ECARO-25 Valuable Asset Fire Protection

Fike · Fike Corporation

A three-page 2010 Fike paper that walks through agent quantity and nozzle layout for the HFC-125 (ECARO-25) clean agent in a 40 x 40 ft telecom room, at a design concentration of 8.0 % v/v.

On this page

Overview

The paper introduces ECARO-25, a total flood system using HFC-125 (DuPont FE-25), for normally occupied Class A spaces such as computer rooms, data storage, telecom switch stations and clean rooms. The agent extinguishes by absorbing heat and interfering with the combustion chain reaction without reducing oxygen, so it is described as no threat to people present at discharge.

It contrasts the system with water-based protection, which it says does not protect business continuity because of slower suppression and water damage, while ECARO-25 is non-conductive, non-corrosive and leaves no residue. The system is stated to be FM and UL approved and covered by NFPA 2001 and ISO 14520.

The technical value is the design example. For a Class A telecom facility of 40 x 40 ft with a 10 ft ceiling and a 2 ft subfloor, the room is 16,000 ft3 (minimum 439 lb) and the subfloor 3,200 ft3 (minimum 88 lb). The suggested practice is to start at 8.2 % v/v and protect both with 542 lb of agent in one 1000 lb container. Discharge time is 9.9 seconds.

As a manufacturer document, the example is tied to the product's own listings and approvals. The calculation method is instructive, but a real project must be re-verified against the current NFPA 2001 edition, the agent's environmental status and local rules.

Key points

  1. ECARO-25 agent is HFC-125 (DuPont FE-25), presented as a Halon alternative with zero ozone depletion potential and low global warming potential.
  2. It is a total flood system for Class A fires; the paper says Class A assets are more than 90 percent of applications.
  3. The example room is 40 x 40 ft with a 10 ft ceiling and 2 ft subfloor: room volume 16,000 ft3, subfloor 3,200 ft3.
  4. Minimum design concentration is 8.0 % v/v; with a flooding factor of 0.0274 lb/ft3 the room needs at least 439 lb and the subfloor at least 88 lb.
  5. Suggested practice starts at 8.2 % v/v (factor 0.0282 lb/ft3): room 452 lb, subfloor 90 lb, one 1000 lb container filled with 542 lb.
  6. To limit turbulence, nozzle flow is kept at or below 20 lb/sec over a 10-second discharge; the room uses four nozzles of about 113 lb each.
  7. Four nozzles are also used under the floor because of cable congestion; discharge time in the example is 9.9 seconds.

Using it in design

  • Calculate connected volumes such as subfloor and ceiling void separately and include them in the agent quantity.
  • Start the calculation above the minimum concentration (8.2 % v/v in the example) so flow calculation confirms minimum agent delivery to every zone.
  • Limit nozzle flow to about 20 lb/sec over a 10-second discharge and balance nozzle placement; do not push nozzle coverage limits in a crowded cable subfloor.
  • Consider an engineered design in which one container protects several volumes (room and subfloor).
  • Check the current NFPA 2001 and ISO 14520 editions, environmental rules and the product's FM and UL approvals when selecting the agent.

Who should read it

Fire engineers designing clean agent systems and specialists reviewing gas suppression calculations for telecom and data rooms.

Document contents

  1. Introduction
  2. Applications
  3. The problem: downtime
  4. The solution: ECARO-25
  5. Selecting a long term clean agent system
  6. ECARO-25 system design example

Related standards

  • NFPA 2001
  • ISO 14520

Publication details

Authors
Fike Corporation
Publisher
Fike
Year
2010
Document number
CAAP 040
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Copyright © Fike Corporation All Rights Reserved (p. 3); copy hosted by a distributor

Citation

Fike Corporation (2010). ECARO-25 Valuable Asset Fire Protection. Fike. CAAP 040. https://horton-group-34jd.squarespace.com/s/fike_fe-25_valuable_asset_paper.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.