What Are the Icu, Ics and Icw Ratings?

Original title Icu, Ics ve Icw Değerleri Nedir?

Federal Elektrik

A technical library note from Turkish manufacturer Federal Elektrik defines the three short-circuit ratings of moulded-case and air circuit breakers: Icu is verified with a two-break O-t-CO sequence, Ics with a three-break O-t-CO-t-CO sequence and must be at least 25% of Icu, and Icw is the current the breaker withstands for a set time without damage.

On this page

Overview

The note explains, briefly and by definition, the Icu, Ics and Icw values printed on moulded-case and air circuit breakers. The first two are known as short-circuit breaking capacities. The rated ultimate short-circuit breaking capacity Icu is the highest short-circuit current the breaker can interrupt twice in succession at the relevant rated operational voltage, in an open, wait, close-open (O-t-CO) sequence, and it is given as an r.m.s. value. After these operations the breaker is expected to carry its rated current.

The rated service short-circuit breaking capacity Ics is the highest current the breaker can interrupt three times in succession at the same voltage (O-t-CO-t-CO sequence), and it is expressed as a percentage of Icu. Ics must be at least 25% of Icu; in practice the 50%, 75% and 100% steps are common. The manufacturer states that on many of its own breakers Ics equals Icu, that is 100%. The time t in the sequence is the interval kept as short as possible while long enough for the breaker to be ready again, and not shorter than 3 minutes.

The rated short-time withstand current Icw is the short-circuit current the breaker can carry without damage under the appropriate test conditions for the time set by the manufacturer; it is also given as an r.m.s. value. The short-time delay associated with Icw must be at least 0.05 s, with preferred values of 0.05, 0.1, 0.25, 0.5 and 1 second. The note shows minimum Icw values in a table. This rating underpins time-delayed selectivity designs, in which the upstream breaker has to carry the fault current until the downstream device clears it.

Key points

  1. Icu (rated ultimate short-circuit breaking capacity): two interruptions in an O-t-CO sequence; given as an r.m.s. value.
  2. Ics (rated service short-circuit breaking capacity): three interruptions in an O-t-CO-t-CO sequence; given as a percentage of Icu.
  3. Ics must be at least 25% of Icu; common steps are 50%, 75% and 100%.
  4. The waiting time t in the sequence cannot be shorter than 3 minutes.
  5. Icw (rated short-time withstand current): the short-circuit current the breaker withstands without damage for the time set by the manufacturer.
  6. The short-time delay associated with Icw is at least 0.05 s; preferred values are 0.05, 0.1, 0.25, 0.5 and 1 s.
  7. On many Federal circuit breakers Ics is 100% of Icu.

Using it in design

  • Compare the prospective short-circuit current calculated at each distribution point with the breaker's Icu; Icu cannot be lower than that current.
  • On critical data-centre switchboards that must return to service quickly after a fault, prefer breakers whose Ics is 100% of Icu.
  • For main and bus-coupler breakers with time-delayed selectivity, verify the Icw value and its duration (for example 0.5 s or 1 s) against the fault current and the set delay.
  • Enter Icu, Ics and Icw in the breaker schedule together with the rated operational voltage; the values change with voltage.
  • Do not compare products on Icu alone; a breaker with a low Ics percentage may have to be replaced after its first fault.

Who should read it

Electrical engineers designing low-voltage switchboards and protection coordination, and technical buyers selecting circuit breakers.

Document contents

  1. Rated ultimate short-circuit breaking capacity (Icu)
  2. Rated service short-circuit breaking capacity (Ics)
  3. Rated short-time withstand current (Icw)

Publication details

Authors
Federal Elektrik
Publisher
Federal Elektrik
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.

Citation

Federal Elektrik Icu, Ics ve Icw Değerleri Nedir?. Federal Elektrik. https://federalelektrik.com/teknik-kutuphane/icu-ics-ve-icw-degerleri-nedir

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.