Evaporative Condensation Air-Conditioning Unit with Microchannel Heat Exchanger: An Experimental Study
Energies / MDPI · Junjie Chu, Xiang Huang et al.
An Energies (2025) paper reports that a microchannel heat-pipe evaporative condensation unit reaches 112.1, 105.8 and 115.4 kW in dry, wet and mixed modes, with an optimal refrigerant charge of 32 kg.
On this page
Overview
The paper proposes a new evaporative condensation refrigerant-pump heat-pipe air-conditioning unit based on a microchannel heat-pipe heat exchanger. The prototype combines pumped heat-pipe operation, evaporative condensation and mechanical refrigeration, and was tested in an enthalpy-difference laboratory in Jiangsu, China. Dry, wet and mixed modes are evaluated as separate operating cases.
Experimental results show cooling capacity of 112.1, 105.8 and 115.4 kW in dry, wet and mixed modes; optimal secondary/primary airflow ratios are 2.2, 1.8 and 1.8, and EER falls as the airflow ratio rises. Capacity and EER decrease as the secondary-side inlet air dry- and wet-bulb temperatures rise; EER in wet mode is higher than in dry mode, which can extend wet-mode operating hours within the dry-mode temperature range. A new refrigerant charge calculation is proposed, and the optimal charge is 32 kg from experiment, matching the theoretical result.
Key points
- Prototype: pumped heat pipe, evaporative condensation and mechanical refrigeration combined.
- Test: enthalpy-difference laboratory in Jiangsu, China.
- Cooling capacity: dry 112.1 kW, wet 105.8 kW, mixed 115.4 kW.
- Optimal secondary/primary airflow ratio: 2.2 (dry), 1.8 (wet), 1.8 (mixed).
- EER in wet mode is higher than in dry mode.
- Optimal refrigerant charge is 32 kg; the proposed calculation agrees with the theoretical result.
Using it in design
- For data-centre evaporative condensation units, set dry, wet and mixed mode changeover temperatures from annual climate data.
- Choose airflow ratio by the trade-off between EER and capacity; the optimum varies by mode.
- Check refrigerant charge with the proposed calculation method and the laboratory result.
- Account for the capacity drop at high wet-bulb ambient conditions at the design point.
Who should read it
Mechanical designers and researchers evaluating evaporative cooling and heat-pipe free cooling solutions.
Publication details
- Authors
- Junjie Chu; Xiang Huang; Hongxu Chu; Liu Yang; Weihua Lv; Xing Tang; Jinxing Tian
- Publisher
- Energies / MDPI
- Year
- 2025
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Article-specific CC BY 4.0 notice verified on the publisher page. Retain attribution, license link and change notices; third-party exceptions require separate review. Generic MDPI dc.rights metadata may say BY 3.0; the article-specific notice takes precedence. Round 5/6 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Junjie Chu; Xiang Huang; Hongxu Chu; Liu Yang; Weihua Lv; Xing Tang; Jinxing Tian (2025). Evaporative Condensation Air-Conditioning Unit with Microchannel Heat Exchanger: An Experimental Study. Energies / MDPI. https://doi.org/10.3390/en18092356
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.