Optimization of Airflow Organization in Bidirectional Air Supply Data Centers in China
Applied Sciences (MDPI AG) · Yixin Wu, Junwei Yan et al.
Field measurements and a Fluent CFD model of a 502 m² raised-floor hall in Guangzhou with 142 racks, where perimeter CRACs feed the plenum from opposite sides: in the bidirectional zone the opposing jets collide and create vortices and uneven static pressure.
CC BY 4.0: share with attribution
On this page
Overview
The study asks how to improve airflow organisation in a bidirectional air-supply data centre in a hot-summer, warm-winter region. The IT room is 502.3 m² with a 0.7 m raised floor and 4.5 m clear height; nine CRACs (seven running, two standby), each rated 34,800 m³/h, supply under the floor with side return to 142 racks in eight rows on 1.2 m aisles. Validation used 72 temperature points (0.5, 1.2 and 1.8 m heights) and 144 tile-velocity points: inlet temperature MBE was 0.70 °C with RMSE 0.92 °C, outlet MBE 0.67 °C, RMSE 1.46 °C, and tile airflow RMSE 0.011 m³/s.
Model settings: standard k-epsilon, polyhedral mesh of 6,972,368 cells, perforated tile porosity 36% and rack door porosity 86% as porous jumps, and server heat as volumetric sources from measured PDU power. Colliding plenum jets gave peak static pressures of 6-14 Pa at the collision interfaces. Mean tile flow was about 0.20 m³/s in the one-sided supply zone and 0.25 m³/s in the two-sided zone, with minimums of 0.14 m³/s in rows AE and AF. The cooling system over-supplies air and cold-air bypass dominates, yet severe mixing of cold and hot air gives an imbalanced cooling capacity distribution.
Seven retrofit cases were scored with RTI, SHI and RCI-HI: three containment variants (doors only, roof only, full), blanking panels, and blanking combined with each containment variant. Baseline RTI was 0.786, SHI 0.230 and RCI-HI 0.992. Blanking panels alone gave SHI 0.132 and RCI-HI 1; blanking plus full cold-aisle containment (Case 7) gave RTI 1 and SHI 0.027. SHI reductions versus baseline were: door-only containment 1.30%, roof-only 0.43%, full containment alone 12.17%, blanking alone 42.61% and blanking plus full CAC 88.26%.
Blanking was the best single measure; blanking plus full containment was best overall, and blanking plus roof-only containment was the cheaper runner-up. Containment without blanking achieved little. Limits: a single hall and climate zone; results depend on this hall's geometry and CRAC layout.
Key points
- The IT room is 502.3 m² with a 0.7 m raised floor and 4.5 m clear height; nine CRACs (seven running, two standby), each 34,800 m³/h, serve 142 racks in eight rows on 1.2 m aisles.
- Validation used 72 temperature points and 144 tile-velocity points: inlet temperature MBE 0.70 °C, RMSE 0.92 °C; outlet MBE 0.67 °C, RMSE 1.46 °C; tile airflow RMSE 0.011 m³/s.
- Model: standard k-epsilon, polyhedral mesh of 6,972,368 cells, tile porosity 36% and rack door porosity 86% as porous jumps, server heat as volumetric sources from measured PDU power.
- Colliding plenum jets gave peak static pressures of 6-14 Pa; mean tile flow about 0.20 m³/s in the one-sided zone and 0.25 m³/s in the two-sided zone, minimum 0.14 m³/s in rows AE and AF.
- Baseline RTI 0.786, SHI 0.230, RCI-HI 0.992. Blanking alone: SHI 0.132, RCI-HI 1. Blanking plus full CAC (Case 7): RTI 1, SHI 0.027.
- SHI reductions versus baseline: door-only containment 1.30%, roof-only 0.43%, full containment alone 12.17%, blanking alone 42.61%, blanking plus full CAC 88.26%; containment without blanking achieved little.
Using it in design
- In retrofitting an existing raised-floor hall, first close unused rack spaces with blanking panels (alone they cut SHI by 42.61%); containment alone gave little benefit.
- In bidirectional plenum supply, check by CFD or measurement the static pressure imbalance (6-14 Pa) and uneven tile flow (0.14 to 0.25 m³/s) where opposing jets collide.
- If budget is limited, compare blanking plus roof-only containment as the cheaper option and blanking plus full cold-aisle containment as the best option, scoring both with RTI, SHI and RCI-HI.
Who should read it
Cooling engineers and operators improving airflow in existing raised-floor data halls.
Document contents
- 1. Introduction
- 2. Materials and Methods (2.1 Field Experiment: overview of data centers, experimental scheme; 2.2 Numerical Simulation: governing equations, simplification assumptions, boundary conditions; 2.3 Thermal Metric)
- 3. Results (3.1 Model Validation, 3.2 Air Supply Characteristics, 3.3 Flow Field Distribution, 3.4 Temperature)
- 4. Airflow Organization Optimization (4.1 Airflow Optimization Strategies, 4.3 Analysis)
- 5. Conclusions
Related standards
- ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
- GB 50174 Code for design of data centers
Read the document
bidirectional-air-supply-dc-2025.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Yixin Wu; Junwei Yan; Xuan Zhou
- Publisher
- Applied Sciences (MDPI AG)
- Year
- 2025
- Volume
- 15
- Issue
- 10
- Pages
- 5711
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1: Licensee MDPI; open access article distributed under the terms of the Creative Commons Attribution (CC BY) license. Note: the deposited PDF contains overlapping review-layer text on some pages.
Citation
Yixin Wu; Junwei Yan; Xuan Zhou (2025). Optimization of Airflow Organization in Bidirectional Air Supply Data Centers in China. Applied Sciences (MDPI AG). 15(10), 5711. https://doi.org/10.3390/app15105711
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.