Equinix to Adjust the Thermostat to Optimise Data Centre Energy Use
Equinix
This 2022 Equinix press release announces a multi-year plan to raise operating temperatures across its colocation portfolio to about 27 degC (80 degF), aligned with the ASHRAE A1 allowable limits.
On this page
Overview
The release states that cooling is about 25% of Equinix's global energy use and expects efficiency improvements of up to 10% at various sites. A higher setpoint is thus offered as an energy lever that needs no new equipment; because cooling's share is so large, even a small rise in setpoint creates a meaningful energy difference at portfolio scale. The expectation is worded as 'up to 10%', so some sites may see clearly less.
The target is about 27 degC (80 degF), aligned with the ASHRAE A1/A1A envelope, which is the top of ASHRAE's recommended 18-27 degC range. Later Equinix releases cite new builds such as Frankfurt FR13 with a typical operating temperature of 27 degC. The plan is multi-year because inlet-temperature limits in customer contracts and existing sites cannot be changed all at once.
The release also gives renewable coverage: above 90% since 2018 and 95% in 2021, a reminder that most of the plan's carbon effect comes from the grid supply mix. As a press release it shows no measured PUE effect; the 10% is only an anticipated upper bound, and the economizer-hour gain has to be weighed against any rise in server fan power.
Key points
- Target operating temperature about 27 degC (80 degF), aligned with the ASHRAE A1/A1A envelope.
- Cooling is about 25% of Equinix's total global energy use.
- Anticipated energy-efficiency (PUE) improvement of up to 10% at various locations.
- Renewable coverage above 90% since 2018; 95% in 2021.
- Later releases cite new builds (e.g. Frankfurt FR13) with typical 27 degC operation.
Using it in design
- Assess a 27 °C colocation setpoint as the upper end of ASHRAE’s recommended 18–27 °C range, comparing PUE and economiser hours across 22–27 °C options.
- Assess an 'SLA max inlet' parameter, since customer SLAs often cap inlet temperature.
- Record the customer contract’s maximum inlet temperature as a constraint on setpoint selection.
Who should read it
Colocation operators and designers planning energy savings by raising the cooling setpoint.
Related standards
- ASHRAE TC9.9 Thermal Guidelines (Class A1)
Publication details
- Authors
- Equinix
- Publisher
- Equinix
- Year
- 2022
- Document language
- English
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Equinix (2022). Equinix to Adjust the Thermostat to Optimise Data Centre Energy Use. Equinix. https://newsroom.equinix.com/2022-12-06-Equinix-to-Adjust-the-Thermostat-to-Optimise-Data-Centre-Energy-Use
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.