Technical guideFree to read2024

Friterm V Type Dry Coolers with Axial Fans: Product and Selection Catalog, 2024

Original title Aksiyal Fanlı V Tipi Kuru Soğutucular: Seçim ve Uygulama Bilgileri

Friterm

Friterm's FDW V type dry cooler catalog (2024, Turkish/English) offers 55 to 2,490 kW capacity, 2 to 20 fans and four sound levels, with selection at 25 °C air and 40/35 °C 34% ethylene glycol using Qn = (Q / f1) x f2.

On this page

Overview

The document is the bilingual Turkish and English product and selection catalog for Friterm's FDW V type dry coolers with axial fans. The series is built for outdoor installation in Standard (S), Low (L), Quiet (Q) and Extremely Quiet (E) types. Fans are arranged in single rows of 1 to 10 and double rows of 2 to 20, and capacity ranges from 55 to 2,490 kW. The new generation offers Ø800 and Ø910 mm fans with 6 sound levels for Ø800 and 8 for Ø910.

The coil uses staggered copper tubes and aluminium fins; standard fin pitches are 2.1, 2.5 and 3.2 mm. The casing is galvanized steel with epoxy polyester powder paint (RAL 7044); magnelis, hot-dip galvanized or stainless options exist. Each fan chamber is separated by baffles so idle fans do not windmill. Fans are ZIEHL-ABEGG, EBM or equivalent external-rotor, two-speed types; EC fans are optional. External-rotor motors work in ambient from -40 to +50 °C / +65 °C, with IP54 protection and insulation class F. Fan data range from Ø910 S at 900/700 rpm, 3.3/2.3 kW and 94/88 dB(A) sound power to Ø910 E at 420/305 rpm, 0.41/0.21 kW and 59/51 dB(A).

The capacity standard is 34% ethylene glycol water, 25 °C inlet air, 40/35 °C fluid temperatures and 0 m altitude. The selection formula is Qn = (Q / f1) x f2; the altitude factor f2 is 1.04 at 500 m, 1.07 at 1,000 m, 1.16 at 2,000 m and 1.25 at 3,000 m. The result is approximate and FPS 6.0 software is recommended for accuracy. Fan speed control options are FMC-S (5 steps, special 15), FMC-V (voltage), FMC-F (frequency), FMC-F-APSF (all-pole sine filter) and FMC-EC. Options include direct spraying and Ecomesh spraying for adiabatic cooling.

Sound pressure levels are calculated from fan sound power at 10 m by the EN 13487 surface method. The company's test room can run calorimetric tests per EN 328, EN 327 and EN 1048 with Eurovent RS 7/C and ANSI/ASHRAE 33 references. It is a product catalog; the data are manufacturer figures.

Key points

  1. FDW V type dry coolers: capacity 55 to 2,490 kW; fan count 1 to 10 in a single row and 2 to 20 in a double row.
  2. Four sound types: S (standard), L (low), Q (quiet), E (extremely quiet); fan diameters Ø800 and Ø910 mm.
  3. Capacity standard: 34% ethylene glycol water, inlet air 25 °C, fluid 40/35 °C, altitude 0 m.
  4. Selection formula Qn = (Q / f1) x f2; altitude factor f2: 500 m 1.04; 1,000 m 1.07; 1,500 m 1.11; 2,000 m 1.16; 2,500 m 1.21; 3,000 m 1.25.
  5. Fan data examples (Ø910, 400 V, Δ/Y): S 900/700 rpm, 3.3/2.3 kW, 94/88 dB(A); E 420/305 rpm, 0.41/0.21 kW, 59/51 dB(A).
  6. Speed control options: FMC-S (5 steps, special 15), FMC-V, FMC-F, FMC-F-APSF (sine filter mandatory for external-rotor motors), FMC-EC.
  7. Adiabatic cooling options: direct spraying and Ecomesh mesh spraying; Ecomesh reduces water use and keeps spray from touching the fins directly.
  8. Coil fin pitches 2.1, 2.5, 3.2 mm; coated aluminium, magnesium alloy and copper fins and stainless tube and casing options.
  9. Sound pressure levels are computed at 10 m per EN 13487; the test room works to EN 328, EN 327, EN 1048 and Eurovent RS 7/C with ANSI/ASHRAE 33 references.

Using it in design

  • When selecting a dry cooler, convert the required capacity to the catalog's 40/35 °C, 25 °C air, 34% glycol, 0 m condition with f1 and f2; a higher data center fluid temperature changes f1, so confirm with FPS software.
  • On noise-limited sites compare S, L, Q and E sound types using the 10 m sound pressure values; EC fans or frequency control help noise and energy.
  • At high-altitude sites apply the f2 correction (for example 1.07 at 1,000 m) to capacity.
  • In hot climates evaluate the adiabatic spray option for peak ambient capacity against water use (WUE).
  • For external-rotor fans, plan the all-pole sine filter requirement and choose the speed control method on energy, noise and investment.

Who should read it

Mechanical designers selecting dry coolers and free cooling circuits, especially for data center and industrial projects in Turkey.

Document contents

  1. Developments in new generation FDW dry coolers
  2. Friterm motor control and monitoring system (FMC)
  3. Features and applications
  4. Classification
  5. Fans and sound levels
  6. Standard and optional accessories
  7. Capacity standards and dry cooler selection
  8. Water spraying systems
  9. Vibration dampers
  10. Technical data tables and test facilities

Publication details

Authors
Friterm
Publisher
Friterm
Year
2024
Document number
BK VDC Rev.1 / 01.08.2024
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Üreticinin herkese açık kaynağı okundu. Açık erişim yeniden dağıtım izni değildir; tam metin kütüphaneye alınmaz. Son sayfada tarih ve Friterm tüm hakları saklıdır bildirimi vardır. Türkçe/İngilizce belge; language tr Türkçe gövde nedeniyle kullanıldı.

Citation

Friterm (2024). Aksiyal Fanlı V Tipi Kuru Soğutucular: Seçim ve Uygulama Bilgileri. Friterm. BK VDC Rev.1 / 01.08.2024. https://www.friterm.com/storage/documents/01JRF8VNEHZRVB2Q34SXV2P75N.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.