HiRef HDC Modular Dry Cooler

HiRef

HiRef's HDC modular dry cooler brochure lists three data-centre models from 372 to 1551 kW, rated at two outdoor air and fluid conditions (10°C and 35°C air) with 30% ethylene glycol.

On this page

Overview

The HiRef HDC range is a set of outdoor dry coolers developed for data-centre use. The brochure positions them for liquid-cooling systems and for sites where free cooling can be used. They are meant to work with water-cooled indoor equipment such as the W, F and K series cabinets and the XSB and XVA chillers, and can run on water-glycol mixtures up to 60%.

The frame is galvanised sheet steel with copper-pipe protection, and the outer panels are galvanised sheet finished in corrosion- and UV-resistant polyester paint. The coil uses copper tubes with wavy aluminium fins at a standard 2 mm spacing. Epoxy treatment, copper fins for marine sites and wider fin spacing for sandy environments are offered as options.

Modularity is the central idea: more heat exchangers can be connected to the master dry cooler as demand grows, without changing the customer-side piping, provided space for the extension is planned at design stage. Each unit carries a water circuit optimised for variable flow, on-board regulation with an integrated ATS, EC fans and a Modbus interface to the CMS.

The rating table covers three models (HDC 04H057E, 06H057E, 08H057E) at two conditions: 10°C air with 30/20°C fluid, and 35°C air with 45/40°C fluid, both with 30% ethylene glycol. The table gives no weight or electrical power, so those values must be obtained separately from the manufacturer.

Key points

  1. The range covers 372-1551 kW; supply is 400 V, 3-phase plus neutral, 50 Hz.
  2. At 10°C air, 30% ethylene glycol and 30/20°C fluid, capacity is 775.6 / 1163.4 / 1551.2 kW (models 04H, 06H, 08H).
  3. At 35°C air, 30% ethylene glycol and 45/40°C fluid, the same models give 372.4 / 558.6 / 744.8 kW.
  4. Fluid flow is 72000 / 108000 / 144000 l/h at the cold condition and 69200 / 103800 / 138400 l/h at the hot condition.
  5. Sound pressure at nominal speed, 2 m distance, is 89 / 91 / 92 dB(A).
  6. Dimensions (L×H×D) are 3750×3135×2250, 5625×3135×2250 and 7500×3135×2250 mm.
  7. Standard fin spacing is 2 mm; glycol up to 60% and epoxy or copper fin options are available.

Using it in design

  • Read capacity only from the row at the design outdoor temperature: the same model gives roughly half the 10°C capacity at 35°C.
  • Pick the table row closest to the real fluid temperatures of the liquid-cooling loop (30/20°C or 45/40°C) and request a manufacturer selection for intermediate points.
  • Weight and electrical power are not in the brochure; obtain them before structural, cable and switchgear sizing.
  • Reserve space and a pipe connection point for future add-on modules at the outset.
  • For coastal or dusty sites, specify the coil coating and fin spacing option in the tender documents.

Who should read it

Data-centre cooling designers and mechanical engineers selecting dry coolers for liquid cooling and free cooling.

Document contents

  1. Product features
  2. Finned coil
  3. Modular solution
  4. Silent operation
  5. Customization
  6. Technical data table

Publication details

Authors
HiRef
Publisher
HiRef
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

HiRef HiRef HDC Modular Dry Cooler. HiRef. https://api.hiref.it/assets/downloads/HDC_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.