GW Modular Data Center Fan Wall (FNW): Preliminary Selection Sales Sheet

Original title Data Center Fan Wall (FNW)

GW Modular

GW Modular's FNW-200/400/650/1000 chilled-water fan wall family: 200-1000 kW nominal, about 28,000-120,000 CFM, with preliminary selection data of 1,034 kW net sensible for the FNW-1000.

On this page

Overview

The two-page sheet introduces GW Modular's factory-built chilled-water fan wall platform for hyperscale, AI/HPC, colocation and enterprise white space. The platform was developed with structural frame, coil package, fan array, piping, controls and factory acceptance test (FAT) discipline. Perimeter or gallery-side deployment and corridor service access are intended. The family comprises FNW-200, 400, 650 and 1000: nominal 200/400/650/1000 kW, 4-12 EC fans and 6/8/10-row chilled-water coils.

Typical module elements include a copper-tube aluminium-fin coil, an EC centrifugal or plug fan array with fan-cell isolation, factory-piped CHWS/CHWR headers with PICV or EPIV valves, a control panel with leak detection, BACnet/IP and optional Modbus. Panels are 2 inch insulated, the base rail 4 inch and the drain pan sloped. Scalability is expressed through N, N+1 and phased expansion strategies.

A sample selection is given for the FNW-1000-G1: 1,102 kW gross coil sensible and 1,034 kW net sensible; 120,000 ACFM with 12 EC fans (10,000 CFM each); coil face velocity 625 FPM and 192 sq ft total net finned face area; water 286 GPM at 71.6°F entering and 97.9°F leaving (26.3°F delta-T); unit water pressure drop 15.0 psi including an internal engineering allowance; 216 x 148.5 x 60 in as two stacked 108 in sections. The sheet states that final capacities, coil selections and fan curves are project-specific and must be validated before release.

Key points

  1. Family FNW-200/400/650/1000: nominal 200-1000 kW, preliminary airflow range about 28,000-120,000 CFM.
  2. 4-12 EC fans and 6, 8 or 10-row chilled-water coil options.
  3. FNW-1000-G1: 1,102 kW gross and 1,034 kW net sensible, 120,000 ACFM, 12 fans at 10,000 CFM.
  4. Coil face velocity 625 FPM and 192 sq ft total net finned face area.
  5. Water: 286 GPM, 71.6°F entering / 97.9°F leaving (about 22°C / 36.6°C), delta-T 26.3°F (about 14.6 K).
  6. Unit water pressure drop 15.0 psi (about 103 kPa) including an internal engineering allowance.
  7. Size 216 x 148.5 x 60 in (about 5.49 x 3.77 x 1.52 m), two stacked 108 in sections.
  8. Factory piping, PICV/EPIV valves, leak detection and BACnet/IP; redundancy planned as N, N+1 and phased expansion.

Using it in design

  • Select on project-specific net sensible capacity rather than nominal; account for the gross-to-net difference (1,102 vs 1,034 kW) as fan heat.
  • Check the 26.3°F delta-T against your chilled-water design; on a low delta-T plant capacity and flow change.
  • Add the 15 psi unit pressure drop to the pump head calculation.
  • Verify the module height of about 5.5 m as two stacked sections against building height and the transport route.
  • For N+1, state the fan cell isolation and block-off plate option in the redundancy scheme.

Who should read it

Mechanical designers planning fan wall cooling in hyperscale and colocation white space.

Document contents

  1. Product family and key advantages
  2. Fan wall detail and operating envelope
  3. Typical module elements and applications
  4. FNW-1000 submitted selection

Publication details

Authors
GW Modular
Publisher
GW Modular
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

GW Modular Data Center Fan Wall (FNW). GW Modular. https://gwmodular.com/datasheets/GW-Modular-FNW-Sales-Sheet.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.