HYFRA FleXX Technology, December 2017: Model Overview

Original title HYFRA FleXX Technology, 2017-12, p.4 Model Overview

HYFRA

HYFRA's FleXX industrial chillers with EC compressor, EC fan and electronic expansion valve: 3-64 kW, R410A, maximum ambient 42 °C; Sigma models recirculate water at 20 °C.

On this page

Overview

The document is HYFRA's 2017-12 FleXX Technology brochure. The Alpha (oil and emulsion circulating), Gamma (immersion) and Sigma (water recirculating) series each offer six models with cooling capacity from 3 to 64 kW. The ranges target industrial processes; they are not a product family designed for data centres.

The core of FleXX is demand-based operation: the EC compressor, EC fan and electronic expansion valve are adjusted together by a PLC that senses the heat load. The maker gives a chart showing about 30% less power consumption than the unregulated equivalent. A microchannel condenser reduces refrigerant charge, and temperature precision reaches ±0.1 K.

The model table gives capacity at 32 °C ambient and nominal conditions, power, sound pressure, airflow, weight and dimensions. A frequency converter allows switching between 3x380-480 V and 50/60 Hz without changing the unit. The FreeAdvance controller is freely programmable and offers remote maintenance. The brochure also describes turnkey, maintenance and training services.

The document is marketing in nature and gives no capacity at data-centre chilled-water conditions (such as 12/7 °C). For a designer its value is as an example of small air-cooled water recirculation and variable-speed compressor logic.

Key points

  1. Six models: 3-9, 6-16, 6-24, 8-34, 14-44, 17-64; cooling capacity 9.9 / 16.5 / 24.5 / 34.6 / 44.7 / 64.0 kW (32 °C ambient).
  2. Refrigerant R410A; maximum ambient temperature 42 °C; maximum temperature 40 °C.
  3. Power consumption (without pump or stirrer) runs from 2.77 kW to 17.8 kW.
  4. Sound pressure level 66.4-74.4 dB(A).
  5. Sigma models have flow of 1.6-10.5 m3/h, pump pressure 2.5-3.5 bar and a 120 or 300 litre tank.
  6. The maker shows a curve with roughly 30% lower power than the unregulated model.
  7. Temperature precision up to ±0.1 K; supply 3x380-480 V, 50/60 Hz.
  8. Sigma weighs 200-480 kg, with dimensions from 855x715x1555 mm to 1500x1000x2055 mm.

Using it in design

  • When selecting small air-cooled water recirculation for process and lab cooling, read capacity at the 32 °C ambient value and compare the 42 °C upper limit with the summer design condition.
  • Use the variable-speed EC compressor and fan logic as a comparison criterion for heat-rejection equipment that runs at part load.
  • Use the sound pressure level (66-74 dB(A)) in unit placement and noise-limit checks.
  • Before use on a data-centre warm-water loop, obtain capacity from the maker at the relevant temperature level; the table is given for 20 °C water.

Who should read it

Mechanical engineers comparing small air-cooled chillers and facility teams planning process cooling.

Document contents

  1. FleXX Technology
  2. Cooling Capacity Overview
  3. Innovative Chiller Technology
  4. Efficiency through Speed Control
  5. Flexibility for International Use
  6. Model Overview
  7. Service Solutions

Publication details

Authors
HYFRA
Publisher
HYFRA
Year
2017
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

HYFRA (2017). HYFRA FleXX Technology, 2017-12, p.4 Model Overview. HYFRA. https://hyfra.com/fileadmin/Dateien/PRODUKTE/HYFRA_FleXX/HYFRA-FleXX_Brochure_EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.