Technical guideFree to read1989

A Sinusoidal Uninterruptible Power Supply with Power MOSFETs and Magnetic Regulation

Original title Güç MOSFET’li ve Manyetik Regüleli Sinüsoidal Kesintisiz Güç Kaynağı

TMMOB Elektrik Mühendisleri Odası · İsmail Coşkun

A 1989 paper in the Chamber of Electrical Engineers journal Elektrik Mühendisliği describing a 36/220 V, 600 VA sinusoidal UPS built with power MOSFETs and a ferroresonant transformer.

On this page

Overview

The paper starts from the need to feed critical loads such as computers, alarms and communications through a UPS on unstable grids. Because power transistors and thyristors in inverters suffer from base-drive problems and from being unable to turn off on their own in a DC circuit, the author proposes power MOSFETs for small ratings.

The technical case has two parts. A power MOSFET is voltage driven and fast, so the drive circuit is simple and economical. A ferroresonant (magnetically regulated) transformer, with loose coupling between primary and secondary and a resonance capacitor on part of the secondary, brings the output close to a sine wave without filters, regulates it and limits current at an output short circuit through saturation.

In the built circuit an IRF 250 power MOSFET (200 V, 30 A) is driven at 8 V. PWM uses 9 pulses per half cycle of the output voltage; more pulses push the dominant harmonic to higher frequency. A larger resonance capacitor improves regulation but distorts the waveform away from a sine, and the conflict is resolved by feeding output voltage back to adjust the pulse width in closed loop.

The conclusion is that power MOSFETs are the right choice for the inverter stage of small UPSs; the paper also notes the prevailing use of power transistors and thyristors at medium and large ratings. It is a 1989 design example and does not apply directly to today's IGBT double-conversion data-centre UPSs, but it remains a historical and educational reference for ferroresonant UPS principles.

Key points

  1. The prototype is a 36/220 V, 600 VA sinusoidal UPS with power MOSFETs and magnetic regulation.
  2. The inverter uses an IRF 250 MOSFET (200 V, 30 A, 8 V gate drive).
  3. PWM pulses are designed for 9 pulses per half cycle of the output voltage.
  4. The inverter is push-pull or bridge depending on load size and device current and voltage limits.
  5. In the ferroresonant transformer the output approaches a sine without filter elements, and short-circuit current is limited by saturation.
  6. A larger resonance capacitor improves regulation but degrades the waveform; closed-loop PWM feedback removes the trade-off.
  7. The trend is power transistors and thyristors at medium and large ratings and power MOSFETs at small ratings.
  8. Thyristors are criticised for not turning off by themselves in a DC circuit and for noise sensitivity.

Using it in design

  • Where legacy ferroresonant UPSs are still installed, add output short-circuit behaviour and resonance capacitor condition to the maintenance list.
  • For small auxiliary loads, ask the manufacturer for the trade-off between output waveform quality and regulation.
  • Treat the switching-device technology (thyristor, transistor, MOSFET), its drive complexity and turn-off behaviour as a separate item in the UPS reliability review.
  • Use the effect of PWM pulse count on harmonic content as a reference when sizing output filters.

Who should read it

Engineers, students and maintenance teams who want the history of UPS power electronics and the ferroresonant principle, including those servicing older installations.

Document contents

  1. Introduction
  2. The uninterruptible power supply: rectifier and inverter, generating the AC voltage
  3. Switching devices and pulses
  4. The UPS and its evaluation
  5. Conclusion

Publication details

Authors
İsmail Coşkun
Publisher
TMMOB Elektrik Mühendisleri Odası
Year
1989
Document number
Elektrik Mühendisliği 365, s. 514–517
Document language
Turkish
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Yayıncının açık PDF dosyası okundu. Açık erişim yeniden dağıtım izni anlamına gelmez; yalnızca künye, özgün kısa özet ve sayfa atıfları kaydedildi. 1989 tarihli deneysel tasarımdır; güncel uygunluk veya ürün performansı iddiası değildir.

Citation

İsmail Coşkun (1989). Güç MOSFET’li ve Manyetik Regüleli Sinüsoidal Kesintisiz Güç Kaynağı. TMMOB Elektrik Mühendisleri Odası. Elektrik Mühendisliği 365, s. 514–517. https://www.emo.org.tr/emoyayin/dosya/2845

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.