ENTES RGP Series 3-Phase Reactive Power Control Relay: User Manual
Original title RGP Serisi 3 Fazlı Reaktif Güç Kontrol Rölesi: Kullanım Kılavuzu
ENTES
User manual for the ENTES RGP three-phase reactive power control relay: 9 or 12 steps with per-phase compensation, automatic wiring and step detection at commissioning, and alarm and warning tables.
On this page
Overview
The manual describes ENTES's new-generation RGP series reactive power control relay. Through 9 or 12 steps (with 9+SVC and 12+SVC options) the relay controls the three phases separately and brings each phase's cos φ towards the user-set target, preventing the facility from entering the reactive-penalty zone. The unit has three-phase voltage inputs, current inputs, an RS-485 communication port, an alarm output and a fan output.
The commissioning section proceeds step by step. On power-up the language selection, tutorial mode and automatic setup screens appear, asking for region, time, date, CT primary and secondary, nominal frequency, target cos φ and reference step. The device first runs automatic wiring detection, correcting phase-sequence and CT polarity errors by switching the three-phase capacitor on the reference step in and out. It then runs step detection to learn each step's power and connection type. Non-linear and suddenly changing loads such as thyristor or triac controlled loads, frequency converters and UPS can defeat the automatic correction; those loads should be switched off temporarily and the procedure repeated.
The alarm and warning structure is broad. It defines 7-day inductive and capacitive ratio alarms and warnings, step capacity loss, contactor life and switching-count alarms, insufficient capacitor or reactor power, and voltage, THDV, THDI and cabinet-temperature alarms. For voltage, THDV, THDI and temperature, enabling the step protection option makes the device switch off all steps to protect the capacitors. A smiley display mode and LED colours (red alarm, yellow warning, blue generator on) show the state.
The manual also covers the measurement menus (voltage, current, frequency, harmonics, energy and daily/monthly compensation data), the Modbus setting, the compliance standards and measurement ranges. It gives a 144 × 144 mm housing, -20/+70 °C operating temperature and IP 54 on the front panel.
Key points
- 9 and 12 steps, with 9+SVC and 12+SVC options; each phase is controlled separately.
- A three-phase capacitor must be connected to the reference step; the device does not work without a three-phase-to-neutral connection.
- Automatic wiring detection corrects phase sequence and CT polarity errors; phase currents must be non-zero for it to work.
- Thyristor/triac controlled, frequency-converter and UPS-type loads can defeat automatic correction; switch them off temporarily and repeat.
- Alarm postpone-time options are 1, 8, 24 and 72 hours.
- On voltage, THDV, THDI and temperature alarms, with step protection on, all steps are switched off.
- Measurement ranges: phase-neutral 10-400 Vac, phase-phase 10-690 Vac, frequency 47-63 Hz, current input 0.005-6 A, harmonics 2nd-31st.
- Housing 144 × 144 mm, panel cut-out 138 × 138 mm, operating temperature -20/+70 °C, front IP 54.
Using it in design
- In the compensation panel, connect the relay CT with the correct phase-neutral pairing and place a three-phase capacitor on the reference step.
- Commission under low-harmonic conditions, or switch off drive and UPS loads temporarily, so their harmonic effect does not disturb the automatic setup.
- Set voltage, THDV and THDI alarm limits and the step protection option to match the capacitor and reactor class.
- Link the contactor life and switching count warnings to the maintenance plan.
- Carry RS-485 Modbus communication into the building management and monitoring system.
Who should read it
Electrical engineers and technicians designing, commissioning and operating reactive power compensation panels.
Document contents
- Introduction: general features, product family, operating conditions
- LED indicator, display and front panel
- Key functions
- Connection diagram
- Commissioning the RGP device
- Using the device and menus: settings, alarms, time, system, reset
- COS φ and compensation menus
- Power, energy, measurement and harmonic menus
- Messages
- Maintenance, warranty and compliance
- Appendices: mechanical and environmental conditions, measurement, capacitor calculation table
Publication details
- Authors
- ENTES
- Publisher
- ENTES
- Year
- Year not stated
- Document number
- RGP Serisi
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public source opened on the access date. No open redistribution licence established; metadata and original short summaries only. PDF text-layer character mapping is corrupt. Pages 2–4, 17, 26, 32 and 33 were rasterized and OCR processed; pages 17 and 32 were visually verified for the two facts. PDF creation metadata is not treated as publication year. Contents-page numbering differs from the actual section page positions; locators use the visible printed pages.
Citation
ENTES RGP Serisi 3 Fazlı Reaktif Güç Kontrol Rölesi: Kullanım Kılavuzu. ENTES. RGP Serisi. https://entes.com.tr/uploads/files/1733815959-tr_rgp_serisi.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.