Eurochiller DCooler & ADCooler Technical Flyer
Original title Eurochiller DCooler & ADCooler technical flyer
Eurochiller
Eurochiller DCooler dry coolers give 63-920 kW and the adiabatic ADCooler series 82-1,220 kW; DC values are at 30 °C ambient and 40/35 °C water, ADC values are printed without adiabatic pads.
On this page
Overview
Eurochiller's DCooler (dry) and ADCooler (adiabatic) flyer presents dry coolers designed for plastics industry cooling. The DCooler rejects heat to ambient air and needs no continuous water supply. The ADCooler pre-cools the incoming air with a controlled water mist to raise heat rejection at peak temperatures; the flyer cites up to 40% more capacity in peak heat. An anti-Legionella design with automatic water flushing is highlighted.
The technical table gives 12 DCooler models (DC-S 60 to DC-L 880) and 12 ADCooler models (ADC-S 80 to ADC-L 1200). DC capacity is 63-920 kW and ADC capacity 82-1,220 kW. The DC reference condition is 30 °C ambient, water 40/35 °C, 0% glycol. ADC capacity is printed per ENV 1048 without adiabatic pads; this is not wet-operation performance.
Fan count is 1-14, fan power 2.25-30.8 kW, water connections 2 to 4 inch and water content 40-790 L. Length is 1,770-10,930 mm and height 2,145 or 2,600 mm; ADC width is 300 mm greater. The optional pump kit for S series is 2.3-11 kW. Options are EC fans (for -20 °C installations), epoxy coating, Cu-Al coils and adiabatic solenoid valves. This document is a distributor copy.
Key points
- DCooler (DC-S and DC-L): 63-920 kW; ADCooler (ADC-S and ADC-L): 82-1,220 kW.
- DC reference condition: ambient 30 °C, water in/out 40/35 °C, 0% glycol.
- ADC capacity is per ENV 1048 without adiabatic pads; it is not wet performance.
- Up to 40% more capacity at peak heat is claimed for the adiabatic system.
- Fan count 1-14, fan power 2.25-30.8 kW.
- Water connections 2 inch-4 inch; water content 40-790 L.
- Length 1,770-10,930 mm; height 2,145 (S) or 2,600 mm (L).
- Anti-Legionella design, adiabatic solenoid valves and an optional internal pump.
Using it in design
- Do not use the ADC table capacity as wet-operation capacity; calculate the pad effect separately with manufacturer software.
- Read DC capacity at 30 °C ambient and 40/35 °C water, and correct if data-centre water temperatures differ.
- For the adiabatic system, state water quality, water consumption and Legionella control requirements in the specification.
- For cold climates consider the EC fan and glycol together.
- Carry dimensions and fan power (up to 30.8 kW) into the layout and electrical plan.
Who should read it
Mechanical designers selecting free-cooling dry coolers and decision makers concerned with water savings.
Document contents
- DCooler and ADCooler range
- Cutting-edge technology and premium components
- Technical data
- Applications
Publication details
- Authors
- Eurochiller
- Publisher
- Eurochiller
- Year
- 2025
- Document number
- DCooler_ADCooler_Flyer_EN_20251008
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Eurochiller (2025). Eurochiller DCooler & ADCooler technical flyer. Eurochiller. DCooler_ADCooler_Flyer_EN_20251008. https://www.ajsolutions.be/wp-content/uploads/2022/05/DCooler-ADCooler_Flyer_EN_20250910.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.