Technical guideFree to read2023

Huawei FusionCol8000-C110/220 chilled-water fan wall

Original title Huawei FusionCol8000-C110/220 Fan Wall Chilled Water Smart Cooling Solution

Huawei

Huawei FusionCol8000-C is a fan-wall chilled-water cooling unit with horizontal airflow, 20/28 °C water and modular combinations of 110 to 440 kW; EC fans are stated to save up to 30%.

On this page

Overview

This two-page 2023 Huawei data sheet presents the FusionCol8000-C110 and C220 fan-wall chilled-water solution. It is an in-room chilled-water unit that works with chillers and pumps in large data centres. Airflow is horizontal and no raised floor is needed. Applications include large cloud data centres, large and medium modular data centres and equipment rooms.

The sheet groups features under green, reliable, simple and smart. Chilled water in/out can be as high as 20/28 °C, and EC fans save up to 30% energy against conventional AC fans. At full load THDi is below 5% and power factor reaches 0.99; for a standalone module A, THDi is below 10%. Dual power supply switches automatically with zero cooling interruption.

The specifications table lists five module combinations: 110 kW (2 fans, 26,500 m³/h, 5.2 kW), 220 kW in two layouts (53,000-53,500 m³/h), 340 kW (81,000 m³/h, 15.9 kW) and 440 kW (8 fans, 106,000 m³/h, 20.9 kW). All values refer to 36 °C return air, 25% RH, 20/28 °C water and 80 Pa external static pressure.

The sheet is a product summary and has no water-side pressure drop, sound level or lifecycle data. AI-based efficiency optimisation depends on a separate Huawei solution (iCooling@AI).

Key points

  1. Chilled water in/out up to 20/28 °C to cut cooling energy.
  2. EC fans save up to 30% energy compared with conventional AC fans.
  3. Full-load THDi below 5% and power factor up to 0.99 (THDi below 10% for a standalone module A).
  4. Dual power supply with automatic transfer; zero cooling interruption during switching.
  5. Horizontal airflow; no raised floor needed.
  6. Module combinations of 110, 220, 340 and 440 kW.
  7. 110 kW module: 2 fans, 26,500 m³/h, 5.2 kW rated power, 1,090 kg.
  8. Nominal condition: 36 °C return air, 25% RH, 20/28 °C water, 80 Pa external static pressure.

Using it in design

  • When moving to 20/28 °C chilled water, recompute chiller and free-cooling hours at that water temperature.
  • Take the 110 kW module as the unit of redundancy and set the module count for N+1.
  • Reflect the 0.99 power factor and THDi below 5% in transformer and generator sizing on the distribution side.
  • Match the horizontal-airflow layout (contained aisle or direct hall) to a floor structure without a raised floor.
  • Compare the sheet's 36 °C return-air rating condition with the project's return-air temperature.

Who should read it

Mechanical designers selecting fan-wall or in-room chilled-water cooling for large cloud and modular data centres.

Document contents

  1. Introduction
  2. Application scenarios
  3. Features
  4. Specifications table

Publication details

Authors
Huawei
Publisher
Huawei
Year
2023
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Huawei (2023). Huawei FusionCol8000-C110/220 Fan Wall Chilled Water Smart Cooling Solution. Huawei. https://solar.huawei.com/admin/asset/v1/pro/view/fd55eb56e8c240bb8a3bd0454afabd11.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.