Technical guideFree to readYear not stated

HLF Cooling HX Series Cooling Tower

HLF Cooling

HLF Cooling's HX series gives the specification and a quick selection table of flow (m3/h) by temperature condition for multi-cell FRP cooling towers of 100-1280 HRT.

On this page

Overview

The brochure presents HLF Cooling's HX series multi-cell cooling towers: high efficiency, compact, low noise and modular. The capacity range is 100-1280 HRT. Tower components are shown on a numbered diagram; FRP access door, FRP hot-water basin, PVC distribution pack and FRP fan stack appear.

Specification sections are structure, casing, distribution, infill, basin, fan-motor-drive and access. The structure is hot-dip galvanised steel to BS 729; the casing is UV-resistant moulded fibreglass-reinforced polyester (FRP) with PVC louvers. The infill is high-grade PVC resistant to grease, oil, acid and alkali, with UV absorber and antioxidant. The cold-water basin is a galvanised frame laminated internally with FRP and has a suction strainer, make-up ball valve, overflow and drain. The fan is axial with adjustable pitch; the motor is IE1, TEFC, IP55, class F insulation, 415 V 3-phase 50 Hz, with the whole V-belt drive enclosed in an FRP cover. Hot water is distributed by an open gravity FRP hot-water basin and a PVC distribution pad above the infill.

The quick selection table gives flow (m3/h) for commonly used combinations of cold-water supply, hot-water return and wet-bulb temperature; other conditions are referred to the maker. This package uses the 37/32/27 °C column. Model rows start at HX 100-18 and proceed in steps such as 100, 125, 150, 175, 200 and 225 HRT. The tower HRT rating must not be read as chiller tons.

Key points

  1. Multi-cell tower, capacity range 100-1280 HRT.
  2. Quick selection table gives m3/h flow by return, supply and wet-bulb combination.
  3. Base condition 37/32/27 °C (return/supply/wet bulb); other conditions via the maker.
  4. Structure hot-dip galvanised steel to BS 729; casing UV-resistant FRP with PVC louvers.
  5. Infill PVC resistant to grease, acid and alkali.
  6. Motor IE1, TEFC, IP55, class F, 415 V 3-phase 50 Hz; V-belt drive inside an FRP cover.
  7. Hot water is distributed by an open gravity FRP hot-water basin and a PVC distribution pad above the infill.

Using it in design

  • Select from the table or from the maker for the project's actual return, supply and summer wet-bulb temperature; do not take HRT as chiller tons.
  • Set the cell count together with redundancy and part-load staging; check remaining flow when one cell is out of service.
  • Verify operating weight, basin and dimensions against roof or foundation load and the layout drawing.
  • Compare the IE1 motor and V-belt drive with the energy target and carry fan power as a separate line.

Who should read it

Mechanical designers selecting multi-cell cooling towers and engineers writing specifications.

Document contents

  1. HX series tower specification
  2. Structure
  3. Casing
  4. FRP distribution system
  5. Infill
  6. Cold-water basin and water sump
  7. Fan, motor and drive system
  8. Access and safety
  9. Quick selection table

Publication details

Authors
HLF Cooling
Publisher
HLF Cooling
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

HLF Cooling HLF Cooling HX Series Cooling Tower. HLF Cooling. https://hlfcooling.com.my/brochures/HX%20SERIES.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.