Technical guideFree to readYear not stated

Hiref Data Center Catalogue: Perimeter, In-Row, Fan Wall, CDU, Dry Cooler and Chiller Solutions

Original title HiRef Data Center catalogue

HiRef

Hiref's data centre catalogue: 33-257 kW chilled-water and 24-185 kW DX perimeter units, FanWall HBCV (45-461 kW), rear doors, CDUs, dry coolers and chillers, with capacity at four air/water conditions.

On this page

Overview

The catalogue lists Hiref's data centre range by category: perimeter units (TRF CW, CS, CF, DX A, W/Z, F, D/K/Q and the NRG series with modulating compressors, JREF radial and centrifugal fan series, HTI for small rooms), high-density cooling (NRCD/NRCV, HRCC, MRAC mini rack cooler, rear door), FanWall HBCV, adiabatic DataBatic (10-330 kW), CDUs, modular dry coolers and remote condensers, and scroll, screw and oil-free centrifugal chillers and heat pumps. Every page carries the notice that technical data may change without notice and must not be used at design stage.

For chilled-water perimeter units capacity is given at several conditions: version A at 24°C/50% air with 7/12°C water, 30°C/35% air with 10/15°C water, and 35°C/30% air with 15/20°C water; versions B and C use higher water outlet temperatures (18 and 22°C, 23 and 27°C). For TRF CW 040-240 in version A (24°C, 7/12°C) capacity is 38.1-257.1 kW and sensible heat ratio 0.74-0.86. The double-circuit chilled-water version has two separate hydraulic circuits with a valve on each.

FanWall HBCV spans 45-461 kW with double coil, double valve and a fully redundant refrigeration circuit; EC fans modulate in constant delta-T, constant airflow or constant delta-P mode, with a PICV valve and Modbus interface. At 30°C/35% air and 10/18°C water the models give 48.5, 97, 118.2, 173.4, 236.4 and 346.8 kW; at 35°C/25% air and 10/18°C water, 63.7-460.6 kW. The catalogue also describes a 1 MW N+1 data centre example in Amsterdam at 36°C and a 25% energy reduction target with the adiabatic system.

Key points

  1. TRF CW chilled-water perimeter: 33-257 kW; TRF CS (slim): 58-242 kW; TRF CF: 78-329 kW.
  2. DX perimeter: TRF DX A 24-160 kW, W/Z 24-165 and 28-185 kW, indirect free-cooling F 23-150 kW; modulating NRG A 9-159 kW.
  3. Refrigerants R-410A and R-513A; the chiller section includes R-454B, R-1234ze, R-515B and R-744.
  4. Capacity conditions: 24°C/50% with 7/12°C water; 30°C/35% with 10/15°C; 35°C/30% with 15/20°C; versions B and C use 18, 22, 23 and 27°C outlet water.
  5. TRF CW 040-240 (24°C/50%, 7/12°C water): 38.1-257.1 kW, SHR 0.74-0.86; a double-circuit chilled-water version is available.
  6. FanWall HBCV 051B-342B: 48.5-346.8 kW at 30°C/35% and 10/18°C water; 63.7-460.6 kW at 35°C/25% and 10/18°C water.
  7. HBCV airflow 8,700-62,200 m³/h, total fan power 0.7-5.8 kW, supply 400 V/3+N/50 Hz.
  8. High density: NRCD/NRCV 12-50 kW and 13-37 kW, HRCC 20-57 kW, MRAC 3-5 kW, DataBatic 10-330 kW.
  9. All data is marked not for design-stage use and subject to change.

Using it in design

  • Read capacity from the one of the four catalogue conditions closest to your design air and water temperatures; the high-temperature rows (10/18 and 15/20°C) suit designs that extend free cooling hours.
  • Use the catalogue to identify product family and range; it must not be used as design data, so take final values from the manufacturer's selection software.
  • Evaluate the double-circuit or double-coil (HBCV) configuration for critical hall redundancy.
  • Match the fan modulation mode (constant delta-T, constant airflow or constant delta-P) to underfloor pressure or contained aisle design.
  • Add water use and water treatment requirements of the adiabatic DataBatic option to the operating plan.

Who should read it

Mechanical designers screening in-room cooling and heat rejection equipment families.

Document contents

  1. Perimeter-mounted units
  2. High density cooling
  3. FanWall HBCV
  4. Adiabatic systems (DataBatic)
  5. Liquid cooling and CDU
  6. Dry cooler and remote condensers
  7. Liquid chillers and heat pumps

Publication details

Authors
HiRef
Publisher
HiRef
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

HiRef HiRef Data Center catalogue. HiRef. https://api.hiref.it/assets/downloads/DATA-CENTER_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.