White paperFree to read2019

Lithium Battery Application in Data Centers (Data Center Facility White Paper 101)

Huawei Technologies Co., Ltd. (Huawei Digital Power)

A 2019 Huawei Digital Power white paper: for the same 200 kW, 30-minute backup, lithium batteries save 88% in weight and 68% in volume over VRLA; LFP chemistry is recommended for data centres.

On this page

Overview

The white paper sets out the case for moving from lead-acid to lithium-ion batteries in data centres. It says lead-acid's market share is falling fast because of short cycle life, large size, heavy weight and environmental impact in production, that lithium batteries are used in almost all 5G sites and in the data centres of some large internet providers outside China, and that lithium's share is predicted to match or pass lead-acid within 3-5 years.

The first section compares lithium's advantages numerically: cycle life, float-charge life, capacity loss in fast discharge and energy density. The second section discusses which lithium chemistry suits a data centre: LFP (lithium iron phosphate) and NCM (nickel cobalt manganese) are compared with LCO and LMO. LFP's olivine three-dimensional structure is stable and releases no oxygen on overcharge or overdischarge; NCM's layered two-dimensional structure releases oxygen in thermal runaway.

The safety comparison rests on a nail-penetration test: an 8 mm steel needle is driven through the geometric centre of the cell at 25 mm/s and observed for one hour. The LFP cell reaches a surface temperature of at most 80 degrees C with no burning or electrolyte leakage; the NCM cell burns within one second, goes into thermal runaway within four seconds and reaches 458 degrees C.

This is a manufacturer white paper and frames the case in lithium's favour; it has no system-level fire, BMS or cost comparison. For a data-centre designer its value is having the grounds for the chemistry choice and the space and weight difference between lead-acid and lithium for the same load in one place.

Key points

  1. Cycle life: lithium at least 3000 cycles at 100% DOD and at least 6000 at 50% DOD; lead-acid about 150 at 100% DOD and about 600 at 50% DOD.
  2. Float-charge life (25 degrees C, 70% EOL): lithium up to 15 years, lead-acid up to 7 years; lead-acid needs replacement every 3-7 years even on a good grid.
  3. Capacity released in fast discharge: lithium 100% at 0.1C, 1C and 2C and 95% at 4C; VRLA 100% at 0.1C, 60% at 1C, 40% at 2C and 20% at 4C.
  4. Energy density: by weight lithium 100-150 Wh/kg against 30-50 Wh/kg for lead-acid; by volume lithium 200-300 Wh/L against 60-90 Wh/L (about 3 to 1).
  5. In a 200 kW, 380 V, 30-minute backup example VRLA weighs 11,210 kg and lithium 1,400 kg; weight falls 88%, volume 68% and battery capacity 63% (300 Ah instead of 800 Ah).
  6. In the nail test the LFP cell reaches at most 80 degrees C and does not burn; the NCM cell burns in 1 second, goes into thermal runaway in 4 seconds and reaches 458 degrees C.
  7. Peak heat-generation power is given as about 1 W for LFP and about 80 W/min for NCM.
  8. Recommendation: NCM has higher energy density, LFP higher reliability; LFP is recommended for data centres to balance reliability and energy density.

Using it in design

  • Where floor loading or space is tight, calculate the weight and area difference between lithium and VRLA for the same autonomy; in the example weight falls 88% and volume 68%.
  • On weak or frequently interrupted grids, include the cycle-life difference (3000 against about 150 cycles at 100% DOD) in the battery replacement cost.
  • State the battery chemistry (LFP or NCM) in the specification and ask for thermal-runaway behaviour (oxygen release, peak heat generation) from product test reports.
  • For UPS duties needing short high-rate discharge, size batteries by capacity released at the stated C-rate, not by nameplate capacity.
  • Reflect the 3-7 year float life of lead-acid and the 15 year float life of lithium in the operations and replacement plan.

Who should read it

Electrical designers selecting data-centre UPS battery systems, capacity and space planners, and investment decision makers.

Document contents

  1. Foreword
  2. Why are lithium batteries needed? (basic concepts, long cycle life, long float-charging life, high discharge efficiency, high energy density)
  3. Why are LFP batteries needed? (stable structure, stable performance)
  4. Summary of data center lithium battery application

Related standards

  • IEC 62619
  • UL 9540A

Publication details

Authors
Huawei Technologies Co., Ltd. (Huawei Digital Power)
Publisher
Huawei Technologies Co., Ltd. (Huawei Digital Power)
Year
2019
Document number
Data Center Facility White Paper 101
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

'Copyright © 2019 HUAWEI TECHNOLOGIES CO., LTD. All Rights Reserved.'

Citation

Huawei Technologies Co., Ltd. (Huawei Digital Power) (2019). Lithium Battery Application in Data Centers (Data Center Facility White Paper 101). Huawei Technologies Co., Ltd. (Huawei Digital Power). Data Center Facility White Paper 101. https://digitalpower.huawei.com/upload-pro/index/index/Lithium-Battery-Application-in-Data-Centers-White-Paper.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.