Hiref Data Center Catalogue: Perimeter, In-Row, Fan Wall, CDU, Dry Cooler and Chiller Solutions
Original title HiRef Data Center catalogue
HiRef
Hiref's data centre catalogue: 33-257 kW chilled-water and 24-185 kW DX perimeter units, FanWall HBCV (45-461 kW), rear doors, CDUs, dry coolers and chillers, with capacity at four air/water conditions.
On this page
Overview
The catalogue lists Hiref's data centre range by category: perimeter units (TRF CW, CS, CF, DX A, W/Z, F, D/K/Q and the NRG series with modulating compressors, JREF radial and centrifugal fan series, HTI for small rooms), high-density cooling (NRCD/NRCV, HRCC, MRAC mini rack cooler, rear door), FanWall HBCV, adiabatic DataBatic (10-330 kW), CDUs, modular dry coolers and remote condensers, and scroll, screw and oil-free centrifugal chillers and heat pumps. Every page carries the notice that technical data may change without notice and must not be used at design stage.
For chilled-water perimeter units capacity is given at several conditions: version A at 24°C/50% air with 7/12°C water, 30°C/35% air with 10/15°C water, and 35°C/30% air with 15/20°C water; versions B and C use higher water outlet temperatures (18 and 22°C, 23 and 27°C). For TRF CW 040-240 in version A (24°C, 7/12°C) capacity is 38.1-257.1 kW and sensible heat ratio 0.74-0.86. The double-circuit chilled-water version has two separate hydraulic circuits with a valve on each.
FanWall HBCV spans 45-461 kW with double coil, double valve and a fully redundant refrigeration circuit; EC fans modulate in constant delta-T, constant airflow or constant delta-P mode, with a PICV valve and Modbus interface. At 30°C/35% air and 10/18°C water the models give 48.5, 97, 118.2, 173.4, 236.4 and 346.8 kW; at 35°C/25% air and 10/18°C water, 63.7-460.6 kW. The catalogue also describes a 1 MW N+1 data centre example in Amsterdam at 36°C and a 25% energy reduction target with the adiabatic system.
Key points
- TRF CW chilled-water perimeter: 33-257 kW; TRF CS (slim): 58-242 kW; TRF CF: 78-329 kW.
- DX perimeter: TRF DX A 24-160 kW, W/Z 24-165 and 28-185 kW, indirect free-cooling F 23-150 kW; modulating NRG A 9-159 kW.
- Refrigerants R-410A and R-513A; the chiller section includes R-454B, R-1234ze, R-515B and R-744.
- Capacity conditions: 24°C/50% with 7/12°C water; 30°C/35% with 10/15°C; 35°C/30% with 15/20°C; versions B and C use 18, 22, 23 and 27°C outlet water.
- TRF CW 040-240 (24°C/50%, 7/12°C water): 38.1-257.1 kW, SHR 0.74-0.86; a double-circuit chilled-water version is available.
- FanWall HBCV 051B-342B: 48.5-346.8 kW at 30°C/35% and 10/18°C water; 63.7-460.6 kW at 35°C/25% and 10/18°C water.
- HBCV airflow 8,700-62,200 m³/h, total fan power 0.7-5.8 kW, supply 400 V/3+N/50 Hz.
- High density: NRCD/NRCV 12-50 kW and 13-37 kW, HRCC 20-57 kW, MRAC 3-5 kW, DataBatic 10-330 kW.
- All data is marked not for design-stage use and subject to change.
Using it in design
- Read capacity from the one of the four catalogue conditions closest to your design air and water temperatures; the high-temperature rows (10/18 and 15/20°C) suit designs that extend free cooling hours.
- Use the catalogue to identify product family and range; it must not be used as design data, so take final values from the manufacturer's selection software.
- Evaluate the double-circuit or double-coil (HBCV) configuration for critical hall redundancy.
- Match the fan modulation mode (constant delta-T, constant airflow or constant delta-P) to underfloor pressure or contained aisle design.
- Add water use and water treatment requirements of the adiabatic DataBatic option to the operating plan.
Who should read it
Mechanical designers screening in-room cooling and heat rejection equipment families.
Document contents
- Perimeter-mounted units
- High density cooling
- FanWall HBCV
- Adiabatic systems (DataBatic)
- Liquid cooling and CDU
- Dry cooler and remote condensers
- Liquid chillers and heat pumps
Publication details
- Authors
- HiRef
- Publisher
- HiRef
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
HiRef HiRef Data Center catalogue. HiRef. https://api.hiref.it/assets/downloads/DATA-CENTER_EN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.