Technical guideFree to readYear not stated

Frigel IndustrialChiller 3HL: Air Cooled Water Chiller Specification Sheet

Original title Frigel 3HL-SPECS.SI.EN.5060.A4.01.00, technical data p.3

Frigel

Frigel 3HL air-cooled twin-screw chiller: 8 models, 300-1450 kW, 0-25°C water, ST to 45°C and HT to 55°C ambient; capacity is given at 15/25°C (water/ambient, 5 K delta-T) and 10/35°C.

On this page

Overview

The sheet presents the 3HL industrial water chiller series, with a double circuit and high-efficiency double screw compressors. Water working temperature is 0 to +25°C and units can be installed outdoors or indoors with suitable fans. The standard ST configuration is designed for ambient up to about 45°C and the HT version for ambient up to 55°C; refrigerant is R134a. The standard range has 8 models from 300 to 1450 kW. Capacity control is continuous over 25-100% with variable-speed screw compressors.

Technical data tables are given separately for 50 Hz (400 V) and 60 Hz (460 V), and each model's capacity is stated at two conditions: 15°C/25°C (water temperature/ambient temperature, water delta-T 5 K) and 10°C/35°C. At 50 Hz, model 1450 in ST gives 1450 and 1106 kW, and in HT 1152 and 872 kW. Tables also give installed compressor power, fan count and airflow, evaporator water flow and pressure drop, connection size, sound level and weight. Footnotes call for glycol at 0°C ambient or set points below +7°C, and EC fans above -15°C ambient, EH fans below.

Three fan options exist: TC (phase-cut speed control), EC (brushless variable speed, more than 30% lower consumption, noise below 57 dB(A)) and EH (high head, for ducted indoor installation and heat recovery). The evaporator is shell-and-tube, expansion valves are electronic, the microprocessor control has a touch screen and can connect to the MiND digital supervision system. The standard hydraulic configuration is without pumps and tank.

Key points

  1. 8 models: 300, 400, 500, 650, 800, 950, 1150, 1450; 300-1450 kW; twin screw compressors, two circuits, R134a.
  2. Water working temperature 0-25°C; ST ambient to about 45°C, HT to 55°C; overall operating range -15°C to +55°C.
  3. Capacity control by variable-speed screw compressors over 25-100%.
  4. Capacity conditions: 15°C/25°C (water/ambient, 5 K delta-T) and 10°C/35°C; 50 Hz ST model 1450: 1450 kW and 1106 kW; HT: 1152 and 872 kW.
  5. HT 300 gives 264 kW at 15/25°C and 199 kW at 10/35°C; at 50 Hz the ST version exists only for models 500 and above.
  6. EC fans cut consumption by more than 30% with noise below 57 dB(A); sound level at 10 m is 63.3-69.8 dB(A).
  7. Net weight ranges from 2,720 kg (HT 300) to 9,950 kg (ST 1450).
  8. Glycol must be added for low ambient (0°C) or set points below +7°C.

Using it in design

  • Read capacity at both conditions: the 10/35°C row shows the capacity loss at hot ambient and higher water temperature (1450 ST: from 1450 kW to 1106 kW).
  • If your data centre design ambient exceeds 45°C, choose the HT version and confirm its 55°C capacity with the manufacturer.
  • Take water delta-T on a 5 K basis in hydraulic calculations; evaporator pressure drop and flow come from the table.
  • In cold climates, write the glycol share and the EC/EH fan split (-15°C threshold) into the design specification.
  • Since pumps and tank are separate, add the hydraulic configuration (N) and buffer volume to the design.

Who should read it

Mechanical designers and procurement engineers selecting air-cooled screw chillers.

Document contents

  1. Introduction and advantages
  2. Main features and options
  3. Technical features
  4. Technical data 50 Hz
  5. Technical data 60 Hz

Publication details

Authors
Frigel
Publisher
Frigel
Year
Year not stated
Document number
3HL-SPECS.SI.EN.5060.A4.01.00
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Frigel Frigel 3HL-SPECS.SI.EN.5060.A4.01.00, technical data p.3. Frigel. 3HL-SPECS.SI.EN.5060.A4.01.00. https://vacca.es/wp-content/uploads/2022/03/3HL-SPECS.SI_.EN_.5060.A4.01.00.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.