Technical guideFree to read2022

Hexonic D.COOL Dry Coolers

Hexonic

Hexonic's 2022 D.COOL dry cooler brochure: horizontal and vertical models, process liquid range of -20 to 100 °C, 10 bar maximum pressure and modular sizes with 800/910 mm fans.

On this page

Overview

The brochure presents Hexonic's closed-circuit dry cooler range. Target applications are data centre cooling systems, industrial processes, power plants and large-volume air conditioning. The dry cooler is positioned as one of the most economical ways to reject excess heat to ambient air, and various process media can be used.

On construction, it uses 12 mm copper tubes, aluminium fins (2.3, 2.5 or 2.5 mm spacing options, depending on application), baffle tube stabilising plates and high-silver solder. The casing is zinc-coated carbon steel, wet painted or powder coated, with C3 as the standard corrosion class. Fans are low-noise axial units of 800 and 910 mm diameter with EC or AC motors, compliant with ErP 2015, and sound levels start below 40 dB(A).

The model family covers horizontal (SDF-H-N, SDF-H-S, SDV-H-N) and vertical (SDF-V-N, SDV-V) units. Dimension tables give series and parallel module combinations from 1x1 to 7x2; for example SDF-H-N 1x1 is about 1 551 mm long and 7x1 about 10 553 mm. Working parameters are a minimum process liquid temperature of -20 °C, a maximum of 100 °C and a maximum pressure of 10 bar.

Options include a weatherproof electrical cabinet, PID controller with frequency converter, PID for EC fans, touch-screen PLC, individual fan switches, vibration dampers, extended legs of 1000 or 1200 mm and an adiabatic cooling system. The adiabatic system lets the cooler operate when ambient temperature exceeds the process medium temperature by raising air humidity and lowering its temperature. The brochure gives dimensions and operating limits rather than capacity tables.

Key points

  1. Process liquid temperature range is -20 to 100 °C, with a maximum working pressure of 10 bar (145 psi).
  2. Fans are 800 mm and 910 mm axial, low-noise, with EC or AC motors; sound levels start below 40 dB(A).
  3. The heat exchanger uses 12 mm copper tubes and aluminium fins with spacing of 2.3, 2.5 or 2.5 mm chosen by application.
  4. Standard corrosion protection is class C3; other classes and three colours (standard RAL 7035, silver RAL 9006, anthracite RAL 7016) are offered.
  5. Models are horizontal (SDF-H-N, SDF-H-S, SDV-H-N) and vertical (SDF-V-N), in module combinations from 1x1 to 7x2.
  6. SDF-H-N 1x1 is 1 551 mm long, SDF-H-N 7x1 is 10 553 mm; SDF-V-N 1x1 is 1 721 mm.
  7. Adiabatic cooling allows operation even when ambient temperature is above the process liquid temperature.
  8. Control options include PID with frequency converter, PID for EC fans and a touch-screen PLC.

Using it in design

  • When selecting a dry cooler, compare the process liquid temperature and pressure limits (-20/100 °C, 10 bar) with the circuit design values.
  • In coastal or polluted environments, check whether the C3 standard is sufficient and specify a higher corrosion class if not.
  • For noise-constrained sites, evaluate the sub-40 dB(A) fan options and EC fan control against the sound limit.
  • Decide on the need for an adiabatic system from the annual ambient temperature distribution, for capacity loss in hot hours.
  • Take capacity figures from the manufacturer's selection software or tested tables, not from this brochure, which gives only sizes and operating limits.

Who should read it

Mechanical designers and specifying engineers selecting dry coolers for data centre and process cooling circuits.

Document contents

  1. Why choose Hexonic dry coolers
  2. Fans
  3. Robustness (materials and corrosion)
  4. Efficiency
  5. Designed to specific needs (options)
  6. Adiabatic system and colours
  7. Horizontal and vertical models, technical parameters
  8. Working parameters and model coding

Publication details

Authors
Hexonic
Publisher
Hexonic
Year
2022
Document number
EN.ver.1.2022
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Hexonic (2022). Hexonic D.COOL Dry Coolers. Hexonic. EN.ver.1.2022. https://hexonic.com/wp-content/uploads/2021/07/HEXONIC_DRY-COOLERS_EN_2022-03-28.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.