Technical guideFree to readYear not stated

In the Data Center - Where and What Am I Testing?

Fluke Networks

A Fluke Networks white paper that walks through the ANSI/TIA-942-A functional areas (ER, MDA, IDA, HDA, ZDA, EDA), stating which fibre or copper links to test in each and the common best practices.

On this page

Overview

The paper organises data centre cabling testing around the functional areas defined by ANSI/TIA-942-A. TIA-942-A references the TIA-568 series and adds data centre specific information: minimum recommendations for pathways and spaces, backbone and horizontal cabling. The applications, cabling and connectivity encountered differ by area, and the paper describes these differences in turn.

In the entrance room (ER), outside plant cable transitions to the data centre backbone; the main cable is single-mode fibre carrying applications such as 40GBASE-LR4, 100GBASE-ER4 and 100GBASE-LR4, and termination is usually by fusion splice. The service provider demarcation is mostly tested by the provider. The main distribution area (MDA) houses core switches, and single-mode or multimode fibre with duplex LC/SC or MPO is tested. The optional intermediate distribution area (IDA) is used in large, multi-floor data centres.

The horizontal distribution area (HDA) houses aggregation, access, SAN and KVM switches; both fibre uplinks and Category 6 or higher copper for 1000BASE-T or 10GBASE-T are tested. The zone distribution area (ZDA) is an optional consolidation point with no active equipment. In the equipment distribution area (EDA), top-of-rack designs use SFP+ or SFP28 twinax direct attach cables (DACs).

Common best practices: end face inspection and cleaning, encircled flux (EF) compliant testing for 40G and 100G multimode links, the 1-cord reference method (a 2-cord reference can give optimistic results and negative loss), bidirectional measurement in Tier 2 OTDR testing, and alien crosstalk and shield integrity testing for 10GBASE-T. The paper is a manufacturer white paper and lists its own test products at the end; the test method explanations are generally applicable.

Key points

  1. ANSI/TIA-942-A references the TIA-568 series and gives minimum pathway, space, backbone and horizontal cabling recommendations for data centre areas.
  2. In the ER the main cable is single-mode fibre carrying applications such as 40GBASE-LR4, 100GBASE-ER4 and 100GBASE-LR4; fusion splicing is the most common termination.
  3. The MDA houses core switches; single-mode and multimode fibre with duplex LC/SC or MPO is tested.
  4. The IDA is optional and used in large multi-floor or multi-room data centres.
  5. The HDA houses horizontal cross-connects; fibre uplinks and Category 6 or higher copper are tested together.
  6. The ZDA contains no active equipment and should not contain a cross-connect.
  7. In the EDA, top-of-rack designs use SFP+ or SFP28 twinax DAC cables.
  8. EF-compliant testing is required by standards for 40G and 100G multimode links, and the 1-cord reference method is preferred.
  9. For 10GBASE-T server links, alien crosstalk testing and shield integrity are critical.

Using it in design

  • Divide the test plan by TIA-942-A areas and list in advance the link types to be tested in each (single-mode, multimode, MPO, copper, DAC).
  • Clarify in the contract who tests the service provider demarcation.
  • Write an EF-compliant tester and the 1-cord reference into the specification for multimode links at 40G and above.
  • Make end face inspection and cleaning a standard step of the acceptance process.
  • If 10GBASE-T is planned, add alien crosstalk and shield integrity tests to the acceptance criteria.

Who should read it

Test technicians certifying data centre cabling, commissioning engineers and those preparing acceptance test plans.

Document contents

  1. Overview
  2. Starting in the Entrance Room (ER)
  3. Moving On To the Main Distribution Area (MDA)
  4. The Optional Intermediate Distribution Area (IDA)
  5. Somewhere in the Horizontal Distribution Area (HDA)
  6. Perhaps in a Zone Distribution Area (ZDA)
  7. Ending in the Equipment Distribution Area (EDA)
  8. Best Practices Hold True

Publication details

Authors
Fluke Networks
Publisher
Fluke Networks
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.

Citation

Fluke Networks In the Data Center - Where and What Am I Testing?. Fluke Networks. https://flukenetworks.com/edocs/white-paper-data-center-where-and-what-am-i-testing.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.