What Are the Icu, Ics and Icw Ratings?
Original title Icu, Ics ve Icw Değerleri Nedir?
Federal Elektrik
A technical library note from Turkish manufacturer Federal Elektrik defines the three short-circuit ratings of moulded-case and air circuit breakers: Icu is verified with a two-break O-t-CO sequence, Ics with a three-break O-t-CO-t-CO sequence and must be at least 25% of Icu, and Icw is the current the breaker withstands for a set time without damage.
On this page
Overview
The note explains, briefly and by definition, the Icu, Ics and Icw values printed on moulded-case and air circuit breakers. The first two are known as short-circuit breaking capacities. The rated ultimate short-circuit breaking capacity Icu is the highest short-circuit current the breaker can interrupt twice in succession at the relevant rated operational voltage, in an open, wait, close-open (O-t-CO) sequence, and it is given as an r.m.s. value. After these operations the breaker is expected to carry its rated current.
The rated service short-circuit breaking capacity Ics is the highest current the breaker can interrupt three times in succession at the same voltage (O-t-CO-t-CO sequence), and it is expressed as a percentage of Icu. Ics must be at least 25% of Icu; in practice the 50%, 75% and 100% steps are common. The manufacturer states that on many of its own breakers Ics equals Icu, that is 100%. The time t in the sequence is the interval kept as short as possible while long enough for the breaker to be ready again, and not shorter than 3 minutes.
The rated short-time withstand current Icw is the short-circuit current the breaker can carry without damage under the appropriate test conditions for the time set by the manufacturer; it is also given as an r.m.s. value. The short-time delay associated with Icw must be at least 0.05 s, with preferred values of 0.05, 0.1, 0.25, 0.5 and 1 second. The note shows minimum Icw values in a table. This rating underpins time-delayed selectivity designs, in which the upstream breaker has to carry the fault current until the downstream device clears it.
Key points
- Icu (rated ultimate short-circuit breaking capacity): two interruptions in an O-t-CO sequence; given as an r.m.s. value.
- Ics (rated service short-circuit breaking capacity): three interruptions in an O-t-CO-t-CO sequence; given as a percentage of Icu.
- Ics must be at least 25% of Icu; common steps are 50%, 75% and 100%.
- The waiting time t in the sequence cannot be shorter than 3 minutes.
- Icw (rated short-time withstand current): the short-circuit current the breaker withstands without damage for the time set by the manufacturer.
- The short-time delay associated with Icw is at least 0.05 s; preferred values are 0.05, 0.1, 0.25, 0.5 and 1 s.
- On many Federal circuit breakers Ics is 100% of Icu.
Using it in design
- Compare the prospective short-circuit current calculated at each distribution point with the breaker's Icu; Icu cannot be lower than that current.
- On critical data-centre switchboards that must return to service quickly after a fault, prefer breakers whose Ics is 100% of Icu.
- For main and bus-coupler breakers with time-delayed selectivity, verify the Icw value and its duration (for example 0.5 s or 1 s) against the fault current and the set delay.
- Enter Icu, Ics and Icw in the breaker schedule together with the rated operational voltage; the values change with voltage.
- Do not compare products on Icu alone; a breaker with a low Ics percentage may have to be replaced after its first fault.
Who should read it
Electrical engineers designing low-voltage switchboards and protection coordination, and technical buyers selecting circuit breakers.
Document contents
- Rated ultimate short-circuit breaking capacity (Icu)
- Rated service short-circuit breaking capacity (Ics)
- Rated short-time withstand current (Icw)
Publication details
- Authors
- Federal Elektrik
- Publisher
- Federal Elektrik
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.
Citation
Federal Elektrik Icu, Ics ve Icw Değerleri Nedir?. Federal Elektrik. https://federalelektrik.com/teknik-kutuphane/icu-ics-ve-icw-degerleri-nedir
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.