What Are Categories A and B in Circuit Breakers? (Devre Kesicilerde A ve B Kategorisi Nedir?)
Original title Devre Kesicilerde A ve B Kategorisi Nedir?
Federal Elektrik
A technical library article from Federal Elektrik explaining the two utilisation categories that IEC 60947-2 defines for low-voltage circuit breakers: category A trips without delay on a short circuit, category B trips with a short-time delay for selectivity, and the rated short-time withstand current (Icw) is defined only for category B.
On this page
Overview
The article is a short explanatory text published in the technical library of Federal Elektrik, a Turkish switchgear manufacturer. It defines a circuit breaker as a mechanical switching and protection device that can open and close under load and no-load conditions and that, on a short circuit or overload, disconnects the circuit it serves in line with its characteristics. Breakers open the circuit immediately or with a delay when the set current is reached, and the tripping characteristic may be thermal or magnetic.
IEC 60947-2 divides circuit breakers into two groups by application. Category A breakers are not intended for selectivity: under short-circuit conditions they trip instantaneously and interrupt without delay. The article notes that, on request, selective tripping can also be achieved with these breakers, depending on the load and the project conditions. Category B breakers are intended for selectivity: they are expected to provide the required short-time delay under a short circuit and therefore open later than category A breakers.
The cost of delayed tripping is that the breaker must carry the fault current for the duration of the delay. The article ties this to the Icw concept: the rated short-time withstand current is a value defined only for category B breakers, and under IEC 60947-2 these breakers must withstand the short-circuit current for a specified time. Federal circuit breakers are produced in category A as standard, and category B units are made on request.
The text stays at the conceptual level. It gives no numerical Icw values or durations, no delay setting ranges, no selectivity tables and no product-by-product list of categories. It therefore does not replace a selectivity study, but it is a short and accurate reference for clarifying the different roles of main and bus-tie breakers and downstream distribution breakers in data-centre distribution, and for deciding which breakers need an Icw value in the specification.
Key points
- IEC 60947-2 divides circuit breakers by application into two categories, A and B.
- Category A: not intended for selectivity; trips instantaneously, without delay, on a short circuit.
- Selective tripping can also be achieved with category A breakers on request, depending on load and project conditions.
- Category B: intended for selectivity; trips with the required short-time delay on a short circuit.
- A category B breaker must withstand the short-circuit current for the specified delay time.
- The rated short-time withstand current (Icw) is defined only for category B breakers.
- Federal circuit breakers are produced in category A as standard and in category B on request.
Using it in design
- Where time-delayed selectivity is needed at main incomers, generator incomers and bus-tie breakers, specify category B breakers and request the Icw value together with its duration.
- Compare the Icw of the selected category B breaker with the prospective short-circuit current at its location and with the delay time set.
- Use category A breakers on final circuits and distribution outgoers, and verify selectivity with the upstream level from the manufacturer's selectivity tables.
- Mark each breaker's category on the single-line diagram in the selectivity study, and check the short-time withstand of the busbars and cables downstream of a delayed breaker.
- Confirm the breaker's default category during procurement, and plan for lead time where category B is made on request.
Who should read it
Electrical designers carrying out protection coordination and selectivity studies in low-voltage distribution, engineers writing switchboard specifications, and newcomers to design.
Document contents
- Devre kesicinin tanımı
- IEC 60947-2'ye göre iki kullanım kategorisi
- Kategori A devre kesiciler
- Kategori B devre kesiciler ve Icw
- Federal devre kesicilerinde kategori
Publication details
- Authors
- Federal Elektrik
- Publisher
- Federal Elektrik
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.
Citation
Federal Elektrik Devre Kesicilerde A ve B Kategorisi Nedir?. Federal Elektrik. https://federalelektrik.com/teknik-kutuphane/devre-kesicilerde-a-ve-b-kategorisi-nedir
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
