H.Stars 40STD R134a water-cooled screw chiller table

Original title H.Stars Screw Type Chiller / Heat Pump Unit: R134a water-cooled technical parameters

H.Stars

The H.Stars 40STD R134a water-cooled screw chiller table lists 26 models from 40STD-MF100WS4 (68 kW) to 40STD-MF5220WT4 (3,513 kW) at 17/12 °C evaporator and 30/35 °C condenser water.

On this page

Overview

This December 2023 H.Stars (Guangzhou) news page introduces the 40STD screw chiller family. It has four series: water-cooled chiller, water-source heat pump, air-cooled chiller and air-source heat pump. The water-cooled series uses twin-screw semi-hermetic compressors, the manufacturer's own evaporator and condenser, thermostatic or electronic expansion valves and a microcomputer controller. Capacity is advertised as 70-3,000 kW with chilled-water outlet of 5-20 °C.

The technical table is given for R134a at 380 V, 3-phase, 50 Hz. It lists 26 models: 16 WS4, 9 WD4 and one WT4. Nominal cooling capacity runs from 68 kW (19 USRT) to 3,513 kW (999 USRT), and compressor input power from 14 kW to 576 kW. Pipe diameter, water flow, water-side pressure drop, noise, shipping weight and operating weight are given for condenser and evaporator.

The nominal condition is evaporator inlet/outlet water at 17/12 °C, condenser inlet/outlet at 30/35 °C and a fouling factor of 0.088 m².°C/kW as published. Chilled water range is 5-20 °C and cooling water range 15-40 °C. The electrical input in the table covers the compressor only, since this is a water-cooled unit with no fans or pumps.

The page is a product news item and gives no COP or IPLV. The fouling factor unit is kept as published and should be confirmed with the manufacturer before use.

Key points

  1. The 40STD family has four series; capacity 70-3,000 kW and chilled-water outlet 5-20 °C.
  2. The R134a water-cooled table has 26 models: 16 WS4, 9 WD4, 1 WT4.
  3. Nominal capacity runs from 68 kW (MF100WS4) to 3,513 kW (MF5220WT4).
  4. Compressor input power is 14-576 kW.
  5. Nominal condition: evaporator 17/12 °C, condenser 30/35 °C, fouling factor 0.088 m².°C/kW.
  6. Cooling water range is 15-40 °C.
  7. Operating noise 73-88 dB(A); operating weight 1,130-22,000 kg.
  8. Power in the table is compressor power only.

Using it in design

  • When comparing capacity for data-centre chiller selection, check that the 17/12 °C evaporator condition matches the project chilled-water temperatures.
  • Confirm the unit of the published fouling factor with the manufacturer and compare it with your design fouling allowance.
  • Treat the power input as compressor-only and add tower, pump and fan power separately for system COP or PUE calculations.
  • Use the water-side pressure drop and pipe diameters as inputs to pump head and piping design.
  • For plant rooms with noise limits, compare the 73-88 dB(A) range with the acoustic specification.

Who should read it

Mechanical designers and procurement engineers selecting water-cooled screw chillers and comparing model tables.

Document contents

  1. 40STD family introduction
  2. Standard configuration
  3. R22 technical parameters
  4. R134a technical parameters
  5. Notes

Publication details

Authors
H.Stars
Publisher
H.Stars
Year
2023
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

H.Stars (2023). H.Stars Screw Type Chiller / Heat Pump Unit: R134a water-cooled technical parameters. H.Stars. https://hstarschiller.com/h-stars-screw-type-chiller-heat-pump-unit_n130

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.