HLF Cooling LC Series Cooling Tower
HLF Cooling
HLF Cooling's LC series gives the specification and model table for single-cell round FRP cooling towers from 5 to 125 HRT; 100 HRT corresponds to 1300 L/min at a 37/32/27 °C nominal condition.
On this page
Overview
The brochure describes HLF Cooling's LC series round cooling towers and presents the series as high efficiency, compact, low noise and modular. The header states a 5-1000 HRT cooling capacity range; the technical table covers single-cell models from 5 to 125 HRT. Tower components (fan motor, pulleys, galvanised fan holder, FRP casing, ladder, PVC infill, sprinkler pipe and heads, FRP cold-water basin) are shown on a numbered diagram.
Specification sections are structure, casing, distribution, infill, basin, fan-motor-drive and access. The structure is hot-dip galvanised steel to BS 729; the casing is UV-resistant moulded fibreglass-reinforced polyester (FRP) with PVC louvers. The infill is high-grade PVC resistant to grease, oil, acid and alkali, with UV absorber and antioxidant. The cold-water basin is a galvanised frame laminated internally with FRP and has a suction strainer, make-up ball valve, overflow and drain. The fan is axial with adjustable pitch; the motor is IE1, TEFC, IP55, class F insulation, 415 V 3-phase 50 Hz, with the whole V-belt drive enclosed in an FRP cover. Distribution is by an open gravity hot-water basin and a PVC distribution pad above the infill. Ladder and fan guard are standard; a cage ladder and handrail are available on request at extra charge.
The single-cell table gives model HRT, flow (L/min), fan diameter, tower diameter, height, fan motor power, connection sizes (inlet, outlet, drain, overflow, make-up) and dry and operating weights. For example the 5 HRT model is for about 65 L/min, the 100 HRT model 1300 L/min and the 125 HRT model 1625 L/min. The nominal condition is 37/32/27 °C. Flow is in L/min and the tower rating must not be read as chiller tons.
Key points
- Single-cell round towers, 5-125 HRT in the table; 5-1000 HRT capacity range in the header.
- Nominal condition 37/32/27 °C (return/supply/wet bulb); flow in L/min.
- 100 HRT model is 1300 L/min, 125 HRT model 1625 L/min.
- Structure hot-dip galvanised steel to BS 729; casing UV-resistant FRP with PVC louvers.
- PVC infill resistant to grease, acid and alkali; open gravity hot-water basin.
- Axial fan with adjustable pitch; IE1 TEFC IP55 motor, 415 V 3-phase 50 Hz, V-belt drive.
- Table includes dimensions, connection sizes, dry and operating weight.
Using it in design
- Do not read tower HRT as chiller tons; select with project flow and the 37/32/27 °C or actual wet-bulb condition.
- Use operating weight and basin capacity in roof or foundation load calculation.
- Compare the IE1 motor class and V-belt drive with any efficiency target; carry fan power into the energy calculation separately.
- Carry inlet, outlet, drain, overflow and make-up connection sizes into the piping drawing.
- If several cells are needed, compare the multi-cell families (FC, HX).
Who should read it
Mechanical designers selecting cooling towers and engineers writing specifications.
Document contents
- LC series tower specification
- Structure
- Casing
- FRP distribution system
- Infill
- Cold-water basin and water sump
- Fan, motor and drive system
- Access and safety
- Technical detail for one cell
Publication details
- Authors
- HLF Cooling
- Publisher
- HLF Cooling
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
HLF Cooling HLF Cooling LC Series Cooling Tower. HLF Cooling. https://hlfcooling.com.my/brochures/LC%20SERIES.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.