Technical guideFree to read2022

EVAPCO EAW Dry Fluid Cooler Certified Thermal Performance Tables

Original title EAW Certified Performance Tables

EVAPCO

EVAPCO's STD-201RS table dated 25 Aug 2022: EAW dry fluid cooler flow ratings (USGPM, water) at 77 and 95 °F dry bulb, with approaches of 5-18 °F and ranges of 9-15 °F.

On this page

Overview

The document is a table of about seven thousand lines listing certified thermal performance of EVAPCO EAW line dry fluid coolers (DFC) in IP units, model by model. The process fluid is water and values are in USGPM. Model codes cover the FD15, VD15, DD33 and FD91 families and S1 to S6 steps, encoding motor power and fan options.

Each row gives flow for ten conditions: dry bulb of 77 °F and 95 °F, each with range/approach pairs of 10/5, 10/10, 15/10, 15/12 and 9/18 °F. Approach is the leaving water minus dry bulb temperature; range is the water inlet-outlet temperature difference. A dash means the flow rate is outside the unit's capability.

Three connection options (first, second, third flow) also list flow, pressure drop (PSI) and inlet pipe size. For example a VD15S1 model handles about 174-226 GPM at 95 °F dry bulb with 9 °F range and 18 °F approach; its first flow option is 242 GPM at 17.4 PSI with a 3 inch inlet.

It is a selection table; it has no method, application guidance or data-centre-specific commentary. Its value to a data centre designer is seeing, from certified data, how much water flow each dry cooler can handle at real design conditions, how close leaving water can approach dry bulb, and the pressure drop and pipe size.

Key points

  1. Table STD-201RS dated 25 Aug 2022, IP units, process fluid water, flow in USGPM.
  2. Dry bulb conditions are 77 °F (25 °C) and 95 °F (35 °C).
  3. Range/approach pairs are 10/5, 10/10, 15/10, 15/12 and 9/18 °F; a smaller approach means less flow.
  4. Model families are FD15, VD15, DD33 and FD91, each in S1-S6 steps.
  5. A dash marks a condition where the flow rate is outside the unit's capability.
  6. Example: a VD15S1 model gives 175.9 GPM at 77 °F and 173.9 GPM at 95 °F for 9/18 °F; first flow 242 GPM, 17.4 PSI, 3 inch inlet.
  7. Moving dry bulb from 77 to 95 °F reduces the same model's flow by a few percent (175.9 to 173.9 GPM).

Using it in design

  • From design dry bulb and required leaving water temperature, choose the range/approach pair and read flow from the nearest column.
  • Account for flow dropping as approach shrinks; a larger approach means more flow but a higher water temperature.
  • Use the pressure drop and inlet pipe size columns for pump selection and pipe sizing.
  • The table is for water; get capacity and pressure drop corrections for glycol mixtures from the manufacturer.
  • Where site maximum dry bulb exceeds 95 °F, request a manufacturer selection rather than extrapolating outside the table.

Who should read it

Mechanical designers selecting dry fluid coolers for data centre cooling circuits.

Document contents

  1. Table 3a: IP units, dry fluid coolers (DFC), EAW line thermal performance, water as process fluid (USGPM)

Publication details

Authors
EVAPCO
Publisher
EVAPCO
Year
2022
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

EVAPCO (2022). EAW Certified Performance Tables. EVAPCO. https://www.evapco.com/sites/evapco.com/files/2022-09/EAW%20Certified%20Performance%20Tables.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.