Comparing Performance Metrics of Partial Aisle Containments in Hard Floor and Raised Floor Data Centers Using CFD
Energies (MDPI AG) · Emelie Wibron, Anna-Lena Ljung et al.
An ANSYS CFX study of a small, reconfigurable test server room at RISE SICS North in Luleå, modelled as hard floor or raised floor, comparing side (end-of-row) and top cover partial containment at 100% and 50% of operating supply flow using RCI, RTI and Capture Index.
CC BY 4.0: share with attribution
On this page
Overview
The study numerically investigates the effect of partial aisle containment between server racks in hard-floor and raised-floor configurations. The room measures 6.484 × 7.000 × 3.150 m with a switchable hard-floor or raised-floor setup; perforated tiles had 56% and 77% open area and were modelled as fully open because open area was at least 50%; supply temperature was 18.3 °C. Validation used velocity profiles at heights of 0.6, 1.0, 1.4, 1.8 and 2.2 m at five locations in both open-aisle configurations, with discretisation error estimated with the GCI on three tetrahedral grids. The Reynolds stress model was used instead of k-epsilon because k-epsilon is less accurate in low-velocity regions.
At operating supply flow, RCI was 100% for both floor types while RTI was only about 40% (hard floor) and 50% (raised floor), meaning the room was well cooled but energy-inefficient because of oversupply. With supply cut by 50%, RTI rose above 80%, and recirculation appeared in all containment variants while RCI still looked acceptable.
At 50% flow, the Capture Index of end rack R1 was 44.66% on the open hard floor versus 86% on the open raised floor (96.88% with a raised floor and side cover), showing local problems that averaged metrics hide. The authors argue for combining temperature-based and airflow-based metrics. Airflow management improved in the raised-floor configurations, where a top or side cover fully prevented recirculation.
Limits: a small test room with uneven rack load; results depend on this room geometry, and only two supply flow rates (100% and 50%) were examined.
Key points
- The room measures 6.484 × 7.000 × 3.150 m with a switchable hard-floor or raised-floor setup; perforated tiles had 56% and 77% open area (modelled as fully open since at least 50%); supply temperature was 18.3 °C.
- Validation used velocity profiles at heights of 0.6, 1.0, 1.4, 1.8 and 2.2 m at five locations in both open-aisle configurations; discretisation error was estimated with the GCI on three tetrahedral grids.
- The Reynolds stress model was used instead of k-epsilon because k-epsilon is less accurate in low-velocity regions.
- At operating supply flow, RCI was 100% for both floor types while RTI was only about 40% (hard floor) and 50% (raised floor): well cooled but energy-inefficient because of oversupply.
- With supply cut by 50%, RTI rose above 80%, and recirculation appeared in all containment variants while RCI still looked acceptable.
- At 50% flow, the Capture Index of end rack R1 was 44.66% on the open hard floor versus 86% on the open raised floor (96.88% with a raised floor and side cover).
Using it in design
- In airflow assessment do not rely on RCI alone; RCI of 100% coexisted with RTI of 40-50%, showing oversupply and bypass. Report RTI and per-rack Capture Index together.
- When reducing supply flow (50%), recognise that recirculation can appear and averaged metrics can hide it; check per-rack CI for end racks.
- In raised-floor layouts, consider a side or top cover for partial containment; on a raised floor these fully prevented recirculation.
Who should read it
Cooling engineers evaluating partial aisle containment and supply-flow reduction using airflow metrics.
Document contents
- 1. Introduction
- 2. Method (2.1 Geometry, 2.2 Boundary Conditions, 2.3 Validation, 2.4 Grid Study, 2.5 Simulation Settings, 2.6 Performance Metrics)
- 3. Results and Discussion (3.1 Grid Study, 3.2 Validation, 3.3 Flow Field, 3.4 Comparison of Setups at Operating Conditions, 3.5 Comparison of Setups with 50% Supply Flow Rate)
- 4. Conclusions
Related standards
- ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
Read the document
partial-aisle-containment-metrics-2019.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Emelie Wibron; Anna-Lena Ljung; T. Staffan Lundström
- Publisher
- Energies (MDPI AG)
- Year
- 2019
- Volume
- 12
- Issue
- 8
- Pages
- 1473
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1: open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Citation
Emelie Wibron; Anna-Lena Ljung; T. Staffan Lundström (2019). Comparing Performance Metrics of Partial Aisle Containments in Hard Floor and Raised Floor Data Centers Using CFD. Energies (MDPI AG). 12(8), 1473. https://doi.org/10.3390/en12081473
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.