Huawei FusionCol8000-C: C210H Technical Specifications
Huawei
Huawei FusionCol8000-C210H is a horizontal-airflow chilled-water fan wall stating 210 kW total and sensible cooling capacity, 53,000 m3/h air volume and 380-415 V AC input.
On this page
Overview
Huawei Digital Power's FusionCol8000-C product page presents the chilled-water fan wall family for public cloud and large colocation DCs, IDCs and medium and large data centres of carriers, enterprises, governments and financial institutions. The model in the technical table is FusionCol8000-C210H: total and sensible capacity 210 kW, horizontal-flow air supply, air volume 53,000 m3/h, input voltage 380-415 V AC 50/60 Hz 3-phase + PE, dimensions 2350 x 1100 x 2450 mm.
The maker highlights five themes: iCooling AI-based efficiency optimisation (adjusting load rate in real time to control air volume), no-heat wet-film humidifying (zero-power humidifying), a very large heat exchanger supporting higher water temperature (the page cites 20 °C water temperature and a 15% reduction in chiller energy consumption), hot-swappable modular main control and fan drive modules (about 1 minute for maintenance), and one-click fault collection with automatic diagnosis.
Horizontal diffused air supply needs no raised floor; the maker says it cuts cooling system cost by 10%. Dual inputs with automatic switching and 6 kV surge filtering add reliability. Case studies on the page estimate annual savings of 13.245 million kWh and 7695 tons of carbon emissions for China Unicom Guangzhou. The table does not publish the full rating condition or electrical power.
Key points
- Model C210H: total and sensible capacity 210 kW.
- Horizontal air supply; air volume 53,000 m3/h.
- Supply 380-415 V AC, 50/60 Hz, 3-phase + PE; dual inputs with automatic switching.
- Dimensions 2350 x 1100 x 2450 mm (W x D x H).
- Maker says horizontal supply without a raised floor cuts cooling cost by 10%.
- The page cites a 15% cut in chiller energy at 20 °C water temperature.
- Main control and fan drive modules are hot-swappable; about 1 minute maintenance.
Using it in design
- Size the 210 kW unit with the hall load, fan-wall redundancy (N+1) and the hot/cold aisle concept.
- Because the table gives no rating condition, confirm capacity with the maker for water temperature and return air.
- Assess horizontal supply for air distribution and obstructions in halls without a raised floor.
- Connect the 380-415 V dual input to A/B power distribution; obtain the electrical load from the maker since it is not published.
- Evaluate the higher water-temperature target together with chiller selection and free-cooling hours.
Who should read it
Mechanical designers selecting chilled-water fan walls for large data centres and operations engineers.
Document contents
- Product overview
- AI-based energy saving
- Zero-power humidifying
- Higher water temperature
- Hot-swap maintenance
- Auto fault diagnosis
- Horizontal air supply
- Dual inputs
- Technical specifications
Publication details
- Authors
- Huawei
- Publisher
- Huawei
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Huawei Huawei FusionCol8000-C: C210H Technical Specifications. Huawei. https://digitalpower.huawei.com/en/data-center-facility/fusioncol8000c
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.