switching frequency (filter size versus switching loss) in UPS efficiency evaluation.

Who should read it

Engineers who want the basic logic of UPS output harmonics and PWM harmonic elimination, and readers studying the historical background of the technology.

Document contents

  1. Introduction
  2. Units of an uninterruptible power supply
  3. Obtaining the AC voltage
  4. Power circuit: switching devices
  5. An example: a 1 kVA UPS (KGK3450)

Publication details

Authors
Cemil Arıkan; Behçet Sarıbatır
Publisher
TMMOB Elektrik Mühendisleri Odası
Year
1986
Document number
Elektrik Mühendisliği 327-328-329, s. 29–32
Document language
Turkish
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Yayıncının açık PDF dosyası okundu. Açık erişim yeniden dağıtım izni anlamına gelmez; yalnızca künye, özgün kısa özet ve sayfa atıfları kaydedildi. 1986 tarihli teknoloji örneğidir; dönemsel ürün ve güç aralıkları güncel kabul edilmemelidir.

Citation

Cemil Arıkan; Behçet Sarıbatır (1986). Kesintisiz Güç Kaynakları ve Bir Örnek. TMMOB Elektrik Mühendisleri Odası. Elektrik Mühendisliği 327-328-329, s. 29–32. https://www.emo.org.tr/emoyayin/dosya/3236

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.