Improving Thermal Performance in Data Centers Based on Numerical Simulations
Buildings (MDPI AG) · Yinjie Guo, Chunyu Zhao et al.
A 6SigmaDC study of a 552 m² cold-aisle-contained raised-floor hall (0.8 m floor, 226 cabinets at 6.3 kW, eleven 175 kW chilled-water units on one side): cabinets in the rows nearest the cooling units run hot because high-velocity plenum flow starves the nearest tiles.
CC BY 4.0: share with attribution
On this page
Overview
The study asks how inappropriate temperature distribution when cooling servers with cold air aggravates the heat-dissipation problem, and how to correct it. The room is about 32.8 m × 16.9 m (552.38 m² including the AC room), 5 m high, with a 0.8 m raised floor and 50%-open grilles. It holds 226 cabinets of 6.3 kW (21 × 600 W 2U servers each) and eleven 175 kW chilled-water precision units, two of them redundant. The model was built from design data in 6SigmaDC.
Two fixes were tested: adjustable underfloor deflectors with adjusted grille openings in the near rows, and fan-assisted floor tiles in the nearest row. Underfloor deflectors under the grilles in rows O and N, with adjusted grille opening, raised airflow to near-side cabinets by 18.1% and cut airflow to far-side cabinets by 5.1%. Replacing the row-Q grilles with fan floor tiles raised near-side cabinet airflow by 4.9% and cut far-side airflow by 3.8%. The largest drop in average cabinet outlet temperature was 2.81 °C.
Both options balanced airflow between near and far cabinets, maximised cooling capacity and improved temperature uniformity. Because server racking is lengthy, data centres often do not run at full load; the study considered the most unfavourable case (full load) and showed both solutions keep server equipment within the normal temperature range even at full capacity.
Limits: the CFD model was not validated against measurements; the paper reports meshing but no measurement-based validation. Results depend on one hall geometry, and the cost, noise and control of fan tiles and deflectors were not assessed.
Key points
- The room is about 32.8 m × 16.9 m (552.38 m² including the AC room), 5 m high, 0.8 m raised floor, 50%-open grilles; 226 cabinets of 6.3 kW (21 × 600 W 2U servers) and eleven 175 kW chilled-water precision units, two redundant.
- Underfloor deflectors under the grilles in rows O and N, with adjusted grille opening, raised airflow to near-side cabinets by 18.1% and cut airflow to far-side cabinets by 5.1%.
- Replacing the row-Q grilles with fan floor tiles raised near-side cabinet airflow by 4.9% and cut far-side airflow by 3.8%.
- The largest drop in average cabinet outlet temperature was 2.81 °C.
- The model is built from design data in 6SigmaDC; the paper reports meshing but no measurement-based validation.
Using it in design
- If cabinets in the rows nearest the cooling units run hot (high-velocity plenum flow starving the nearest tiles), consider adjustable underfloor deflectors and grille opening adjustment before fan-assisted tiles (18.1% and 4.9% airflow shift).
- Verify the design at the full-load worst case, since racking is lengthy and the hall often runs at part load.
- Label CFD results without measurement validation as indicative and compare them with tile airflow measurement at commissioning.
Who should read it
Cooling engineers balancing near- and far-side cabinets in raised-floor, cold-aisle-contained halls.
Document contents
- 1. Introduction
- 2. Fundamental Methods (2.1 Project Overview and Physical Model, 2.3 Post-Processing, 2.4 Transformation Process)
- 3. Comparison and Results (effect of the measures, CFD simulation analysis, CFD simulation analysis of cabinets at different heights)
- 4. Conclusions
Related standards
- GB 50174 Code for design of data centers
Read the document
fan-floor-cabinet-airflow-balance-2024.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Yinjie Guo; Chunyu Zhao; Hao Gao; Cheng Shen; Xu Fu
- Publisher
- Buildings (MDPI AG)
- Year
- 2024
- Volume
- 14
- Issue
- 5
- Pages
- 1416
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1: open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Citation
Yinjie Guo; Chunyu Zhao; Hao Gao; Cheng Shen; Xu Fu (2024). Improving Thermal Performance in Data Centers Based on Numerical Simulations. Buildings (MDPI AG). 14(5), 1416. https://doi.org/10.3390/buildings14051416
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.