Energy efficiency enhancement in two European data centers through CFD modeling
Scientific Reports (Springer Science and Business Media LLC) · Onur Muhammed Sarikaya, Mustafa Kuzay et al.
OpenFOAM-based CFD models of two small pilot server rooms from the EU HEATWISE project (PSNC in Poland and Aalborg University in Denmark) were validated against measurements and used to compute KPIs and test retrofits step by step.
CC BY 4.0: share with attribution
On this page
Overview
The EU's new reporting scheme focuses on assessing data-centre efficiency through key performance indicators (KPIs); the study asks how such KPIs can be calculated through CFD simulation and used to guide improvements. PSNC is an open-aisle micro data centre with 2 racks and 9 active servers cooled by ceiling-mounted units; AAU has 6 racks and 21 active servers cooled by two fan-coil units. AAU measurements used 16 calibrated Dantec 54R103 anemometers (0-5 m/s, ±5%) and PT100 sensors (setup uncertainty 0.21 °C); PSNC used IPMI data sampled every 10 minutes over two days.
Turbulence was modelled with k-omega SST. Servers were open-box models with momentum and heat sources and a Darcy-Forchheimer porous resistance (porosity 0.5), and cooling units were black-box fixed-flow boundaries with buoyancy from the ideal-gas law. Mesh3 was chosen after a five-level mesh study; final meshes had 1,652,180 cells (PSNC) and 1,066,351 cells (AAU) with y+ between about 1.1 and 9.8. Mean absolute differences between simulated and measured server inlet temperatures were 1.3 °C (PSNC) and 1.6 °C (AAU), with larger error near a server whose airflow is rotated 90 degrees.
KPI limits were ASHRAE recommended 18-27 °C and allowable 15-32 °C inlet temperatures. The PSNC retrofit (remove ceiling ventilation units, add separators to form hot/cold containment, seal unused server faces) gave a 50% RHI improvement and a 31% RI improvement. The AAU retrofit (reposition racks, separators, seal unused bays) gave a 75% RTI improvement and an 18% RHI improvement. RCI-HI can fall even when airflow is well organised if supply air is below the recommended minimum, so supply temperature and flow must be tuned separately from containment.
Limits: two small pilot rooms (2 and 6 racks), so results do not transfer directly to large halls. The paper presents the work as a KPI-guided retrofit workflow that fits the EU Energy Efficiency Directive reporting regime.
Key points
- PSNC is an open-aisle micro data centre with 2 racks and 9 active servers cooled by ceiling-mounted units; AAU has 6 racks and 21 active servers cooled by two fan-coil units.
- AAU measurements used 16 calibrated Dantec 54R103 anemometers (0-5 m/s, ±5%) and PT100 sensors (setup uncertainty 0.21 °C); PSNC used IPMI data sampled every 10 minutes over two days.
- Turbulence by k-omega SST; servers as open-box models with Darcy-Forchheimer porous resistance (porosity 0.5); cooling units as fixed-flow black-box boundaries.
- Mesh3 was chosen after a five-level mesh study: 1,652,180 cells (PSNC) and 1,066,351 cells (AAU), y+ about 1.1-9.8.
- Mean absolute differences between simulated and measured server inlet temperatures were 1.3 °C (PSNC) and 1.6 °C (AAU); error was larger near a server whose airflow is rotated 90 degrees.
- KPI limits: ASHRAE recommended 18-27 °C and allowable 15-32 °C inlet temperatures.
- The PSNC retrofit gave a 50% RHI and 31% RI improvement; the AAU retrofit gave a 75% RTI and 18% RHI improvement.
- RCI-HI can fall even when airflow is well organised if supply air is below the recommended minimum, so supply temperature and flow must be tuned separately from containment.
Using it in design
- Set up the retrofit workflow as KPI-guided: with a validated CFD model compute RCI, RHI, RTI and the recirculation index, then test rack repositioning, separators, sealing unused bays and removing badly placed ventilation units in sequence.
- Record the simulated-versus-measured server inlet temperature difference (here 1.3-1.6 °C) as an acceptance criterion for CFD validation, and expect higher error near servers with rotated airflow.
- When RCI-HI comes out low, tune supply temperature and flow separately from containment; supply may be below the recommended minimum.
Who should read it
Engineers preparing KPI-guided airflow retrofits and EU Energy Efficiency Directive reporting for small and medium server rooms.
Document contents
- Introduction
- Methodology (experimental studies at the pilot data centers)
- Results and discussions (validation of the numerical model with the experimental data)
- Conclusions
Related standards
- ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
- EU Energy Efficiency Directive (EU) 2023/1791
- EU Code of Conduct on Data Centre Energy Efficiency
Read the document
cfd-two-european-dcs-2025.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Onur Muhammed Sarikaya; Mustafa Kuzay; Ender Demirel; Simon Pommerencke Melgaard; Jesper Ellerbaek Nielsen; Rasmus Lund Jensen; Ariel Oleksiak; Wojciech Szeliga
- Publisher
- Scientific Reports (Springer Science and Business Media LLC)
- Year
- 2025
- Volume
- 15
- Issue
- 1
- Pages
- 24952
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.nature.com
Original licence note
PDF open-access statement: licensed under a Creative Commons Attribution 4.0 International License (http://creativecommons.org/licenses/by/4.0/).
Citation
Onur Muhammed Sarikaya; Mustafa Kuzay; Ender Demirel; Simon Pommerencke Melgaard; Jesper Ellerbaek Nielsen; Rasmus Lund Jensen; Ariel Oleksiak; Wojciech Szeliga (2025). Energy efficiency enhancement in two European data centers through CFD modeling. Scientific Reports (Springer Science and Business Media LLC). 15(1), 24952. https://doi.org/10.1038/s41598-025-11048-0
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
