ICS Cool Energy i-Chiller Compact-n technical sheet

Original title ICS Cool Energy i-Chiller Compact-n, 05/23 v3, printed p.5

ICS Cool Energy

ICS Cool Energy's i-Chiller Compact-n is a series of compact R290 air-cooled process chillers of 1.7-4.4 kW; four models give 1.19-2.98 kW at 12/7 °C and 1.71-4.37 kW at 20/15 °C.

On this page

Overview

This May 2023 (v3) sheet presents ICS Cool Energy's i-Chiller Compact-n series for industrial and process cooling. The units use the natural refrigerant R290 (GWP 3, ODP 0) and an evaporator mounted inside the storage tank. The hydraulic circuit is non-ferrous, so fluids aggressive to carbon steel can be handled. Outlet water runs from 0 to +30 °C and ambient from +5 to +45 °C.

The technical table lists models IC03n, IC05n, IC08n and IC10n. At 12/7 °C water and 35 °C air, nominal capacity is 1.19, 1.83, 2.21 and 2.98 kW with EER from 2.81 to 2.72. At 20/15 °C water and 25 °C air, capacity is 1.71-4.37 kW and EER 4.86-4.33. Supply is 230 V single phase, sound pressure 46-47 dB(A) and tank volume 15 or 22 litres.

R290 is flammable (class A3), so a DSEAR risk assessment is required before siting. The sheet also states that the refrigerant charge complies with IEC 60335-2-89 and that all models meet ErP SEPR HT Tier 2. Data are declared per EN 14511:2018.

The series is aimed at process cooling, not data centres, and capacities are very small. For a data-centre designer the interest is as an example of a small natural-refrigerant chiller and the constraints of flammable refrigerants.

Key points

  1. Refrigerant R290 (GWP 3, ODP 0); flammability class A3, DSEAR risk assessment required before siting.
  2. Series capacity is presented as 1.7-4.4 kW.
  3. IC03n-IC10n give 1.19, 1.83, 2.21 and 2.98 kW at 12/7 °C water and 35 °C air.
  4. At 20/15 °C water and 25 °C air, capacity is 1.71-4.37 kW with EER 4.86-4.33.
  5. EER at 12/7 °C is 2.81-2.72; SEPR HT 5.01-5.14.
  6. Outlet water 0 to +30 °C, ambient +5 to +45 °C; delta T up to 10 °C.
  7. Tank volume 15 and 22 litres; evaporator inside the tank.
  8. Sound pressure 46-47 dB(A) free field at 10 m; operating weight 63-94 kg.

Using it in design

  • When selecting an R290 chiller for small process or laboratory loads, write the A3 flammability siting and ventilation risk assessment into the specification.
  • Compare the manufacturer's two nominal conditions (12/7 °C and 20/15 °C) with the project water temperatures and read capacity at the matching one.
  • With only 15-22 l of tank volume, check whether the load side needs extra buffer volume to limit temperature swings during short interruptions.
  • Glycol compatibility is up to 30%; use that limit for outdoor installations with freeze risk.
  • Note that the capacity range is too small for main data-centre cooling; limit use to auxiliary systems.

Who should read it

Mechanical designers choosing small process or auxiliary chillers and those exploring natural-refrigerant options.

Document contents

  1. Industries and leading benefits
  2. Unique evaporator-in-tank
  3. Features
  4. Specification table
  5. Option kits

Publication details

Authors
ICS Cool Energy
Publisher
ICS Cool Energy
Year
2023
Document number
i-Chiller Compact-n_2023; 05/23 v3
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ICS Cool Energy (2023). ICS Cool Energy i-Chiller Compact-n, 05/23 v3, printed p.5. ICS Cool Energy. i-Chiller Compact-n_2023; 05/23 v3. https://www.icscoolenergy.com/wp-content/uploads/sites/3/2024/04/i-Chiller-Compact-n-2023-v2.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.