Eurochiller GCevo AG: Air-Cooled Water Chillers (R32)
Original title Eurochiller GCevo AG, internal revision 20251008, p.2 technical data
Eurochiller
The Eurochiller GCevo AG flyer presents 14 models of R32 air-cooled water chillers for the plastics industry, from 20 to 155 kW, with EER between 3.48 and 5.20.
On this page
Overview
Eurochiller's GCevo AG series is a range of air-cooled water chillers designed for plastics industry process cooling. It uses R32 refrigerant (GWP 675); the flyer says this can cut energy consumption by up to 10% and reach target temperature faster. It is not a data-centre document, but it gives a capacity and efficiency reference for process and auxiliary cooling.
The technical table covers 14 models at 50 Hz, numbered 18 to 130, with cooling capacity from 20.0 kW to 155.0 kW. Power consumption runs from 4.45 kW to 44.50 kW, EER from 3.48 to 5.20, and SEPR HT from 5.01 to 6.02 (EU 2016/2281). The reference condition is 25 °C ambient air, evaporator 20/15 °C, 0% glycol, AC fan and 3 bar pump. SEPR values are for the configuration without a pump.
Components include scroll compressors, electronic expansion valves, microchannel coils, centrifugal pumps (3 bar and 5 bar), open or pressurised tank options, epoxy coating and an EC fan option for -20 °C installations. Control is by IQ21 PLC with a touch screen; an optional gateway supports Ethernet and Profibus. Models have 1 or 2 compressors on 1 circuit, with buffer tank options of 50, 90 or 200 L.
Key points
- Series: GCevo AG R32, 50 Hz, 14 models, 20.0-155.0 kW cooling capacity.
- Refrigerant R32, GWP 675.
- EER from 3.48 (model 130) to 5.20 (model 40); SEPR HT 5.01-6.02.
- Reference condition: 25 °C ambient, evaporator 20/15 °C, 0% glycol, AC fan and 3 bar pump.
- SEPR HT is declared for the configuration without pump under EU 2016/2281.
- Power consumption is 4.45-44.50 kW.
- Pump 3 bar or 5 bar; buffer tank options 50, 90, 200 L.
- Dimensions range from 1,260 x 535 x 1,370 mm for small models to 2,405 x 1,070 x 1,995 mm for large ones (L x W x H).
Using it in design
- Compare capacity and EER only at the reference condition; other ambient or water temperatures need the manufacturer's selection software.
- SEPR applies to the pump-less configuration and EER to the pumped one; do not mix the two indicators.
- For -20 °C ambient installations, specify the EC fan option and glycol percentage.
- Choose pump pressure (3 or 5 bar) and tank type against the hydraulic circuit pressure drop.
- For BMS integration, confirm the gateway protocols (Ethernet, Profibus).
Who should read it
Mechanical designers and buyers selecting air-cooled chillers for process and auxiliary cooling.
Publication details
- Authors
- Eurochiller
- Publisher
- Eurochiller
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Eurochiller (2025). Eurochiller GCevo AG, internal revision 20251008, p.2 technical data. Eurochiller. https://www.eurochiller.com/content/dam/brands/eurochiller/documents/brochures/GCevo%20AG_Flyer_EN_20250916.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.