HLF Cooling HX Series Cooling Tower
HLF Cooling
HLF Cooling's HX series gives the specification and a quick selection table of flow (m3/h) by temperature condition for multi-cell FRP cooling towers of 100-1280 HRT.
On this page
Overview
The brochure presents HLF Cooling's HX series multi-cell cooling towers: high efficiency, compact, low noise and modular. The capacity range is 100-1280 HRT. Tower components are shown on a numbered diagram; FRP access door, FRP hot-water basin, PVC distribution pack and FRP fan stack appear.
Specification sections are structure, casing, distribution, infill, basin, fan-motor-drive and access. The structure is hot-dip galvanised steel to BS 729; the casing is UV-resistant moulded fibreglass-reinforced polyester (FRP) with PVC louvers. The infill is high-grade PVC resistant to grease, oil, acid and alkali, with UV absorber and antioxidant. The cold-water basin is a galvanised frame laminated internally with FRP and has a suction strainer, make-up ball valve, overflow and drain. The fan is axial with adjustable pitch; the motor is IE1, TEFC, IP55, class F insulation, 415 V 3-phase 50 Hz, with the whole V-belt drive enclosed in an FRP cover. Hot water is distributed by an open gravity FRP hot-water basin and a PVC distribution pad above the infill.
The quick selection table gives flow (m3/h) for commonly used combinations of cold-water supply, hot-water return and wet-bulb temperature; other conditions are referred to the maker. This package uses the 37/32/27 °C column. Model rows start at HX 100-18 and proceed in steps such as 100, 125, 150, 175, 200 and 225 HRT. The tower HRT rating must not be read as chiller tons.
Key points
- Multi-cell tower, capacity range 100-1280 HRT.
- Quick selection table gives m3/h flow by return, supply and wet-bulb combination.
- Base condition 37/32/27 °C (return/supply/wet bulb); other conditions via the maker.
- Structure hot-dip galvanised steel to BS 729; casing UV-resistant FRP with PVC louvers.
- Infill PVC resistant to grease, acid and alkali.
- Motor IE1, TEFC, IP55, class F, 415 V 3-phase 50 Hz; V-belt drive inside an FRP cover.
- Hot water is distributed by an open gravity FRP hot-water basin and a PVC distribution pad above the infill.
Using it in design
- Select from the table or from the maker for the project's actual return, supply and summer wet-bulb temperature; do not take HRT as chiller tons.
- Set the cell count together with redundancy and part-load staging; check remaining flow when one cell is out of service.
- Verify operating weight, basin and dimensions against roof or foundation load and the layout drawing.
- Compare the IE1 motor and V-belt drive with the energy target and carry fan power as a separate line.
Who should read it
Mechanical designers selecting multi-cell cooling towers and engineers writing specifications.
Document contents
- HX series tower specification
- Structure
- Casing
- FRP distribution system
- Infill
- Cold-water basin and water sump
- Fan, motor and drive system
- Access and safety
- Quick selection table
Publication details
- Authors
- HLF Cooling
- Publisher
- HLF Cooling
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
HLF Cooling HLF Cooling HX Series Cooling Tower. HLF Cooling. https://hlfcooling.com.my/brochures/HX%20SERIES.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.