Mission Critical Facilities: Artificial Intelligence and Dynamic Rotary UPS Systems
HITEC Power Protection
A HITEC Power Protection white paper arguing that, with AI racks reaching 50-100 kW and swinging loads, dynamic rotary UPS (DRUPS) units up to 3600 kVA can feed both IT and cooling from one no-break output.
On this page
Overview
The paper states that Dynamic Rotary UPS (DRUPS) systems have protected critical processes for over 60 years, are installed in hundreds of data centres and often run more than 25 years without replacement. Nominal unit power has grown to 3600 kVA. A conventional static UPS comprises a rectifier, batteries and an inverter and hands the load to a generator in long outages; a DRUPS merges a synchronous generator, a kinetic energy module and a diesel engine, drawing kinetic energy until the engine takes over.
The authors stress cooling continuity: rack consumption rises from a traditional average of 7 kW to 50-100 kW or more with AI hardware, a four- to fifteen-fold increase. Direct-to-chip liquid cooling can cut cooling-related energy by nearly 20%, but as a rule of thumb only 60-70% of GPU heat is captured that way, the rest goes to the room, and air cooling suffices only up to 30 kW racks. Both room and chip cooling are needed, and a thermal-inertia gap appears in an outage. The proposed simplification is to connect cooling directly to the DRUPS no-break output.
On the power side, AI racks are expected to move from 50-100 kW to 150 kW and later up to 500 kW. Breakers, busbars and PDUs are sized with little or no headroom and engineers assume close to 100% load. AI loads surge and sag, straining static UPSs; the integrated oversized alternator can absorb large load steps, inrush and short-circuit currents of 10-20 times nominal. It should be noted that this is a vendor white paper promoting its own technology.
Additional advantages cited are kinetic storage instead of batteries (no lithium-ion fire risk, recharge in minutes, unlimited cycles, at least 25 years of service), a redundant starting system, HVO fuel and fuel-saving modes, fully recyclable materials and a 40-50% smaller comparative UPS footprint.
Key points
- DRUPS units have been used for over 60 years, many run over 25 years unreplaced; nominal unit power reaches 3600 kVA.
- Rack consumption rises from a traditional 7 kW average to 50-100 kW or more with AI hardware (four- to fifteen-fold).
- Direct-to-chip liquid cooling can cut cooling energy by nearly 20%; only 60-70% of GPU heat is captured that way and air cooling suffices up to 30 kW racks.
- The cooling system, including motor and compressor loads, can be connected to the DRUPS no-break output; Uptime Institute has recommended this approach.
- AI racks may go from 50-100 kW to 150 kW, with 500 kW projected; breakers, busbars and PDUs are sized with little headroom, assuming near 100% load.
- The integrated oversized alternator can absorb short-circuit currents of 10-20 times nominal and large load steps.
- Kinetic storage recharges in minutes, has no cycle limit, runs at least 25 years and carries no lithium-ion fire risk.
- A 40-50% reduction in comparative UPS footprint and a lower TCO are claimed.
Using it in design
- For large AI campuses, compare a rotary UPS architecture against the static UPS plus generator chain on cost, space and operation; the paper is a vendor view, so ask for independent validation.
- In liquid-cooled racks, document which supply feeds the cooling pumps and CDUs together with ride-through and thermal inertia time.
- Size panels, busbars and PDUs for AI load with a near 100% continuous-load assumption.
- For load swings, write load-step, inrush and short-circuit contribution requirements into UPS and generator selection.
- Compare battery and kinetic storage options on fire risk, cycle life and recharge time.
Who should read it
Electrical designers and investment decision makers choosing large-scale UPS architecture for hyperscale and AI data centres.
Document contents
- Introduction
- HITEC Diesel Rotary UPS (DRUPS)
- Continuous cooling
- Understanding AI power requirements
- Selecting an uninterruptible power supply
- Additional advantages of Dynamic Rotary UPS
Publication details
- Authors
- HITEC Power Protection
- Publisher
- HITEC Power Protection
- Year
- Year not stated
- Document number
- Whitepaper AI DRUPS; Version 1.0 footer
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public manufacturer document or page inspected. No document-specific redistribution permission established; retain metadata and original short summaries only.
Citation
HITEC Power Protection Mission Critical Facilities: Artificial Intelligence and Dynamic Rotary UPS Systems. HITEC Power Protection. Whitepaper AI DRUPS; Version 1.0 footer. https://hitec-ups.com/wp-content/uploads/2026/01/HITEC-Whitepaper-Artificial-Intelligence-and-Dynamic-Rotary-UPS-Systems.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.