Haier SuperClima R32 Inverter Air-Cooled Modular Chiller Catalogue (2024)

Original title Haier 2024 Chillers Catalogue, p.9 specifications

Haier

Haier's SuperClima R32 inverter air-cooled modular chillers (CA0070, CA0100, CA0140HANH) give 65 to 130 kW cooling, SEER 4.6 to 4.88, cooling from -20 to 53 °C ambient and combination of up to 16 modules.

On this page

Overview

The document is the SuperClima R32 inverter air-cooled modular chiller section of Haier's 2024 chiller catalogue. There are three models: CA0070HANH, CA0100HANH and CA0140HANH. The catalogue sets out the regulatory frame (MEES, ErP Lot 21 Regulation (EU) 2016/2281 and F-Gas): ErP Lot 21 sets minimum seasonal efficiency for air-cooled chillers below 400 kW at 149% in January 2018 and 161% in January 2021. Under F-Gas, from 2025 refrigerants above GWP 750 (R22, R410A) are restricted in new equipment, and R32 is presented as an option within that frame.

The units cover cooling, heating and domestic hot water (DHW). They have a Ø1000 mm DC fan, a shell-and-tube evaporator (patented design resistant to frosting and fouling), a one-piece U-shaped tube-fin coil and a DC inverter scroll compressor with EVI technology. Ambient range is -20 to 53 °C in cooling and -30 to 50 °C in heating; leaving water is -5 to 20 °C in cooling (-5 to 5 °C with glycol) and 20 to 60 °C in heating. Up to 16 units combine under one controller to reach 2,080 kW.

In the specification table, cooling capacity at 7 °C leaving water and 35 °C ambient is 65, 100 and 130 kW with EER 2.82, 3.24 and 2.90; at 18 °C leaving water capacity is 73, 110 and 145 kW with EER 3.85, 4.70 and 3.60. SEER is 4.6, 4.88 and 4.82; ηs,c is 181%, 192% and 190%. Sound power is 88, 88 and 91 dB(A) and R32 charge 10, 2x11 and 2x11 kg. Data are calculated to EN 14511 and EN 14825 and the maker states they are indicative.

Key points

  1. Three models: CA0070HANH, CA0100HANH, CA0140HANH; cooling capacity 65, 100 and 130 kW (7 °C water, 35 °C ambient).
  2. EER (7 °C water): 2.82, 3.24 and 2.90; with 18 °C water capacity is 73, 110 and 145 kW and EER 3.85, 4.70 and 3.60.
  3. SEER 4.6, 4.88 and 4.82; ηs,c 181%, 192% and 190%; heating COP up to 5.00.
  4. Ambient range is -20 to 53 °C cooling and -30 to 50 °C heating; leaving water in cooling -5 to 20 °C (-5 to 5 °C with glycol).
  5. Up to 16 units can be combined on one controller; capacity up to 2,080 kW.
  6. Sound power is 88, 88 and 91 dB(A); sound pressure 71, 70 and 72 dB(A); quiet mode lowers fan speed.
  7. Refrigerant R32; charge 10, 11x2 and 11x2 kg; electronic expansion valve.
  8. Size: CA0070 1265 x 1210 x 2260 mm (525 kg operating), CA0100 and CA0140 2260 x 1255 x 2260 mm (940 kg).
  9. ErP Lot 21: minimum seasonal efficiency for air-cooled chillers below 400 kW is 161% from January 2021; F-Gas restricts refrigerants above GWP 750 from 2025.

Using it in design

  • For data center auxiliary areas or partial-load rooms, consider modular inverter chillers for the combination of up to 16 units and the redundancy it allows.
  • Raising leaving water temperature lifts EER markedly (CA0100: 3.24 at 7 °C versus 4.70 at 18 °C); on plants without free cooling prefer a warmer water loop.
  • Catalogue values are at EN 14511 and EN 14825 conditions; confirm capacity with the manufacturer at ambient above 35 °C.
  • Because of regulatory requirements (ErP Lot 21 minimum seasonal efficiency and F-Gas GWP limits), put refrigerant and efficiency class in the specification.
  • Compare sound power (88 to 91 dB(A)) and quiet mode values with environmental noise limits.

Who should read it

Mechanical designers and consultants selecting air-cooled modular chillers.

Document contents

  1. About Haier
  2. Reducing carbon emissions and regulation (MEES, ErP Lot 21, F-Gas)
  3. Applications and product line-up
  4. R32 modular series features
  5. Wide operating range
  6. DC fan, shell-and-tube exchanger, tube-fin exchanger, inverter compressor
  7. Operating envelope, 16-unit combination, intelligent defrosting, low sound, easy installation, controller
  8. Specifications

Publication details

Authors
Haier
Publisher
Haier
Year
2024
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Haier (2024). Haier 2024 Chillers Catalogue, p.9 specifications. Haier. https://haierhvac.eu/sites/haierhvac-eu/files/2025-04/Haier_2024_Catalogue_Chillers_ENG.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.