GW Modular Data Center Fan Wall (FNW): Preliminary Selection Sales Sheet
Original title Data Center Fan Wall (FNW)
GW Modular
GW Modular's FNW-200/400/650/1000 chilled-water fan wall family: 200-1000 kW nominal, about 28,000-120,000 CFM, with preliminary selection data of 1,034 kW net sensible for the FNW-1000.
On this page
Overview
The two-page sheet introduces GW Modular's factory-built chilled-water fan wall platform for hyperscale, AI/HPC, colocation and enterprise white space. The platform was developed with structural frame, coil package, fan array, piping, controls and factory acceptance test (FAT) discipline. Perimeter or gallery-side deployment and corridor service access are intended. The family comprises FNW-200, 400, 650 and 1000: nominal 200/400/650/1000 kW, 4-12 EC fans and 6/8/10-row chilled-water coils.
Typical module elements include a copper-tube aluminium-fin coil, an EC centrifugal or plug fan array with fan-cell isolation, factory-piped CHWS/CHWR headers with PICV or EPIV valves, a control panel with leak detection, BACnet/IP and optional Modbus. Panels are 2 inch insulated, the base rail 4 inch and the drain pan sloped. Scalability is expressed through N, N+1 and phased expansion strategies.
A sample selection is given for the FNW-1000-G1: 1,102 kW gross coil sensible and 1,034 kW net sensible; 120,000 ACFM with 12 EC fans (10,000 CFM each); coil face velocity 625 FPM and 192 sq ft total net finned face area; water 286 GPM at 71.6°F entering and 97.9°F leaving (26.3°F delta-T); unit water pressure drop 15.0 psi including an internal engineering allowance; 216 x 148.5 x 60 in as two stacked 108 in sections. The sheet states that final capacities, coil selections and fan curves are project-specific and must be validated before release.
Key points
- Family FNW-200/400/650/1000: nominal 200-1000 kW, preliminary airflow range about 28,000-120,000 CFM.
- 4-12 EC fans and 6, 8 or 10-row chilled-water coil options.
- FNW-1000-G1: 1,102 kW gross and 1,034 kW net sensible, 120,000 ACFM, 12 fans at 10,000 CFM.
- Coil face velocity 625 FPM and 192 sq ft total net finned face area.
- Water: 286 GPM, 71.6°F entering / 97.9°F leaving (about 22°C / 36.6°C), delta-T 26.3°F (about 14.6 K).
- Unit water pressure drop 15.0 psi (about 103 kPa) including an internal engineering allowance.
- Size 216 x 148.5 x 60 in (about 5.49 x 3.77 x 1.52 m), two stacked 108 in sections.
- Factory piping, PICV/EPIV valves, leak detection and BACnet/IP; redundancy planned as N, N+1 and phased expansion.
Using it in design
- Select on project-specific net sensible capacity rather than nominal; account for the gross-to-net difference (1,102 vs 1,034 kW) as fan heat.
- Check the 26.3°F delta-T against your chilled-water design; on a low delta-T plant capacity and flow change.
- Add the 15 psi unit pressure drop to the pump head calculation.
- Verify the module height of about 5.5 m as two stacked sections against building height and the transport route.
- For N+1, state the fan cell isolation and block-off plate option in the redundancy scheme.
Who should read it
Mechanical designers planning fan wall cooling in hyperscale and colocation white space.
Document contents
- Product family and key advantages
- Fan wall detail and operating envelope
- Typical module elements and applications
- FNW-1000 submitted selection
Publication details
- Authors
- GW Modular
- Publisher
- GW Modular
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
GW Modular Data Center Fan Wall (FNW). GW Modular. https://gwmodular.com/datasheets/GW-Modular-FNW-Sales-Sheet.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.