Heng An Cooling Equipment Catalogue: BNX International Market
Original title Heng An Cooling Equipment Catalogue: BNX international market
Heng An
Shandong Heng An catalogue of closed-circuit cooling towers, evaporative condensers, air-cooled heat exchangers and radiators; BNX counter-flow towers are tabulated from 12 to 280 m3/h (37/32 °C water, 28.2 °C wet bulb).
On this page
Overview
The catalogue covers products of Shandong Heng An Eco-technologies and affiliates (Weifang Heng An Imp&Exp, Heng An Radiator Group): closed-circuit cooling towers, evaporative condensers, air-cooled heat exchangers and radiators. Content is a company profile, research and development, certificates (pressure vessel manufacturing licence, CE certificates for closed towers and evaporative condensers, a patent for a combined-flow evaporative condenser), product sections and a list of Chinese and international projects. The text is bilingual Chinese and English.
A closed-circuit tower cools process fluid in an internal coil with spray water and air and is commonly chosen for commercial and industrial process cooling. The BNX series is counter-flow: air enters at the bottom, mixes with the falling spray water in reverse flow as saturated hot air and is discharged by fans at the top; water is recovered by a special drift eliminator and re-sprayed. With no infill inside, coil heat-transfer area is larger; the structure is compact and uses little floor area, suiting fluids with high inlet temperature. Spray water is pumped over the coil at no less than 6.8 l/s, keeping the surface wet, improving heat transfer and reducing scaling.
The BNX international-market table gives model, cooling flow (m3/h), fan count and power, air volume, spray pump count and power, weight and dimensions. BNX-10: 12 m3/h, one 1.5 kW fan, 18,000 m3/h air, 0.55 kW pump, 890 kg net and 1660 kg operating weight; BNX-100: 100 m3/h, 2 x 4 kW fans, 5120 kg net; BNX-280: 280 m3/h, 4 x 5.5 kW fans, 2 pumps x 4 kW, 11,720 kg net. The table design condition is 28.2 °C wet bulb, 37 °C inlet and 32 °C outlet water. Per the notes the data must not be used for construction and must be reconfirmed at purchase, and coil connection positions are approximate. The same model codes repeat in the China-market table with different values, so the market configuration must be kept.
Key points
- The BNX international table runs from BNX-10 (12 m3/h) to BNX-280 (280 m3/h).
- Design condition: wet bulb 28.2 °C, water inlet 37 °C, outlet 32 °C.
- BNX-10: 1.5 kW fan, 18,000 m3/h air, 0.55 kW pump, 890 kg net weight.
- BNX-100: 100 m3/h, 2 fans x 4 kW, 5120 kg net weight.
- BNX-280: 280 m3/h, 4 fans x 5.5 kW, 2 pumps x 4 kW, 11,720 kg net weight.
- Counter-flow, no-infill design; spray water over the coil at no less than 6.8 l/s.
- Notes: table not for construction, connection positions approximate; the China-market table has different values for the same model codes.
Using it in design
- Compare the table condition (28.2 °C wet bulb, 37/32 °C) with the project summer design condition when selecting a closed-circuit tower; confirm capacity with the maker for other conditions.
- Do not mix the international and China-market tables; the same model code carries different values.
- Use fan and spray pump power as separate lines in the total electrical load.
- Use operating weight in roof load and erection planning; do not treat connection positions as final drawings.
- For circuits needing clean process fluid or high inlet temperature, compare the counter-flow closed tower with an open tower on water use and cost.
Who should read it
Mechanical designers selecting closed-circuit cooling towers for data-centre heat rejection and purchasing engineers.
Document contents
- About Heng An
- Research and development
- Honours and certificates
- Closed circuit cooling towers (BNX counter flow, BHX combined flow)
- Evaporative condensers
- Air cooled heat exchangers
- Radiators
- Projects (China and international)
Publication details
- Authors
- Heng An
- Publisher
- Heng An
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Heng An Heng An Cooling Equipment Catalogue: BNX international market. Heng An. https://coinrefriair.com/wp-content/uploads/2021/03/14.-Catalogo-de-Condensadores-Evaporativos.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.