Euroklimat EKS New Gen Technical Data (R454B Air-Cooled Chillers)
Original title EKS New Gen technical data
Euroklimat
Euroklimat EKS New Gen is a multi-scroll air-cooled chiller series; 12 models give 148 to 589 kW cooling capacity, EER of 3.02-3.17 and microchannel coils.
On this page
Overview
EKS New Gen are MultiScroll air-cooled liquid chillers designed for outdoor installation. The capacity range is 148-589 kW. Solution types are Base (B), Base with pump (P) and Integrata (I); versions are Standard (ST), Low Noise (LN) and Super Low Noise (SL); equipment is Standard (AS) or desuperheater (DS). The structure is galvanised sheet steel with polyester powder coating in RAL 7035.
Components: hermetic scroll compressors, axial fans with IE4-class EC motors, a microchannel air heat exchanger, AISI 316 plate or shell-and-tube water heat exchanger, electronic expansion valve, HP and LP pressure sensors and a microprocessor control with BMS connection. The water circuit can include automatic filling, safety valve, expansion tank, pump and water tank. Main accessories are spring vibration isolation, soft start, remote control panel, standby pump and voltage relay.
The technical table gives 12 models (055-2-1 to 240-6-2) in four configurations. In the P/ST/EC/OO configuration, cooling capacity is 148 to 589 kW, total power 46.7 to 195 kW, EER 3.02 to 3.17 and SEPR 5.54 to 5.82. Capacity values depend on 35 °C air and 12/7 °C water; the pump configuration is selected separately. The desuperheater option gives 40-177 kW and the heat recovery option 184-760 kW of heating capacity.
Key points
- Series capacity 148-589 kW; 12 models (055-2-1 to 240-6-2).
- Reference condition: 35 °C air, 12/7 °C water (pump configuration selected separately).
- P/ST/EC/OO: capacity 148-589 kW, total power 46.7-195 kW, EER 3.02-3.17, SEPR 5.54-5.82.
- In the optional OI configuration capacity rises on some models (for example 055 from 148 to 164 kW).
- Desuperheater option: 40-177 kW heating; heat recovery: 184-760 kW.
- Axial fans with IE4-class EC motors, microchannel air coil.
- AISI 316 plate water heat exchanger; electronic expansion valve.
- Three versions: ST, LN, SL; three solutions: B, P, I.
Using it in design
- Read capacity at 35 °C air and 12/7 °C water; correct with the manufacturer's software if data-centre design temperatures differ.
- Choose pump and tank configuration (B, P, I) from the hydraulic schematic; include pump power in EER or add it separately.
- On noise-limited sites evaluate the LN or SL version.
- Match the heat recovery or desuperheater option to the building's heating demand.
- State BMS connection and soft start options in the specification.
Who should read it
Mechanical designers selecting air-cooled chillers for data-centre and process cooling.
Document contents
- General features and main accessories
- Technical data: cooling mode
- Desuperheater
- Heat recovery
Publication details
- Authors
- Euroklimat
- Publisher
- Euroklimat
- Year
- 2025
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Euroklimat (2025). EKS New Gen technical data. Euroklimat. https://www.euroklimat.it/wp-content/uploads/2025/05/Technical-Data_EKS-New-Gen_05-25_rev0_EN-1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.