Technical guideFree to readYear not stated

Air Cooling: Global Solutions

Haier

Haier's data centre air-cooling portfolio: 200 kW and 120 kW fan walls, 30-200 kW chilled-water and 5.5-100 kW DX precision units, plus heat-pipe in-row and near-rack units.

On this page

Overview

The page lists Haier's air-side cooling products for data centre applications by family: fan walls, chilled-water (CW) solutions, DX precision air conditioners and heat-pipe units. Each product gets a short set of values such as nominal cooling capacity, airflow and fan type. It is an overview of the application portfolio rather than a catalogue.

Two fan walls are listed. The dual-coil fan wall offers 200 kW and 50,000 m³/h and supports three modes: direct free cooling, pre-cooling and mechanical cooling. Its free-cooling switch point is given as 20°C and above, with COP up to 6.0 (EWT/LWT 35/40°C, outdoor 37°C). The chilled-water fan wall provides 120 kW and 34,000 m³/h with EC fans.

In the CW and DX ranges, the DTline in-row unit covers 30/60 kW (5,000-10,000 m³/h), the DTroom chilled-water room unit 40-200 kW (11,500-43,000 m³/h, temperature ±1°C, humidity ±5%), the DTroom DX unit 20-100 kW and the DTstation 5.5-15 kW (2,100-3,800 m³/h). Both heat-pipe products use R134a: an in-row unit at 25/45/60 kW and a near-rack fan wall at 60/72 kW. The page gives few model codes or rating conditions, so the values suit preliminary sizing rather than selection.

Key points

  1. Dual-coil fan wall: 200 kW, 50,000 m³/h, free-cooling switch at 20°C and above, COP up to 6.0 (EWT/LWT 35/40°C, outdoor 37°C).
  2. Chilled-water fan wall: 120 kW, 34,000 m³/h, EC fans; hot and cold aisles are enclosed and coil air goes straight to IT intakes.
  3. DTline chilled-water in-row: 30/60 kW, 5,000-10,000 m³/h, hot-swappable fans.
  4. DTroom chilled-water room unit: 40-200 kW, 11,500-43,000 m³/h, upflow or downflow, ±1°C temperature and ±5% humidity control.
  5. DTroom DX: 20-100 kW, 5,800-26,000 m³/h; DTstation: 5.5-15 kW, 2,100-3,800 m³/h for small rooms and edge sites.
  6. Heat-pipe in-row: 25/45/60 kW, 5,000/10,500/14,000 m³/h, R134a, leak detection and dual power supply.
  7. Near-rack heat-pipe fan wall: 60/72 kW, 20,000/23,000 m³/h, a design that keeps water away from the rack.

Using it in design

  • Use the fan wall capacities for preliminary sizing only; rating conditions (entering air, water temperatures) are not given, so confirm the order model and final capacity with the manufacturer.
  • Compare the 20°C free-cooling switch point against local climate data to estimate annual free and mechanical cooling hours.
  • Compare in-row and near-rack heat-pipe units against chilled-water units for in-room water risk and redundancy planning.
  • Match unit airflow to enclosed-aisle demand: the unit must cover the combined airflow need of the racks it serves.

Who should read it

Mechanical designers selecting in-room cooling equipment and procurement teams screening product families.

Document contents

  1. Fan Wall Cooling Solutions
  2. Chilled Water (CW) Cooling Solutions
  3. Precision Cooling (DX) Cooling Solutions
  4. In-Row Heat Pipe Cooling Unit
  5. Near-Rack Heat Pipe Fan Wall

Publication details

Authors
Haier
Publisher
Haier
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Haier Air Cooling: Global Solutions. Haier. https://www.haier.com/business/build/global-solutions/product-display/air-cooling/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.